Plan Review Details - Permit 21040709
Plan Review Stops For Permit 21040709
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-08-04 Cont ID  
Sent By rmcphers Date 2021-08-04 Time 17:01 Rev Time 0.00
Received By rmcphers Date 2021-08-04 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-30 Cont ID  
Sent By rmcphers Date 2021-07-30 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2021-07-30 Time 11:14 Sent To  
Notes
2021-07-30 11:17:13VEHICLE CHARGING STATIONS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ONE OF THE CHARGING STATION PARKING SPACES MUST HAVE
 A SIGN AND BE MARKED ACCESSIBLE - FBC ACCESSIBILITY
 502.6.1
 EACH SUCH PARKING SPACE MUST BE STRIPED IN A MANNER
 THAT IS CONSISTENT WITH THE STANDARDS OF THE
 CONTROLLING JURISDICTION FOR OTHER SPACES AND
 PROMINENTLY OUTLINED WITH BLUE PAINT, AND MUST BE
 REPAINTED WHEN NECESSARY, TO BE CLEARLY DISTINGUISHABLE
 AS A PARKING SPACE DESIGNATED FOR PERSONS WHO HAVE
 DISABILITIES. THE SPACE MUST BE POSTED WITH A PERMANENT
 ABOVE-GRADE SIGN OF A COLOR AND DESIGN APPROVED BY THE
 DEPARTMENT OF TRANSPORTATION, WHICH IS PLACED ON OR AT
 LEAST 60 INCHES (1525 MM) ABOVE THE FINISHED FLOOR OR
 GROUND SURFACE MEASURED TO THE BOTTOM OF THE SIGN AND
 WHICH BEARS THE INTERNATIONAL SYMBOL OF ACCESSIBILITY
 AND THE CAPTION "PARKING BY DISABLED PERMIT ONLY." SUCH
 A SIGN, ERECTED AFTER OCTOBER 1, 1996, MUST INDICATE
 THE PENALTY FOR ILLEGAL USE OF THE SPACE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2021-07-23 Time 14:56 Sent To  
Notes
2021-07-23 15:02:20VEHICLE CHARGING STATIONS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) UNABLE TO DETERMINE IF THERE ARE DOUBLE STRIPES AND
 OR THE WIDTH OF THE DOUBLE STRIPE - AS I STATED IN THE
 MEETING 12' IS THE SIZE THAT SHOULD BE SHOWN FOR THE
 WIDTH OF THE ACCESSIBLE PARKING SPACE - THE 5' ACCESS
 AISLE DIMENSION IS SHOWN FROM OUT SIDE OF STRIPES -
 SHOULD BE TO THE CENTER OF DOUBLE STRIPES - FBC 406.1.7
 - PLEASE SHOW THE WIDTH OF THE PARKING SPACE AND THE
 ACCESS AISLE TO COMPLY WITH FBC ACCESSIBILITY CHAPTER
 5.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 10:31 Rev Time 0.00
Received By rmcphers Date 2021-06-17 Time 10:31 Sent To  
Notes
2021-06-17 10:32:57VEHICLE CHARGING STATIONS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW - NO CHANGES
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 406.1.7 - PLEASE SHOW THE WIDTH OF THE PARKING
 SPACE AND THE ACCESS AISLE TO COMPLY WITH FBC
 ACCESSIBILITY CHAPTER 5.
 2) CANNOT HAVE A BOLLARD IN THE MIDDLE OF THE
 ACCESSIBLE ACCESS AISLE.
 3) PLEASE SHOW THE CLEAR FLOOR SPACE NEXT TO THE
 CHARGING STATION PER FBC A309.2
  
 FYI = YOU ARE ADDING AN "ELEMENT" (CHARGING STATION) TO
 THE PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN
 ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO
 COMPLY WITH 2020 FBC ACCESSIBILITY - SEE CODE SECTIONS
 BELOW.
  
 106.1 ELEMENT. AN ARCHITECTURAL OR MECHANICAL COMPONENT
 OF A BUILDING, FACILITY, SPACE, OR SITE.
  
 201.4SCOPE OF COVERAGE.
 THIS CODE APPLIES TO FIXED OR BUILT-IN ELEMENTS OF
 BUILDINGS, STRUCTURES, SITE IMPROVEMENTS AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE. UNLESS
 SPECIFICALLY STATED OTHERWISE, ADVISORY NOTES, APPENDIX
 NOTES AND FIGURES CONTAINED IN THE CODE EXPLAIN OR
 ILLUSTRATE THE REQUIREMENTS; THEY DO NOT ESTABLISH
 ENFORCEABLE REQUIREMENTS.
  
 202.3ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING
 PARKING.
  
 206.2.2WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 228DEPOSITORIES, VENDING MACHINES, CHANGE MACHINES,
 MAIL BOXES, AND FUEL DISPENSERS
 228.1 GENERAL.
 WHERE PROVIDED, AT LEAST ONE OF EACH TYPE OF
 DEPOSITORY, VENDING MACHINE, CHANGE MACHINE, AND FUEL
 DISPENSER SHALL COMPLY WITH 309.
  
 309 OPERABLE PARTS
  
 309.1GENERAL.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
  
  
  
 ADD THIS STOP FOR ADA REQUIREMENTS IF NEEDED,, JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-06-01 Time 11:22 Rev Time 0.00
Received By rmcphers Date 2021-06-01 Time 11:00 Sent To  
Notes
2021-06-01 11:19:10VEHICLE CHARGING STATIONS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 406.1.7 - PLEASE SHOW THE WIDTH OF THE PARKING
 SPACE AND THE ACCESS AISLE TO COMPLY WITH FBC
 ACCESSIBILITY CHAPTER 5.
 2) CANNOT HAVE A BOLLARD IN THE MIDDLE OF THE
 ACCESSIBLE ACCESS AISLE.
 3) PLEASE SHOW THE CLEAR FLOOR SPACE NEXT TO THE
 CHARGING STATION PER FBC A309.2
  
 FYI = YOU ARE ADDING AN "ELEMENT" (CHARGING STATION) TO
 THE PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN
 ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO
 COMPLY WITH 2020 FBC ACCESSIBILITY - SEE CODE SECTIONS
 BELOW.
  
 106.1 ELEMENT. AN ARCHITECTURAL OR MECHANICAL COMPONENT
 OF A BUILDING, FACILITY, SPACE, OR SITE.
  
 201.4SCOPE OF COVERAGE.
 THIS CODE APPLIES TO FIXED OR BUILT-IN ELEMENTS OF
 BUILDINGS, STRUCTURES, SITE IMPROVEMENTS AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE. UNLESS
 SPECIFICALLY STATED OTHERWISE, ADVISORY NOTES, APPENDIX
 NOTES AND FIGURES CONTAINED IN THE CODE EXPLAIN OR
 ILLUSTRATE THE REQUIREMENTS; THEY DO NOT ESTABLISH
 ENFORCEABLE REQUIREMENTS.
  
 202.3ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING
 PARKING.
  
 206.2.2WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 228DEPOSITORIES, VENDING MACHINES, CHANGE MACHINES,
 MAIL BOXES, AND FUEL DISPENSERS
 228.1 GENERAL.
 WHERE PROVIDED, AT LEAST ONE OF EACH TYPE OF
 DEPOSITORY, VENDING MACHINE, CHANGE MACHINE, AND FUEL
 DISPENSER SHALL COMPLY WITH 309.
  
 309 OPERABLE PARTS
  
 309.1GENERAL.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
  
  
  
2021-05-20 15:52:15ADD THIS STOP FOR ADA REQUIREMENTS IF NEEDED,, JLEAHY

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-07-30 Cont ID  
Sent By jleahy Date 2021-07-30 Time 12:00 Rev Time 0.00
Received By jleahy Date 2021-07-30 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-22 Cont ID  
Sent By ppetty Date 2021-07-22 Time 13:26 Rev Time 0.00
Received By ppetty Date 2021-07-22 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-10 Cont ID  
Sent By equinone Date 2021-06-10 Time 14:18 Rev Time 0.00
Received By equinone Date 2021-06-10 Time 14:18 Sent To  
Notes
2021-06-10 14:18:31PAPER DRAWINGS SUBMITTED WITH ORIGNAL SEAL AND
 SIGNATURE. ROUTED TO STORAGE. EQ

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By jleahy Date 2021-05-20 Time 15:52 Rev Time 0.00
Received By jleahy Date 2021-05-20 Time 11:46 Sent To  
Notes
2021-05-20 15:56:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-600
  
 1) TRANSFORMER ON FOURTH FLOOR HAS A GEC LABELED #7
 WHAT IS IT GOING TO CONNECT TO?
  
 PAGE E-601
  
 !) LOAD CALCULATIONS FOR BOTH THE FEEDER AND BRANCH
 CIRCUITS SHALL BE FIGURED AT 125% PER 625.41 OF THE NEC
  
 2) PANEL CHS2 IS IT A MLO OR MCB?

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By aborngra Date 2021-05-17 Time 11:43 Rev Time 0.00
Received By aborngra Date 2021-05-17 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-30 Cont ID  
Sent By jleahy Date 2021-07-30 Time 12:01 Rev Time 0.00
Received By jleahy Date 2021-07-30 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 15:56 Rev Time 0.00
Received By rmcphers Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2021-06-10 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-06-01 Time 11:22 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 16:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-08-05 Cont ID  
Sent By rmcphers Date 2021-08-05 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2021-08-05 Time 12:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-07-23 Cont ID  
Sent By rmcphers Date 2021-07-23 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2021-07-23 Time 15:08 Sent To  
Notes
2021-07-23 15:09:16SIGNATURE REVIEW
 DRAWINGS ADDED TO PROJECTDOX ON 6/10/2021 DO NOT SHOW
 AS ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2021-06-17 Time 10:34 Sent To  
Notes
2021-06-17 10:35:56SIGNATURE REVIEW
 DRAWINGS ADDED TO PROJECTDOX ON 6/10/2021 DO NOT SHOW
 AS ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-06-01 Time 11:22 Rev Time 0.00
Received By rmcphers Date 2021-05-10 Time 06:19 Sent To  
Notes
2021-05-10 06:22:21ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME