Plan Review Details - Permit 21040677
Plan Review Stops For Permit 21040677
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By cpuell Date 2021-04-16 Time 10:50 Rev Time 0.00
Received By cpuell Date 2021-04-16 Time 10:50 Sent To  
Notes
2021-04-16 10:52:07PASSED - GUEST HOUSE WILL NEED IT'S OWN ADDRESS HOWEVER
 ACCORDING TO THE PLANS IT WILL BE APPLIED FOR BY A
 SEPARATE PERMIT. PLEASE REACH OUT TO [email protected] TO
 DISCUSS ADDRESSING OPTIONS FOR THE GUEST HOUSE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jgomez Date 2021-05-05 Time 11:21 Rev Time 0.00
Received By jgomez Date 2021-05-04 Time 09:44 Sent To  
Notes
2021-05-05 11:22:54NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040677
  
 1- ARCHITECTURAL PLANS AND NOTES ARE REFERENCING THE
 2017 FBC. THE NEW 2020 FBC 7TH EDITION WENT INTO EFFECT
 ON DECEMBER 31ST 2020. REVISE ALL ARCHITECTURAL
 DRAWINGS AND NOTES AS REQUIRED.
 CHAPTER 553 F.S.
  
 2- ENTRY DOOR DOESN'T COMPLY WITH THE MIN. DOOR CLEAR
 WIDTH OPENING OF 32" AS REQUIRED BY SEC. R311.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- MASTER BEDROOM WINDOW (B) AND BEDROOM #2 WINDOW (J).
 PROVIDE MANUFACTURER CUT SHEETS SHOWING THAT SPECIFIED
 CASEMENT WINDOW WIDTH SIZE (2'-8") COMPLIES WITH THE
 MIN. WIDTH CLEAR OPENING REQUIREMENT OF SEC. R310.2.1
 FBC-RESIDENTIAL.
 ALSO, CLARIFY WHY WINDOW SCHEDULE ONLY IDENTIFY THE
 BEDROOM #2 AS AN EGRESS WINDOW, WHILE WINDOW IN THE
 MASTER BEDROOM IS NOT. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE BOTTOM OF FORM SUBMITTED THAT THE
 BUILDING IS IN COMPLIANCE WITH THE CODE, AS PER SECTION
 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING THE
 PERMIT TO BEGIN CONSTRUCTION OR RENOVATION AS REQUIRED
 BY SEC. C103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION (THIS JURISDICTION NUMBER IS 604700).
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C)NUMBER OF BEDROOMS IS INCORRECT. (4 BEDROOMS, NOT 5).
 REVISE AS REQUIRED. SEE PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)ADJACENT WALL IN ITEM #10 (B) IS NOT CONCRETE BLOCK.
 SEE PLANS AND REVISE WALL TYPE AND INSULATION R-VALUE.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)REVISE ROOF TYPE ON PAGE 2 OF 5. THIS HOUSE HAS HIP
 AND GABLE END ROOFS NOT JUST HIP ROOFS. SEE PLANS AND
 REVISE. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 5- PIZZA OVEN:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE 48" WOOD BURNING PIZZA OVEN AND
 CHIMNEY. SEC. R1003 FBC-RESIDENTIAL. SEC. 107.2.1.2
 CITY AMENDMENTS.
 NOTE: SPECIFY THE HEIGHT TERMINATION OF ALL CHIMNEYS
 SHOWN ON PLANS.
  
 B) PROVIDE MANUFACTURER SPECS FOR THE PIZZA OVEN FOR
 HOUSEHOLD USE. SEC. M1901.2 FBC-RESIDENTIAL.
  
 6- PROVIDE CLEAR SPECIFICATIONS FOR THE GARAGE DOOR
 LEADING TO THE INTERIOR OF THE HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PROPOSED FACTORY BUILT FIREPLACE SHOWING COMPLIANCE
 WITH SEC. R1004 FBC-RESIDENTIAL AND FACTORY BUILT
 CHIMNEY SHOWING COMPLIANCE WITH SEC. R1005
 FBC-RESIDENTIAL
 NOTE: ARCHITECT TO REVIEW AND APPROVE IN WRITING PRIOR
 TO SUBMITTAL TO THIS OFFICE.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY GUARDRAIL SHOWN ON THE EXTERIOR ELEVATION. SHOW
 COMPLIANCE WITH SEC. R312.1 FBC-RESIDENTIAL.
 HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: PROVIDE
 SHOP DRAWINGS REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE STAIRWAY. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- SPECIFY ATTIC ACCESS AND LOCATION IN ALL ROOF AREAS
 IN FIRST AND SECOND FLOOR AS REQUIRED BY SEC. R807
 FBC_RESIDENTIAL.
  
 11- ROOF FRAMING PLAN ON SHEET S3 SHOWS A HIP TRUSS
 GOING THRU THE PIZZA OVEN CHIMNEY LOCATED IN THE REAR
 LOGGIA. REVISE CLARIFY FRAMING IN THIS AREA. SEC.
 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH ITEM #5 ABOVE.
  
 12- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 IN THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 PROVIDE PRODUCT APPROVAL. IF SPECIFYING SCREWS, THEN
 SPECIFY SCREW SIZE AND NUMBER OF SCREWS.
  
 13- PROVIDE COMPLETE PRODUCT APPROVALS AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE.
  
 B)ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 C)ENTRY DOOR.
  
 D)CASEMENT WINDOWS.
  
 E)DOOR AND WINDOW MULLIONS AS HOWN ON PLANS. NOTE:
 CLEARLY SPECIFY SIZE OF ALL MULLIONS FOR DOORS AND
 WINDOWS ASSEMBLIES SHOWN ON PLANS.
  
 F)DOOR SLIDER #107 AS SHOWN ON PLANS.
  
 G)STOREFRONT SYSTEMS AS SHOWN ON PLANS.
  
 H)FIXED WINDOWS.
  
 I)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 J)PATIO DOORS
  
 K) FLAT ROOF ABOVE MASTER BATHROOM. AND, CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 14-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS (NOT SIGNING AND SEALING)AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- NEED TO GET PERMIT FOR THE DEMOLITION OF EXISTING
 HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By equinone Date 2021-04-26 Time 09:48 Rev Time 0.00
Received By equinone Date 2021-04-26 Time 09:48 Sent To  
Notes
2021-04-26 09:49:24CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET E101 ELECTRICAL PLAN: ELECTRICAL NOTE NO. 6.
 REFERENCES TO CODES ARE OUTDATED. PLEASE SEE BELOW FOR
 CURRENT CODES AND UPDATE NOTE TO REFLECT THEM.
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 1) SHEET E-2.01 ELECTRICAL PLAN: ELECTRICAL NOTE 5.
 CURRENT FLORIDA ENERGY CODE 2020 7TH EDITION REQUIRES
 THAT:
  
 "R 404.1 NOT LESS THAN 90 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY
 OF AT LEAST 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS
 WITH AN EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT."
  
 PLEASE UPDATE NOTE TO REFLECT NEW CODE REQUIREMENTS
  
 2) SHEET E-2.01 ELECTRICAL PLAN (FEEDER SIZES): FEEDER
 NO. 2 (3#2/0, 1#4 CU) IS TOO SMALL. PLEASE INCREASE TO
 NEXT SIZE (#3/0 CU) MINIMUM. NEC 240.4(B)(2)
  
 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT
 SERVICE EQUIPMENT AND PANELS. FBC 107
  
 4) A MINIMUM OF ONE COMMUNICATION OUTLET SHALL BE
 INSTALLED AS PER NEC 800.156 (A NOTE WILL SUFFICE)
  
 5) SHEET E-2.01 ELECTRICAL PLAN: ELECTRICAL NOTES MAKE
 REFERENCES TO NEC 2014 AND FBC 2014. PLEASE UPDATE CODE
 REFERENCES ON ALL DRAWINGS AND NOTES TO REFLECT NEW
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 6) FUTURE GENERATOR WILL REQUIRE SEPARATE PERMIT FBC
 107.
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By parking Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By tklarge Date 2021-04-27 Time 13:40 Rev Time 0.00
Received By tklarge Date 2021-04-27 Time 06:26 Sent To  
Notes
2021-04-27 06:36:521) SHT. P-1.02 - NOTE #7 REFERS TO THE TRACER WIRE
 BEING HELD TO THE TOP OF THE GAS PIPE. THE TRACER WIRE
 IS NOT PERMITTED TO TOUCH THE PE PIPE PER FBC-FUEL GAS
 SEC.404.17.3.
 2) ALL GAS EQQUIPMENT SHALL BE LISTED AND LABELED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT BEING INSTALLED AT THIS TIME. FBC-FUEL GAS
 SEC.301.3.
 3) THE GAS DRYER MAKEUP AIR SHALL COMPLY WITH FBC-FUEL
 GAS SEC.614.6.
 4) THE TANKLESS WATER HEATERS HALL BE INSTALLED A
 MINIMUM OF 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER
 THE MANUFACTURER'S INSTALLATION MANUAL. THE DISTANCE TO
 SOFFIT VENNTS SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION MANUAL.
 5) THE 1 1/4 INCH SCH. 40 PIPE ON THE LOW PRESURE
 SYSTEM IS UNDERSIZED. A MAXIMUM OF 322,000 BTU'S SHALL
 BE SUPPLIED BY A 1- 1/4 INCH SCH. 40 METALLIC PIPE PER
 FBC-FUEL GAS TABLE 402.4 (2) AT 143 FEET LENGTH.
 6) THE CSST SECTIONS OF PIPE ARE UNDERSIZED. A MXXIMUM
 OF 320,000 BTU'S SHALL BE SUPPLIED BY A CSST LINE WITH
 AN EHD OF 46 AT A DEVELOPED LENGTH OF 143 FEET PER
 FBC-FUEL GAS TABLE 402.4.(15).
 7) THE 3/4- INCH SCH. 40 LINE LINE TO THE RANGE IS
 UNDERSIZED . THE MINIMUM SIZE LINE SHALL COMPLY WITH
 FBC-FUEL GAS TABLE 402.4 (2).
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE GAS SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-14 Cont ID  
Sent By jgomez Date 2021-05-14 Time 10:39 Rev Time 0.00
Received By jgomez Date 2021-04-13 Time 10:35 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-05-04 Cont ID  
Sent By jgomez Date 2021-05-04 Time 10:14 Rev Time 0.00
Received By jgomez Date 2021-05-04 Time 10:14 Sent To  
Notes
2021-05-04 10:15:18IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By medwards Date 2021-04-26 Time 12:57 Rev Time 0.00
Received By medwards Date 2021-04-26 Time 12:57 Sent To  
Notes
2021-04-26 12:59:17 
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040677
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECS FOR THE KITCHEN RANGE AND HOOD.
 FBC RES M1503.4
  
 2) PLEASE PROVIDE DETAILS ABOUT THE MUA UNIT FOR THE
 KITCHEN. FBC 107.2.1
  
 3) PLEASE SHOW THE CONDENSATE LINES FOR EACH UNIT AND
 WHERE IT TERMINATES OUTDOORS. FBC M 307.2.1
  
 4) PLEASE PROVIDE SPECS. FOR THE PIZZA OVEN. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By tklarge Date 2021-04-27 Time 06:46 Rev Time 0.00
Received By tklarge Date 2021-04-23 Time 06:01 Sent To  
Notes
2021-04-27 05:53:311) THE PLANS REFER TO THE THE 2017 FBC. THE PLANS SHALL
 BE DESIGNED UNDER THE 2020 FBC WWHICH WENT INTO EFFECT
 DECEMBER 31, 2020. REVISE THE NOTE ON ALL AFFECTED
 SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER DETAIL ON SHT. P-1.01.
 3) SHT. P-1.01 - THE SOIL STACK FOR THE SECOND FLOOR
 BATH #2 SHALL NOT CONNECT TO THE FIRST FLOOR BRANCH
 DRAIN BETWEEN THE WATER CLOSET AND THE
 LAVATORY.FBC-PLUMBING SEC. 912.1.
 4) SHT. C-1 - WHERE ARE THE AREA DRAINS DISCHARGING?
 THE DISCHARGE SHALL CCOMPLY WITH FBC-PLUMBING
 SEC.1101.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jgomez Date 2021-05-05 Time 11:24 Rev Time 0.00
Received By jgomez Date 2021-05-05 Time 11:23 Sent To  
Notes
2021-05-05 11:26:22ROOFING REVIEW COMMENTS:
  
 1- PROVIDE COMPLETE PRODUCT APPROVALS AS REQUIRED BY
 FAC 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE.
  
 B)ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 C) FLAT ROOF ABOVE MASTER BATHROOM. AND, CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL THE PRODUCT APPROVALS (NOT SIGNING AND SEALING)AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-05 Cont ID  
Sent By jgomez Date 2021-05-05 Time 12:54 Rev Time 0.00
Received By jgomez Date 2021-05-05 Time 12:54 Sent To  
Notes
2021-05-05 10:39:08**8SIGNATURE REVIEW: SOIL TESRT REPROT OFIGINAL
 SEAL/SIGNARUE OR DIGITAL. ARCH PRODUCT APPROVASL LETTER

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By awooten Date 2021-05-12 Time   Rev Time  
Received By awooten Date 2021-05-12 Time   Sent To  
Notes
2021-05-12 15:28:36***************ZONING REVIEW FAILED*******************
  
 SIDE SIDE SETBACKS ON SITE PLAN DO NOT MATCH THE
 INFORMATION TABLE.
  
 NEW SINGLE FAMILY RESIDENTIAL DEVELOPMENTS REQUIRE A
 SEPARATE LANDSCAPE PLAN SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 DIMENSION THE OVERHANG, IT CANNOT EXCEED 3 FEET.
  
 SEPARATE PERMIT REQUIRED FOR FENCES/WALLS, GENERATORS,
 IRRIGATION, POOLS, DRIVEWAYS AND LANDSCAPING.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  