| Plan Review Stops For Permit 21040675 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-15 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-15 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-10 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-10 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2021-06-10 13:55:42 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [NOT RESOLVED.] SUBMIT A SURVEY SHOWING THE LOCATION | | | OF THE POOL AND EQUIPMENT. SEE ZONING COMMENTS. FBC | | | 107.2.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-05-20 |
Time |
21:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-05-20 |
Time |
21:28 |
Sent To |
|
|
| Notes |
| 2021-05-20 21:33:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT A SURVEY SHOWING THE LOCATION OF THE POOL AND | | | EQUIPMENT. SEE ZONING COMMENTS. FBC 107.2.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-06-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-04 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-04 |
Time |
15:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2021-05-11 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2021-05-11 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2021-05-11 10:03:09 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.VALUE OF ELECTRICAL NOT IN CONTRACT. | | | 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER | | | | | | 561-805-6742 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-06-23 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-06-23 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-06-17 |
Time |
09:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-10 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-05-25 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-05-20 |
Time |
21:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-04-30 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-05-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-28 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-28 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2021-05-28 10:06:33 | 05/28/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-04 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-04 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2021-05-04 08:41:03 | 05/04/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR | | | THE MAXIMUM SYSTEM FLOW. THE TDH CALCULATIONS MUST | | | INCLUDE ALL THE SYSTEM COMPONENTS, INCLUDING SUCTION | | | AND RETURN PIPING, FITTINGS, VALVES, HEATER, AND | | | FILTER. ALL SYSTEM COMPONENTS EXCEPT THE PUMP. | | | | | | 2. PLEASE THE POOL PUMP CURVE. IDENTIFY ON THE PUMP | | | CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING | | | INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE | | | MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE | | | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. INDICATE | | | ON THE PUMP CURVE WHICH CURVE KEY IS FOR THE PUMP BEING | | | INSTALLED ON THIS SYSTEM PER THE WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR | | | THE HEATER, FILTER, AND PUMP PER THE WPB AMENDMENTS TO | | | FBC SEC. 107.2.1. | | | | | | 4. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY | | | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT | | | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR | | | OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2017 | | | FBC- ENERGY- SEC. R 403.10.3. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-15 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-15 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-06-10 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-10 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2021-06-10 13:40:42 | [STILL UNABLE TO VERIFY THE ENGINEER'S SIGNATURE. | | | INCLUDING THE ONES IN THE SIGNATURE FOLDER. THE | | | DIGITALLY SIGNED DRAWINGS CAN NOT BE MODIFIED IN ANY | | | WAY FROM WHEN THEY ARE DIGITALLY SIGNED BY THE | | | ENGINEER, INCLUDING ROTATING THE DRAWINGS OR PRINTING, | | | SCANING AND THEN UPLOADING THEM.] UNABLE TO VERIFY THE | | | ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED | | | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR | | | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE | | | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF | | | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN | | | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15 | | | | | | | | 2021-06-04 16:02:42 | ELECTRICAL SIGNATURE IS GOOD JLEAHY |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-05-20 |
Time |
21:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-05-20 |
Time |
21:30 |
Sent To |
|
|
| Notes |
| 2021-05-20 21:31:17 | UNABLE TO VERIFY THE ENGINEER'S DIGITAL SIGNATURE. | | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | | YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 & | | | 61G15 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-06-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2021-06-22 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-06-09 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2021-06-09 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-06-09 11:26:25 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 6/9/21 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ON THE CORRECT SURVEY, MARK THE PROPOSED POOL | | | SHOWING THE SETBACKS TO ALL PROPERTY LINES. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-14 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-05-14 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-05-14 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-05-14 11:53:27 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 5/14/2021 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. THE SUBMITTED SURVEY DOES NOT MATCH THE EXISTING | | | PROPERTY, PLEASE SUBMIT AN UPDATED SURVEY SHOWING THE | | | EXISTING CONDITIONS OF THE PROPERTY PRIOR TO OBTAINING | | | ZONING APPROVAL. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | | [email protected] AND REQUEST TO HAVE YOUR | | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | | ARE FINISHED UPLOADING. | | | | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | W: WPB.ORG | | | |
|
|