Plan Review Details - Permit 21040660
Plan Review Stops For Permit 21040660
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By cpuell Date 2021-04-16 Time 16:11 Rev Time 0.00
Received By cpuell Date 2021-04-16 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 08:10 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 16:18 Sent To  
Notes
2022-07-07 08:10:37LETTER FROM CONTRACTOR TO RB ON 6/30/2022, PLEASE
 REVOKE PERMIT. OWNERS DO NOT WANT TO PROCEED. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 14:27 Rev Time 0.00
Received By cthroop Date 2022-04-19 Time 12:37 Sent To  
Notes
2022-04-22 14:34:04PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. CORRECTED
  
 2. CORRECTED
  
 3. CORRECTED
  
 4. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 APPLIED INSULATION. DESIGNER SHALL IDENTIFY SYSTEM TO
 BE INSTALLED. (NOT SUBMITTED FOR REVIEW)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NEW COMMENTS:
  
 PLACE THE FOLLOWING INFORMATION ON GARAGE FLOOR PLAN,
 PG A1.1 NEXT TO EACH FV:
  
 FV MODEL 1540-520
 NET 122.1 SQ/IN = 200 SF COVERAGE
 EACH GARAGE IS 498 SF
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-01-07 Cont ID  
Sent By cthroop Date 2022-01-07 Time 14:12 Rev Time 0.00
Received By cthroop Date 2022-01-06 Time 17:11 Sent To  
Notes
2022-01-07 14:27:23PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN CRITERIA PER ARCHITECT OF RECORD (AOR) FOR
 PROPOSED STRUCTURE IS RISK FACTOR (1), EXPOSURE "D",
 ENCLOSED BUILDING.
 CORRECT BUILDING DATA ON COVER PAGE C-1 FROM EXPOSURE
 "C" TO EXPOSURE "D".
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. REFERENCE SITE PLAN SP1 FOR THE FOLLOWING: NOTE FOR
 EQUIPMENT ELEVATION USES NGVD DATUM.
 ALL DATUM SHALL BE IN NAVD 88. PLEASE CORRECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE INSTALLATION INSTRUCTIONS FOR SMART VENT
 PRODUCT APPROVAL FL5822-R8. ONLY THE COVER SHEET WAS
 SUBMITTED FOR REVIEW.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 APPLIED INSULATION. DESIGNER SHALL IDENTIFY SYSTEM TO
 BE INSTALLED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By cthroop Date 2021-09-23 Time 13:24 Rev Time 0.00
Received By cthroop Date 2021-09-07 Time 07:23 Sent To  
Notes
2021-09-07 13:36:35PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. REF. COVER PAGE FOR THE FOLLOWING COMMENT:
 GOVERNING CODES ARE THE FBC 2020 7TH ED WITH 2017 NEC.
 (NOT ADDRESSED)
  
 2. PROVIDE A BOUNDARY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 CORRECTED
  
 3. PROVIDE FINISHED FLOOR ELEVATION OF MAIN RESIDENCE
 AND GARAGE ON FLOOR PLAN AND/OR FOUNDATION PLAN.
 R322.2.1ELEVATION REQUIREMENTS.
 CORRECTED
  
 4. N/A
  
  
 5. SITE DRAINAGE PLAN-SEE PLAN PAGES C-1 AND C-2.
 CORRECTED
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 (RETAINING WALL UNDER PERMIT 21030567)
  
 6. PROVIDE A SOILS REPORT.
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6.
 CORRECTED
  
 7. REF. THE WINDOW AND DOOR SCHEDULE FOR THE FOLLOWING
 COMMENT: CORRECTED
 7A) PROVIDE DESIGN PRESSURES FOR EACH OPENING.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
 (NOT ADDRESSED)
  
 8. PRODUCT APPROVALS:
 8A) FL15438-R2 HAS EXPIRED. PROVIDE PRODUCT APPROVAL
 APPROVED UNDER THE 2020 FBC 7TH ED.
 (NOT ADDRESSED)
 8B) DESIGNER SHALL SELECT MODEL OF DOOR TO BE INSTALLED
 FROM FL15446-R2.
 (NOT ADDRESSED)
 8C) PROVIDE INSTALLATION INSTRUCTIONS FOR FL15446-1.
 CORRECTED
 8D) WINDOW SCHEDULE INDICATES SINGLE HUNG WINOWS SHALL
 BE INSTALLED. PROVIDE PRODUCT APPROVALS FOR SH WINDOWS.
  
 8E) SHOP DRAWINGS FOR 6' AND 10" HOLLOW CORE FLOORING
 IS DEFERRED. PROVIDE TO CITY INSPECTOR.
  
 NEW COMMENTS:
  
 9. PROVIDE PRODUCT APPROVALS FOR SMART VENTS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 10. PROVIDE ICC-ES REPORT FOR ICYNENE SPRAY FOQAM
 INSULATION. A COPY OF THIS SHALL BE IN THE FIELD FOR
 INSPECTION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 10:58 Rev Time 0.00
Received By cthroop Date 2021-06-25 Time 15:59 Sent To  
Notes
2021-06-28 12:31:17PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF. COVER PAGE FOR THE FOLLOWING COMMENT:
 GOVERNING CODES ARE THE FBC 2020 7TH ED WITH 2017 NEC.
  
 2. PROVIDE A BOUNDARY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE FINISHED FLOOR ELEVATION OF MAIN RESIDENCE
 AND GARAGE ON FLOOR PLAN AND/OR FOUNDATION PLAN.
 R322.2.1ELEVATION REQUIREMENTS.
  
 4. IDENTIFY LOCATION OF REQUIRED FLOOD OPENINGS ON
 GARAGE FOUNDATION PLANS. SEE COMMENTS UNDER NFIP
 REVIEW.
 R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
  
 5. PROVIDE A SITE DRAINAGE PLAN. DRAINAGE PERMIT
 21030567 HAS NOT BEEN REVIEWED OR APPROVED. NO FEES
 PAID TO DATE.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
  
 6. PROVIDE A SOILS REPORT.
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6.
  
 7. REF. THE WINDOW AND DOOR SCHEDULE FOR THE FOLLOWING
 COMMENT:
 7A) PROVIDE DESIGN PRESSURES FOR EACH OPENING.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 8. PRODUCT APPROVALS:
 8A) FL15438-R2 HAS EXPIRED. PROVIDE PRODUCT APPROVAL
 APPROVED UNDER THE 2020 FBC 7TH ED.
 8B) DESIGNER SHALL SELECT MODEL OF DOOR TO BE INSTALLED
 FROM FL15446-R2.
 8C) PROVIDE INSTALLATION INSTRUCTIONS FOR FL15446-1.
 8D) WINDOW SCHEDULE INDICATES SINGLE HUNG WINOWS SHALL
 BE INSTALLED. PROVIDE PRODUCT APPROVALS FOR SH WINDOWS.
 8E) PROVIDE PRODUCT APPROVALS FOR 6" AND 10" HOLLOW
 CORE PLANKS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-01 Cont ID  
Sent By jleahy Date 2021-06-01 Time 09:22 Rev Time 0.00
Received By jleahy Date 2021-06-01 Time 09:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-06-04 Cont ID  
Sent By lcrespo Date 2021-06-04 Time 11:22 Rev Time 0.00
Received By lcrespo Date 2021-06-04 Time 11:22 Sent To  
Notes
2021-06-04 11:24:53A GRILL IS SHOWN IN A COVERED PATIO AND IF NATURAL GAS
 OR A LP TANK IS CONNECTED IT WILL REQUIRE THE FOLLOWING
 BELOW;
  
 GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS AND OR HOOD PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 08:10 Rev Time 0.00
Received By cthroop Date 2022-05-05 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 15:00 Rev Time 0.00
Received By cthroop Date 2022-03-15 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-08 Cont ID  
Sent By cpuell Date 2022-01-08 Time 09:00 Rev Time 0.00
Received By cpuell Date 2021-11-15 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-09 Cont ID  
Sent By cthroop Date 2021-09-09 Time 13:29 Rev Time 0.00
Received By cthroop Date 2021-08-05 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 12:50 Rev Time 0.00
Received By cthroop Date 2021-05-20 Time 10:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-06-26 Cont ID  
Sent By cthroop Date 2021-06-26 Time 06:56 Rev Time 0.00
Received By cthroop Date 2021-06-26 Time 06:56 Sent To  
Notes
2021-06-26 06:57:28PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 11:11 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By medwards Date 2021-06-02 Time 16:19 Rev Time 0.00
Received By medwards Date 2021-06-02 Time 15:59 Sent To  
Notes
2021-06-02 16:19:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040660
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 2) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
 THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB.
  
 I WILL REVIEW THE DRAWINGS ONCE THE ENGINEER HAS
 APPROVED AND DIGITALLY SIGNED THEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 6 Status N Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 08:08 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 16:18 Sent To  
Notes
2022-07-07 08:09:55LETTER FROM CONTRACTOR TO RB ON 6/30/2022, PLEASE
 REVOKE PERMIT. OWNERS DO NOT WANT TO PROCEED. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status F Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 13:47 Rev Time 0.00
Received By cthroop Date 2022-04-19 Time 12:37 Sent To  
Notes
2022-04-22 13:40:13PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 5TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 SEE 4TH REVIEW COMMENTS BELOW:
  
 1) A1. CORRECTED
 2) A2. CORRECTED
 3) A5. CORRECTED
  
 4) A9. THE LOCATIONS, SIZE AND TYPE OF FLOOD VENTS NEED
 TO BE SHOWN ON THE FLOOR PLANS.
 PLACE THE FOLLOWING INFO ON GARAGE FLOOR PLAN, PG A1.1
 NEXT TO EACH FV:
  
 FV MODEL 1540-520
 NET 122.1 SQ/IN = 200 SF COVERAGE
 EACH GARAGE IS 498 SF
  
 5) A9(C). CORRECTED
 6) C2. CORRECTED
 7) C2(E) CORRECTED
  
 8) C2(F) & (G) THE LOWEST ADJACENT GRADE APPEARS TO BE
 5.92 FT AT THE ATTACHED GARAGE AND THE HIGHEST ADJACENT
 GRADE APPEARS TO BE 7.5 FT. AT THE FRONT OF THE
 RESIDENCE.
 DATA ENTERED FOR LINE C2 (F) IS 5.0 FT AND DATA ENTERED
 FOR LINE C2 (G) IS 7.0 FT.
 SEE PLAN PAGE C-1 FOR ELEVATION DATA FOR C2(F) 5.9 2FT
 & (G) 7.5 FT
  
 9) CORRECTED
 10) CORRECTED
  
 NEW COMMENTS:
  
 11) INCLUDE THE FOLLOWING INFORMATION IN THE COMMENTS
 AREA OF SECTION D:
  
 FV MODEL 1540-520
 NET 122.1 SQ/IN = 200 SF COVERAGE
 EACH GARAGE IS 498 SF
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 10:29 Sent To  
Notes
2022-01-13 09:19:45NFIP PEER REVIEW STATUS IS DENIED.
 THE FOLLOWING CORRECTIONS ARE REQUIRED.
  
 1) A1. THE CURRENT OWNERS NAME IS 3010 FLAGLER LLC.
 2) A2. THE ZIP CODE IS 33407.
 3) A5. THE NEGATIVE SIGN AND W ARE BOTH GIVEN FOR
 LONGITUDE. SINCE YOU USED THE DIRECTION N FOR THE
 LATITUDE TO BE CONSISTANT USE W FOR LONGITUDE AND
 REMOVE THE NEGATIVE SIGN.
 4) A9. THE LOCATIONS, SIZE AND TYPE OF FLOOD VENTS NEED
 TO BE SHOWN ON THE FLOOR PLANS.
 5) A9(C). IF YOU ARE USING THE ENGINEERED SMART VENTS
 WHICH MEASURE 15-3/4" X 7-3/4", THEN EACH OPENING IS
 122.1 SQUARE INCHES. THE TOTAL FOR SIX IS 732.6 SQUARE
 INCHES. FEMA'S ELEVATION CERTIFICATE INSTRUCTIONS
 ALLOWS THIS WHEN THE NET AREA OF THE FLOOD VENTS CAN
 NOT BE REASONABLY ESTIMATED. THE TYPE OF VENT AND
 COVERAGE CAN BE INDICATED IN THE COMMENT SECTION.
 6) C2. THE BENCH MARK UTILIZED SHOULD BE THE PID OR
 OTHER UNIQUE IDENTIFIER ASSIGNED BY THE MAINTAINER OF
 THE BENCHMARK. THE VERTICAL SHOULD BE NAVD 88.
 7) C2(E) THE ELEVATIONS OF THE GENERATOR AND A/C PADS
 NEED TO BE SHOWN ON THE CONSTRUCTION DRAWINGS.
 8) C2(F) & (G) THE LOWEST ADJACENT GRADE APPEARS TO BE
 5.92 FT AT THE ATTACHED GARAGE AND THE HIGHEST ADJACENT
 GRADE APPEARS TO BE 7.5 FT. AT THE FRONT OF THE
 RESIDENCE.
 9) IN SECTION D MARK YES OR NO TO THE QUESTION OF
 WHETHER OR NOT LAT. AND LONG. WERE PROVIDED BY A
 LICENSED LAND SURVEYOR.
 10) NOTES SHOULD BE ADDED TO THE PLANS FOR THE GARAGE
 TO SPECIFY THAT ALL MATERIALS INSTALLED BELOW THE
 DESIGN FLOOD ELEVATION SHALL BE FLOOD DAMAGE RESISTANT
 AND ALL EQUIPMENT IS TO BE ELEVATED ABOVE THE DFE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-01-11 Cont ID  
Sent By cthroop Date 2022-01-11 Time 09:42 Rev Time 0.00
Received By cthroop Date 2022-01-06 Time 17:11 Sent To  
Notes
2022-01-11 09:43:14SENT TO ROBBIE FOR PEER REVIEW. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-09-09 Cont ID  
Sent By cthroop Date 2021-09-23 Time 13:26 Rev Time 0.00
Received By cthroop Date 2021-09-07 Time 07:22 Sent To  
Notes
2021-09-09 13:28:57PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION A5. LATITIUDE AND LONGITUDE ARE INCORRECT.
 CORRECT AND RE-SUBMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 12:31 Rev Time 0.00
Received By cthroop Date 2021-06-25 Time 16:09 Sent To  
Notes
2021-06-28 12:50:41PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. DESIGN FLOOD
 ELEVATION SHALL BE 9.0 FEET NAVD.
  
 1. PROVIDE A CONSTRUCTION DRAWING ELEVATION CERTIFICATE
 (EC)
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 AE WITH BASE FLOOD ELEVATIONS (BFE) OF 6.0 FEET AND 7.0
 FEET NAVD. THE CITY OF WEST PALM BEACH (THROUGH CITY
 ORDINANCE NO. 4729-17) REQUIRES AN ADDITIONAL 24 INCHES
 OF FREEBOARD REQUIRING THE DESIGN FLOOD ELEVATION (DFE)
 TO BE 9. 0 FEET NAVD. PLEASE NOTE THIS INFORMATION ON
 YOUR PLANS.
  
 NOTICE:
  
 3 EC S REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 2. INDICATE THE FINISHED FLOOR ELEVATIONS OF THE MAIN
 RESIDENCE AND GARAGE ON THE FLOOR THE PLAN AND/OR
 FOUNDATIUON PLAN.
 R322.2.1ELEVATION REQUIREMENTS.
  
 3. FLOOD OPENINGS:
  
 1) PROVIDE FLOOD OPENINGS DESIGNED BY A DESIGN
 PROFESSIONAL PER R322.2.2 ENCLOSED AREA BELOW DESIGN
 FLOOD ELEVATION.
 2) SIGNATURE AND SEAL OF DESIGNER IS REQUIRED.
  
 ENGINEERED FLOOD VENTS:
  
 1) PROVIDE ENGINEERED FLOOD VENTS. (SMART VENTS)
 2) ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD
 VENT CERTIFICATION OR EVALUATION SERVICE REPORT ISSUED
 BY THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
 (ICC ES).
 3) PROVIDE FLORIDA PRODUCT APPROVALS OR MIAMI DADE
 NOA?S FOR PROPOSED SMART VENTS.
 4) FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 5) FLOOD OPENINGS SHALL BE INSTALLED PER
 R322.2.2.1INSTALLATION OF OPENINGS.
 6) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON
 FOUNDATION PLAN.
  
 FBC R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION
  
 NOTICE: EC PROVISO'S ON PLAN PAGES A1.0 AND A1.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-03 Cont ID  
Sent By lcrespo Date 2021-06-03 Time 08:45 Rev Time 0.00
Received By lcrespo Date 2021-06-03 Time 14:59 Sent To  
Notes
2021-06-09 08:47:0506/03/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2022-04-19 Cont ID  
Sent By cthroop Date 2022-04-19 Time 15:25 Rev Time 0.00
Received By cthroop Date 2022-04-19 Time 12:36 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2022-01-07 Cont ID  
Sent By cthroop Date 2022-01-07 Time 14:27 Rev Time 0.00
Received By cthroop Date 2022-01-06 Time 17:11 Sent To  
Notes
2022-01-07 15:29:41PLAN REVIEW ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THERE ARE THREE (3) ROOF TYPES PROPOSED:
 A) MODIFIED BITUMEN BUILT UP ROOF SYSTEM WITH TAPERED
 INSULATION OVER 5/8" PLYWOOD DECK. (PLAN PAGE A3.0)
 B) STANDING SEAM METAL ROOF OVER MODIFIED BITUMEN
 (SECONDARY WATER BARRIER) OVER 5/8" PLYWOOD DECK. (PLAN
 PAGE A3.1)
 C) 10" HOLLOW CORE PLANK WITH 2" CONCRETE TOPPING.(PLAN
 PAGE A3.0). WHITE COOL DECK FINISH. (PLAN PAGE A1.3)
 WHAT IS THE ROOF COVERING FOR THIS AREA?
  
 1.REFERENCE PLAN PAGE S2.0 FOR THE FOLLOWING:
 DESIGN CRITERIA PER ARCHITECT OF RECORD (AOR) FOR
 PROPOSED STRUCTURE IS RISK FACTOR (1), EXPOSURE "D",
 ENCLOSED BUILDING.
 SYSTEM W-1, SELECTED TO BE INSTALLED FROM PRODUCT
 APPROVAL FL16709-R7, PG. 6 OF 25, IS NOT APPROVED FOR
 EXPOSURE "D" ENCLOSED.
 SUBMIT A ROOFING SYSTEM APPROVED FOR EXPOSURE "D",
 ENCLOSED, 20-30FT MRH.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PROVIDE PRODUCT APPROVALS FOR STANDING SEAM METAL
 ROOFING.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. PROVIDE PRODUCT APPROVALS FOR TYPE (C) ROOF ABOVE.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By cthroop Date 2021-09-23 Time 13:18 Rev Time 0.00
Received By cthroop Date 2021-09-07 Time 07:23 Sent To  
Notes
2021-09-07 13:24:14PLAN REVIEW ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
 (NOT ADDRESSED)
  
 2. MAX DESIGN PRESSURE OF CERTAINTEED SBS AND APP
 MODIFIED BITUMEN ROOF SYSTEM IS -97.5. PROVIDE THE
 DESIGN PRESSURES OF ROOF ZONES 1, 2 AND THRE PER
 R301.2.1.1.
 PROVIDE DESIGN PRESSURES PER FIGURE R301.2(7) COMPONENT
 AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
 (NOT ADDRESSED)
  
 NEW COMMENTS:
  
 3. PROVIDE PRODUCT APPROVALS FOR METAL ROOF.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE PRODUCT APPROVALS FOR DOUBLE ROOF HATCH AT
 3RD FLOOR.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-06-28 Cont ID  
Sent By cthroop Date 2021-06-28 Time 10:52 Rev Time 0.00
Received By cthroop Date 2021-06-25 Time 15:59 Sent To  
Notes
2021-06-28 10:58:05PLAN REVIEW ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. MAX DESIGN PRESSURE OF CERTAINTEED SBS AND APP
 MODIFIED BITUMEN ROOF SYSTEM IS -97.5. PROVIDE THE
 DESIGN PRESSURES OF ROOF ZONES 1, 2 AND THRE PER
 R301.2.1.1.
 PROVIDE DESIGN PRESSURES PER FIGURE R301.2(7) COMPONENT
 AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 NOTICE: SEE COMMENTS UNDER BUILDING REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status N Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 08:10 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 16:18 Sent To  
Notes
2022-07-07 08:10:15LETTER FROM CONTRACTOR TO RB ON 6/30/2022, PLEASE
 REVOKE PERMIT. OWNERS DO NOT WANT TO PROCEED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-22 Cont ID  
Sent By cthroop Date 2022-04-22 Time 15:00 Rev Time 0.00
Received By cthroop Date 2022-04-19 Time 12:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-01-07 Cont ID  
Sent By cthroop Date 2022-01-07 Time 11:41 Rev Time 0.00
Received By cthroop Date 2022-01-06 Time 17:11 Sent To  
Notes
2022-01-07 11:42:47SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 3RD REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 11:11 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 11:11 Sent To  
Notes
2021-08-19 11:16:39PLANS SUBMITTED APPEAR TO HAVE A COPY OF THE DIGITAL
 SIGNATURES ON THE MECHANICAL PLANS. PLEASE EITHER
 SUBMIT THE DRAWINGS WITH THE DIGITAL SIGNATURES OR YOU
 CAN BRING THE SIGNED AND SEALED PAPER DRAWINGS TO OUR
 OFFICE. C-1 AND C-2 HAVE A COPY OF THE SIGNED AND
 SEALED PAPER DRAWINGS. PLEASE PROVIDE THE ORIGINAL
 SIGNED AND SEALED PAPER DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By medwards Date 2021-06-02 Time 15:47 Rev Time 0.00
Received By medwards Date 2021-06-02 Time 15:47 Sent To  
Notes
2021-06-02 15:50:01THE ENGINEER SIGNATURE IS A COPY OF THEIR SIGNATURE.
 PLEASE PROVIDE THE ORIGINAL DIGITAL SIGNTURES FOR ALL
 DRAWINGS INCLUDING THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By vbroglia Date 2022-04-13 Time 09:24 Rev Time 0.00
Received By vbroglia Date 2022-04-13 Time 09:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-03-18 Cont ID  
Sent By vbroglia Date 2022-03-18 Time 14:36 Rev Time 0.00
Received By vbroglia Date 2022-03-18 Time 14:32 Sent To  
Notes
2022-03-18 14:36:063/18/2022 FAILED
  
 PLEASE APPLY FOR A LANDSCAPE PERMIT AND OBTAIN A PERMIT
 NUMBER TO ALLOW STAFF TO MOVE FORWARD WITH PERMIT
  
 PLEASE PROVIDE THE HEIGHT OF THE PROJECT STARTING FROM
 FINISHED GRADE, NOT FIRST FLOOR GRADE ON ELEVATION
 PLANS
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By RTHERMID Date 2021-06-22 Time   Rev Time  
Received By rthermid Date 2021-06-22 Time   Sent To I
Notes
***NONE***