Plan Review Details - Permit 21040637
Plan Review Stops For Permit 21040637
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2021-06-28 Time 08:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By rmcdouga Date 2021-05-13 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2021-05-13 Time 08:58 Sent To  
Notes
2021-05-13 09:25:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FOUNDATION/ANCHORING PLANS ARE NOT PART OF THE
 STATE APPROVED MODULAR BUILDING PLANS. SUBMIT ORIGINAL
 SIGNED AND SEALED FOUNDATION/ANCHORING PLANS. FBC
 AMENDMENTS 107.2.1
 2) SOME OF PLAN SHEETS THAT WERE SUBMITTED ARE NOT
 LEGIBLE. PLEASE SUBMIT CLEAR LEGIBLE PLANS. FBC
 AMENDMENTS 107.2.1.4
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2021-06-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By rmcdouga Date 2021-05-17 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2021-04-29 Time 09:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By rmcdouga Date 2021-06-28 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2021-06-28 Time 08:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By rmcdouga Date 2021-05-13 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2021-05-13 Time 08:59 Sent To  
Notes
2021-05-13 09:34:12THE FOUNDATION/ANCHORING PLAN THAT WAS SUBMITTED IS NOT
 AN ORIGINAL ELECTRONIC DOCUMENT WITH THE ENGINEER'S
 ORIGINAL DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-14 Cont ID  
Sent By rthermid Date 2021-05-14 Time   Rev Time 0.00
Received By rthermid Date 2021-05-14 Time   Sent To I
Notes
2021-05-14 10:42:42PASSED WITH PROVISO:
  
 SHED MUST BE LOCATED A MINIMUM OF 5 FEET FROM THE SIDE
 AND REAR PROPERTY LINES
  
 RAFAELA THERMIDOR
 ASSOCIATE PLANNER, 561-822-1443
 [email protected]
  