Plan Review Details - Permit 21040592
Plan Review Stops For Permit 21040592
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 17:24 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-08 Time 10:03 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 08:57 Sent To  
Notes
2021-06-07 10:06:03REVISED 06/08/21
  
 NEW DOCK BUILDING, SECOND REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040592
  
 1- OK
 2- OK
 3- OK
  
 ORIGINAL COMMENT:
 4- PROVIDE SIGNED/SEALED ENGINEERING FOR THE TWO
 BOAT-LIFT SPECIFIED ON PLANS. ENGINEER OF RECORD TO
 REVIEW AND APPROVE THEM PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 4(A)- BOAT LIFT ENGINEERING SUBMITTED SUBMITTED WAS NOT
 REVIEWED/APPROVED BY THE DOCK ENGINEER OF RECORD. IT
 NEEDS TO BE APPROVED BY THE ENGINEER OF RECORD. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 4(B) BOAT LIFT CAPACITY MARKED ON BOAT LIFT ENGINEERING
 SUBMITTED DOESN'T MATCH BOAT LIFT CAPACITY SPECIFIED BY
 THE DOCK ENGINEER OF RECORD ON SHEET 2. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 4(C)BOAT LIFT ENGINEERING SUBMITTED. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM WHEN SUBMITTING FOR PUBLIC
 RECORDS. FS 471 & 61G15
 YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF
 DRAWINGS WITH THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL.
  
 5- OK
  
 ORIGINAL COMMENT:
 6- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
 RESPONSE:
 06/07/21 PER ROBERT BROWN: OK TO USE THE SURVEY WITH
 THE PROPOSED DOCK JUST AS A REFERENCE AS LONG AS THE
 ENGINEER OF RECORD SHOWS SITE PLAN WITH PROPOSED DOCK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By jgomez Date 2021-04-28 Time 13:50 Rev Time 0.00
Received By jgomez Date 2021-04-28 Time 11:21 Sent To  
Notes
2021-04-28 13:54:35NEW DOCK BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040592
  
 1- DESIGN CRITERIA ON DOCK CONSTRUCTION NOTES ON SHEET
 #2 IS MISSING THE STRUCTURE WIND EXPOSURE. ENGINEER OF
 RECORD TO SPECIFY ALL THE WIND DESIGN DATA, INCLUDING
 THE ULTIMATE AND NOMINAL WIND LOADS AND WIND EXPOSURE.
 SEC. R301.1 FBC-RESIDENTIAL. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: THIS STRUCTURE IS LOCATED IN EXPOSURE D.
  
 2- ENGINEER OF RECORD TO SPECIFY THE DECKING FASTENING
 TO SHOW COMPLIANCE WITH THE SPECIFIED WIND DESIGN
 CRITERIA.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 3- ENGINEER PLANS NEED TO HAVE A TITLE BLOCK WITH ALL
 THE ENGINEER'S INFORMATION AS REQUIRED BY SEC.
 61G15-23.001(4) F.A.C.
  
 4- PROVIDE SIGNED/SEALED ENGINEERING FOR THE TWO
 BOAT-LIFT SPECIFIED ON PLANS. ENGINEER OF RECORD TO
 REVIEW AND APPROVE THEM PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS MAY BE SUBMITTED FOR REVIEW LATER AFTER THE
 PERMIT IS ISSUED BUT BEFORE INSTALLATION TO AVOID
 CONFLICTS/DELAYS.
  
 5- DOCK DRAWINGS: ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON
 THEM WHEN SUBMITTING FOR PUBLIC RECORDS.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF
 DRAWINGS WITH THE ENGINEER?S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
 6- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-15 Cont ID  
Sent By jleahy Date 2021-06-15 Time 14:01 Rev Time 0.00
Received By jleahy Date 2021-06-15 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-06-02 Cont ID  
Sent By jleahy Date 2021-06-01 Time 07:28 Rev Time 0.00
Received By jleahy Date 2021-05-27 Time 13:57 Sent To  
Notes
2021-06-01 07:28:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) NEED TO SHOW LOCATION OF PEDESTAL, IF ON DOCK THEN
 GFCI IS REQUIRED TO THE PEDESTAL. 555.3
  
 555.3 GROUND-FAULT PROTECTION. THE OVERCURRENT
 PROTECTIVE DEVICES THAT SUPPLY THE MARINA, BOATYARDS,
 AND COMMERCIAL AND NONCOMMERCIAL DOCKING FACILITIES
 SHALL HAVE GROUND-FAULT PROTECTION NOT EXCEEDING 30 MA.
  
 2) NEED TO SUBMIT CUTSHEET FOR PEDESTAL. 110.3
  
 3) THE USE OF EXPANSION FITTINGS WILL BE REQUIRED.
 352.44
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By jleahy Date 2021-04-29 Time 12:15 Rev Time 0.00
Received By jleahy Date 2021-04-29 Time 12:02 Sent To  
Notes
2021-04-29 12:27:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SHOW WHERE MAIN IS TO SUBPANEL AND SEE IF IT
 COMPLIES WITH 555.3
  
 ELECTRICAL CONNECTION SHALL COMPLY WITH 555.9
  
 EQUIPMENT GROUNDING TO BE PER 555.15
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By rrossano Date 2021-05-12 Time   Rev Time 0.00
Received By rrossano Date 2021-05-12 Time   Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-24 Cont ID  
Sent By jleahy Date 2021-06-24 Time 10:43 Rev Time 0.00
Received By jleahy Date 2021-06-10 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 10:09 Rev Time 0.00
Received By jgomez Date 2021-05-25 Time 11:39 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 13:51 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 09:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 17:23 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 17:23 Sent To  
Notes
2021-06-15 14:02:22ELECTRICAL SIGNATURE IS GOOD JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 10:06 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 10:06 Sent To  
Notes
2021-06-07 10:07:44SIGNATURE REVIEW COMMENTS:
  
 1-- SURVEY WITH PROPOSED DOCK NEEDS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN
 SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. PROVIDE
 HARD COPY WITH ORIGINAL SEAL/SIGNATURE OR UPLOAD SURVEY
 WITH DIGITAL SIGNATURE.
  
 2- BOAT LIFT ENGINEERING SUBMITTED. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM WHEN SUBMITTING FOR PUBLIC
 RECORDS. FS 471 & 61G15
 YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF
 DRAWINGS WITH THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
2021-06-01 07:29:49ELECTRIC SIGNATURE IS GOOD. JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By jgomez Date 2021-04-28 Time 13:54 Rev Time 0.00
Received By jgomez Date 2021-04-28 Time 13:54 Sent To  
Notes
2021-04-28 13:55:48SIGNATURE REVIEW COMMENTS:
  
 1- DOCK DRAWINGS: ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON
 THEM WHEN SUBMITTING FOR PUBLIC RECORDS.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF
 DRAWINGS WITH THE ENGINEER?S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
 2- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By rthermid Date 2021-06-22 Time   Rev Time 0.00
Received By rthermid Date 2021-06-22 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-11 Cont ID  
Sent By rthermid Date 2021-05-11 Time   Rev Time  
Received By rthermid Date 2021-05-11 Time   Sent To I
Notes
***NONE***