Plan Review Details - Permit 21040514
Plan Review Stops For Permit 21040514
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-08-23 Cont ID  
Sent By jgomez Date 2021-08-23 Time 11:15 Rev Time 0.00
Received By jgomez Date 2021-08-23 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-10 Cont ID  
Sent By jgomez Date 2021-08-10 Time 13:52 Rev Time 0.00
Received By jgomez Date 2021-08-10 Time 11:26 Sent To  
Notes
2021-08-10 13:53:30RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040514
  
 1- OK
  
 ORIGINAL COMMENT:
 2-PROVIDE COMPLETE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. COMPLETE PRODUCT APPROVAL
 WAS NOT SUBMITTED.
 NOTE: IF PRODUCT APPROVAL IS A FLORIDA PRODUCT
 APPROVAL, THEN PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND COMPLETE CORRESPONDING SINGLE HUNG
 INSTALLATION DRAWINGS.
 IF THE PRODUCT APPROVAL IS A MIAMI DADE NOA, THEN
 PROVIDE COMPLETE NOA INCLUDING THE CORRESPONDING SINGLE
 HUNG INSTALLATION DRAWINGS.
  
 B)HORIZONTAL SLIDING WINDOWS AS SPECIFIED ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. COMPLETE PRODUCT APPROVAL
 WAS NOT SUBMITTED.
 NOTE: IF PRODUCT APPROVAL IS A FLORIDA PRODUCT
 APPROVAL, THEN PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND COMPLETE CORRESPONDING HORIZONTAL
 SLIDING WINDOWS INSTALLATION DRAWINGS.
 IF THE PRODUCT APPROVAL IS A MIAMI DADE NOA, THEN
 PROVIDE COMPLETE NOA INCLUDING THE CORRESPONDING
 HORIZONTAL SLIDING WINDOWS INSTALLATION DRAWINGS.
  
 C)HARDIE PLANK LAP SIDING AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. PROVIDE COMPLETE NOA. NOT JUST THE
 COVER PAGE.
  
 D)WINDOW MULLIONS:
 PROVIDE COMPLETE NOA. NOT JUST THE COVER PAGE.
  
 ORIGINAL COMMENT.
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 THIS WILL BE VERIFIED ONCE THE COMPLETE PRODUCT
 APPROVALS ARE UPLOADED TO PROJECTDOX.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 10:59 Rev Time 0.00
Received By jgomez Date 2021-07-06 Time 08:43 Sent To  
Notes
2021-07-06 08:49:58RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040514
  
 ORIGINAL COMMENT:
 1- DRAWINGS SUBMITTED ARE TOO SMALL AND ARE NOT
 LEGIBLE. DRAWINGS HAVE A COPY OF THE ARCHITECT'S
 DIGITAL SIGNATURE AND WERE REDUCED TO 8-1/2 X 11 PAGES.
 DRAWINGS NEED TO HAVE ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS
 AS REQUIRED BY 61G1-16.003 FAC. THERE ARE TWO WAYS TO
 SUBMIT THE DRAWINGS. ONE IS TO UPLOAD THE DRAWINGS TO
 PROJECTDOX WITH THE ARCHITECT'S DIGITAL SIGNATURE OR
 THE OTHER OPTIONS TO SUBMIT FULL SCALE DRAWINGS WITH
 THE ARCHITECT'S ORIGINAL SEAL/SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT. PLANS SUBMITTED ARE NOT SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD.
  
 ORIGINAL COMMENT:
 2-PROVIDE COMPLETE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. COMPLETE PRODUCT APPROVAL WAS NOT
 SUBMITTED.
  
 B)HORIZONTAL SLIDING WINDOWS AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. COMPLETE PRODUCT APPROVAL WAS NOT
 SUBMITTED.
  
 C)HURRICANE SHUTTERS AND COMPLETE INSTALLATION SINCE
 WINDOWS DON'T HAVE IMPACT GLASS. YOU MAY USE THE CITY
 SAMPLE FOR HURRICANE SHUTTERS INSTALLATION SCHEDULE OR
 PROVIDE COMPLETE INFORMATION IN ANY OTHER FORMAT.
 RESPONSE:
 REPEAT COMMENT. INFORMATION WAS NOT SUBMITTED.
 NOTE: SINGLE HUNG WINDOWS AND HORIZONTAL ROLLING
 WINDOWS UPLOADED TO PROJECTDOX ON 04/09/21 WERE FOR
 NON-IMPACT WINDOWS. ARCHITECT SPECIFIES IMPACT WINDOWS.
 COORDINATE PRODUCT APPROVALS WITH ARCHITECT'S
 SPECIFICATIONS TO AVOID CONFLICTS/DELAYS.
  
 D)HARDIE PLANK LAP SIDING AS SPECIFIED ON PLANS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT.
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 SINGLE HUNG WINDOWS AND HORIZONTAL ROLLING WINDOWS
 UPLOADED TO PROJECTDOX ON 04/09/21 WERE FOR NON-IMPACT
 WINDOWS. ARCHITECT SPECIFIES IMPACT WINDOWS. COORDINATE
 PRODUCT APPROVALS WITH ARCHITECT'S SPECIFICATIONS TO
 AVOID CONFLICTS/DELAYS.
  
 NEW COMMENTS BASED ON PLANS THAT ARE LEGIBLE NOW:
 4- WINDOW DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 ARE TOO LOW. ACCORDING TO TABLE R301.2(2)
 FBC-RESIDENTIAL AND CORRESPONDING HEIGHT AND EXPOSURE
 COEFFICIENT FOR EXPOSURE "C" ON TABLE R301.2(3)
 FBC-RESIDENTIAL THE DESIGN PRESSURES SPECIFIED BY THE
 ARCHITECT OF RECORD ARE TOO LOW. ARCHITECT OF RECORD TO
 REVISE DESIGN PRESSURES ON THE WINDOW/DOOR SCHEDULE OR
 PROVIDE ACTUAL CALCULATIONS. (NOTE: WORST CASE SCENARIO
 IS FOR THE LOWEST OPENING EFFECTIVE WIND AREA LOCATED
 IN THE END ZONE).
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 5-WINDOW SILL DETAIL AND FRAME WALL SECTION SHOWN ON
 SHEET G0.1 DON'T MATCH. THE WINDOW SILL DETAIL IS FOR
 EIFS WALLS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By jgomez Date 2021-04-26 Time 16:18 Rev Time 0.00
Received By jgomez Date 2021-04-26 Time 13:44 Sent To  
Notes
2021-04-26 16:22:05RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040514
  
 1- DRAWINGS SUBMITTED ARE TOO SMALL AND ARE NOT
 LEGIBLE. DRAWINGS HAVE A COPY OF THE ARCHITECT'S
 DIGITAL SIGNATURE AND WERE REDUCED TO 8-1/2 X 11 PAGES.
 DRAWINGS NEED TO HAVE ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS
 AS REQUIRED BY 61G1-16.003 FAC. THERE ARE TWO WAYS TO
 SUBMIT THE DRAWINGS. ONE IS TO UPLOAD THE DRAWINGS TO
 PROJECTDOX WITH THE ARCHITECT'S DIGITAL SIGNATURE OR
 THE OTHER OPTIONS TO SUBMIT FULL SCALE DRAWINGS WITH
 THE ARCHITECT'S ORIGINAL SEAL/SIGNATURE.
  
 2-PROVIDE COMPLETE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 B)HORIZONTAL SLIDING WINDOWS AS SPECIFIED ON PLANS.
  
 C)HURRICANE SHUTTERS AND COMPLETE INSTALLATION SINCE
 WINDOWS DON'T HAVE IMPACT GLASS. YOU MAY USE THE CITY
 SAMPLE FOR HURRICANE SHUTTERS INSTALLATION SCHEDULE OR
 PROVIDE COMPLETE INFORMATION IN ANY OTHER FORMAT.
  
 D)HARDIE PLANK LAP SIDING AS SPECIFIED ON PLANS.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT (EVEN IF OWNER/BUILDER)AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION AS REQUIRED, INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 5- ARCHITECT NEEDS TO CONTACT AND UPDATE HIS LICENSE
 WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION (DBPR).
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-23 Cont ID  
Sent By jgomez Date 2021-08-23 Time 11:15 Rev Time 0.00
Received By jgomez Date 2021-08-23 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-10 Cont ID  
Sent By jgomez Date 2021-08-10 Time 13:54 Rev Time 0.00
Received By jgomez Date 2021-07-22 Time 15:59 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 11:16 Rev Time 0.00
Received By jgomez Date 2021-06-23 Time 10:08 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-26 Cont ID  
Sent By jgomez Date 2021-04-26 Time 16:22 Rev Time 0.00
Received By jgomez Date 2021-04-08 Time 07:15 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-10 Cont ID  
Sent By jgomez Date 2021-08-10 Time 13:54 Rev Time 0.00
Received By jgomez Date 2021-08-10 Time 13:54 Sent To  
Notes
2021-07-22 15:59:24DIGITALLY SIGNED FILE UNDER SIGNATURES FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 11:16 Rev Time 0.00
Received By jgomez Date 2021-07-06 Time 11:16 Sent To  
Notes
2021-07-06 11:16:48SIGNATURE REVIEW COMMENTS.
  
 1-ARCHITECTURAL DRAWINGS SUBMITTED HAVE A COPY OF THE
 ARCHITECT'S DIGITAL SIGNATURE. PLANS NEED TO HAVE
 ARCHITECT'S ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003
 FAC. NEED TO UPLOAD PLANS TO PROJECTDOX WITH THE
 ARCHITECT'S DIGITAL SIGNATURE AS REQUIRED BY SEC.
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. OR PROVIDE
 HARD COPY PLANS WITH THE ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 NOTE: IN ORDER TO EXPEDITE THE REVIEW PROCESS, IT IS
 PREFERABLE TO DOWNLOAD THE DRAWINGS WITH THE DIGITAL
 SIGNATURE. OTHERWISE, HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE IS REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-26 Cont ID  
Sent By jgomez Date 2021-04-26 Time 15:29 Rev Time 0.00
Received By jgomez Date 2021-04-26 Time 15:25 Sent To  
Notes
2021-04-26 15:42:18SIGNATURE REVIEW COMMENTS.
  
 1-ARCHITECTURAL DRAWINGS SUBMITTED HAVE A COPY OF THE
 ARCHITECT'S DIGITAL SIGNATURE. PLANS NEED TO HAVE
 ARCHITECT'S ORIGINAL SEAL AND SIGNATURE WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS AS REQUIRED BY 61G1-16.003
 FAC. NEED TO UPLOAD PLANS TO PROJECTDOX WITH THE
 ARCHITECT'S DIGITAL SIGNATURE AS REQUIRED BY SEC.
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. OR PROVIDE
 HARD COPY PLANS WITH THE ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 NOTE: IN ORDER TO EXPEDITE THE REVIEW PROCESS, IT IS
 PREFERABLE TO DOWNLOAD THE DRAWINGS WITH THE DIGITAL
 SIGNATURE. OTHERWISE, HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE IS REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]