Plan Review Details - Permit 21040407
Plan Review Stops For Permit 21040407
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-15 Cont ID  
Sent By rmcdouga Date 2021-06-15 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2021-06-15 Time 08:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-09 Cont ID  
Sent By rmcdouga Date 2021-06-09 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2021-06-09 Time 10:09 Sent To  
Notes
2021-06-09 09:52:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. THE DOCUMENTS THAT WERE SUBMITTED ARE
 FOR A MECHANICAL STAND, NOT A GENERATOR. THE DRAWINGS
 ARE ILLEGIBLE. THE DRAWINGS ARE GENERAC AND THE ITEMS
 THAT ARE SPECIFIC TO THIS PROJECT ARE NOT INDICATED BY
 BEING CIRCLED OR HI-LIGHTED. NO DETAILS FOR THE
 EXISTING CONCRETE SLAB WERE PROVIDED.] PROVIDE DETAILS
 OF THE EXISTING GENERATOR SLAB (SIZE, THICKNESS AND
 MATERIAL) AND SPECIFY THE TYPE AND NUMBER OF FASTENERS
 THAT WILL BE USED TO ANCHOR THE GENERATOR TO RESIST
 WIND LOADS. FBC 107.2.1
  
 2) [ NOT RESOLVED. THIS REQUIREMENT HAS NOT BEEN
 SPECIFIED ON THE SITE PLAN AS REQUESTED.] THE GENERATOR
 EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET FROM ANY
 OPENINGS INTO A BUILDING. SPECIFY THIS ON THE LOCATION
 SURVEY. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-29 Cont ID  
Sent By rmcdouga Date 2021-04-29 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2021-04-29 Time 14:30 Sent To  
Notes
2021-04-29 14:36:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE DETAILS OF THE EXISTING GENERATOR SLAB
 (SIZE, THICKNESS AND MATERIAL) AND SPECIFY THE TYPE AND
 NUMBER OF FASTENERS THAT WILL BE USED TO ANCHOR THE
 GENERATOR TO RESIST WIND LOADS. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. SPECIFY THIS ON
 THE LOCATION SURVEY. R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-27 Cont ID  
Sent By fgiaquin Date 2021-05-27 Time 19:47 Rev Time 0.00
Received By fgiaquin Date 2021-05-27 Time 18:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By fgiaquin Date 2021-04-20 Time 23:01 Rev Time 0.00
Received By fgiaquin Date 2021-04-20 Time 21:55 Sent To  
Notes
2021-04-20 23:01:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. PROVIDE SPEC SHEETS FOR GEN AND TRANSFER SWITCH
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-08 Cont ID  
Sent By tklarge Date 2021-06-08 Time 05:39 Rev Time 0.00
Received By tklarge Date 2021-06-08 Time 04:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By abelisle Date 2021-04-22 Time 22:01 Rev Time 0.00
Received By abelisle Date 2021-04-22 Time 21:32 Sent To  
Notes
2021-04-22 21:41:431ST REVIEW FBC-2020 PLUMBING
 PERMIT-21040407
 4/22/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2- SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 3- SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 4- SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020
 FBC FUEL GAS RES. SEC. G2413.2.
 6- SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
 7- SUBMIT SIZING TABLE USED IN THE DESIGN FOR THE GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM 2020 FBC
 FUEL GAS SEC. 402.3 OR 2020 FBC FUEL GAS RES. SEC.
 G2413.3
 8- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 9- GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS
 10- THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?)
 FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
 11- THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR
 SHALL BE ONSITE FOR FINAL GAS INSPECTION. THE GENERATOR
 SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE
 GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-04-23 Cont ID  
Sent By fmittner Date 2021-04-23 Time 11:05 Rev Time 0.00
Received By fmittner Date 2021-04-23 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-17 Cont ID  
Sent By lmarchan Date 2021-06-17 Time 11:06 Rev Time 0.00
Received By lmarchan Date 2021-06-14 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By rmcdouga Date 2021-06-14 Time 11:08 Rev Time 0.00
Received By shill Date 2021-05-27 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-29 Cont ID  
Sent By rmcdouga Date 2021-04-29 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-06-08 Cont ID  
Sent By tklarge Date 2021-06-08 Time 05:39 Rev Time 0.00
Received By tklarge Date 2021-06-08 Time 05:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By abelisle Date 2021-04-22 Time 21:41 Rev Time 0.00
Received By abelisle Date 2021-04-22 Time 21:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-15 Cont ID  
Sent By rmcdouga Date 2021-06-15 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2021-06-15 Time 08:06 Sent To  
Notes
2021-06-15 08:07:54AN EXISTING 4" CONCRETE SLAB IS BEING USED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-09 Cont ID  
Sent By rmcdouga Date 2021-06-09 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2021-06-09 Time 09:57 Sent To  
Notes
2021-06-09 10:01:27THE ENGINEERED DRAWINGS THAT WERE SUBMITTED FOR THE
 MECHANICAL STANDS ARE COPIES AND DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE AS REQUIRED BY FS 471 AND
 FAC 61G-15 FOR ELECTRONICALLY SUBMITTED DOCUMNETS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-29 Cont ID  
Sent By rmcdouga Date 2021-04-29 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2021-04-29 Time 14:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-06-17 Cont ID  
Sent By fmittner Date 2021-06-17 Time 10:20 Rev Time 0.00
Received By fmittner Date 2021-06-17 Time 10:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-06-14 Cont ID  
Sent By fmittner Date 2021-06-14 Time 10:32 Rev Time 0.00
Received By fmittner Date 2021-06-14 Time 10:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-23 Cont ID  
Sent By kalexand Date 2021-04-23 Time 11:05 Rev Time 0.00
Received By fmittner Date 2021-04-23 Time 11:05 Sent To  
Notes
2021-04-23 11:05:42SETBACKS FROM PROPERTY LINE NOT CLEARLY DEMARCATED