| Plan Review Stops For Permit 21040400 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2021-08-11 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-11 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-11 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-30 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-30 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2021-07-30 11:01:59 | AC DUCT REPLACEMENT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWINGS NEED TO SHOW ALL FIRE AND SMOKE WALLS - | | | PROVIDED DRAWINGS DO NOT SHOW ALL FIRE RATED WALLS (YOU | | | CAN REQUEST A RECORDS SEARCH - HTTPS://WESTPALMBEACHFL. | | | GOVQA.US/WEBAPP/_RS/(S(JYNBG4BW3AQKIWM33ZN5FYNB))/SUPPO | | | RTHOME.ASPX ) | | | 2) PLEASE SHOW ALL FIRE RATED WALL AND FLOOR | | | (HORIZONTAL ASSEMBLIES) PENETRATION DETAILS PER FBC | | | 714.1.1DUCTS AND AIR TRANSFER OPENINGS. | | | PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS | | | THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH | | | SECTIONS 714.3 THROUGH 714.4.3. PENETRATIONS OF | | | HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS | | | PERMITTED BY SECTION 717.6, AND NOT REQUIRED TO BE | | | PROTECTED WITH FIRE DAMPERS BY OTHER SECTIONS OF THIS | | | CODE, SHALL COMPLY WITH SECTIONS 714.5 THROUGH 714.6.2. | | | DUCTS AND AIR TRANSFER OPENINGS THAT ARE PROTECTED WITH | | | DAMPERS SHALL COMPLY WITH SECTION 717. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
N |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-21 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-21 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2021-06-21 08:25:08 | REPLACE MECHANICAL EQUIPMENT NO STRUCTURAL REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-28 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-28 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2021-04-28 13:32:35 | NEW 2 STORY APT. BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE ROOF TOP GUARD RAIL DETAILS FROM A | | | DESIGN PROFESSIONAL TO COMPLY WITH REQUIRED LOADS PER | | | FBC 1607.8.1 - - 1607.8.1.1 | | | 2) GUARD REQUIREMENTS - 1015.6 MECHANICAL EQUIPMENT, | | | SYSTEMS AND DEVICES. | | | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT | | | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF | | | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH | | | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD | | | SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND | | | EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE | | | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 | | | INCHES (533 MM) IN DIAMETER. | | | 3) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL | | | FOR THE MECHANICAL EQUIPMENT STANDS AND CURBS OR | | | PROVIDE THE MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVAL TO COMPLY WITH THE REQUIRED WIND LOADS PER FBC | | | 1609 AND NOTE NUMBER 4 ON DRAWING M001. | | | 4) PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL | | | FOR THE MECHANICAL BEAM SUPPORT ON DRAWING M102 NOTE | | | NUMBER 8. | | | 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR DESIGN | | | ON ANY ADDED DETAILS FBC 1603.1.4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-04-27 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-27 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-27 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2021-08-11 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-11 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-02 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-07-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-07-30 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-07-16 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-07-08 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-06-30 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-21 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-25 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-04-28 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-04-12 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2021-08-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-11 |
Time |
06:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-11 |
Time |
06:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2021-07-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-29 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-28 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2021-07-29 09:10:22 | 5TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M101: EF-5 APPEARS TO BE PASSING THROUGH 2 | | | RATED WALLS, PLEASE SHOW THE PENETRATION PROTECTION. | | | FBC M 607 | | | | | | 2) SHEET M101: THERE ARE SEVERAL DUCTS PENETRATING | | | SMOKE BARRIERS AND RATED PARTITIONS, PLEASE SHOW THE | | | PENETRATION PROTECTIONS AT EACH LOCATION. FBC M 607 | | | | | | 3) PLEASE PROVIDE A DETAIL DRAWING OF THE SMOKE | | | BARRIER. IS THE CEILINGS DROPPED AND THE WALL AND | | | CEILING MEET LEAVING AN AREA ABOVE FOR THE RETURN AIR? | | | FBC 107.2.1 | | | | | | 4) IS THERE NO RATED WALLS AT THE STAGE AND BACK OF | | | STAGE AREA? | | | | | | 5) PLEASE EXPLAIN HOW YOU ARE PROVIDING THE OUTDOOR AIR | | | TO THE BACK OF STAGE AREAS CONDITIONED BY THE AHU?S | | | | | | 6) SHEETS M101 AND M102: THERE IS A SYMBOL THAT LOOKS | | | LIKE THE LETTER H IN RATED WALLS, PLEASE SHOW WHAT | | | THESE ARE. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2021-07-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-07 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-07 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2021-07-07 16:13:00 | 4TH REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M002: YOU MAY USE ASHRAE 62.1 AS AN ALTERNATE | | | MEANS AND METHODS FOR VENTILATION CALCULATIONS, BUT YOU | | | MUST SHOW YOUR CALCULATIONS. PLEASE PROVIDE THE | | | CALCULATIONS FOR THE BI-POLAR IONIZATION. FBC M 403.2 | | | (EXCEPTION) | | | | | | 2) IF THERE IS ANY DUCTWORK THAT IS NOW GOING TO BE | | | EXISTING (REUSED FROM EXISTING SYSTEM) PLEASE INDICATE | | | THAT DUCTWORK ON THE DRAWINGS. FBC 107.2.1 | | | | | | 3) PLEASE SHOW ALL DAMPER PROTECTION AT DUCT | | | PENETRATIONS OF RATED WALLS. FBC M 607 | | | | | | 4) PLEASE PROVIDE A RATED WALL GUIDE I.E. ONE HOUR | | | RATED, TWO HOUR RATED, FIRE PARTITION, FIRE WALL, SMOKE | | | RATED. FBC 107.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-06-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-04 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-04 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2021-06-04 08:25:36 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) I DO NOT SEE ANY SCOPE OF WORK FOR A GENERAL | | | CONTRACTOR. PLEASE SHOW WHY A G.C. HAS APPLIED FOR A | | | PERMIT FOR MECHANICAL WORK. ALSO PLEASE HAVE A FLORIDA | | | LICENSED MECHANICAL CONTRACTOR APPLY FOR A MECHANICAL | | | PERMIT FOR THIS PROJECT. | | | | | | 2) PLEASE SHOW THE RATED WALLS IN THIS BUILDING AND HOW | | | THE PENETRATIONS IN THE RATED WALLS BY THE DUCT WORK | | | WILL BE PROTECTED(FIRE DAMPERS AND FIRE SMOKE DAMPERS) | | | FBC M 607 | | | | | | 3) SHEET M002: WE ARE CURRENTLY UNDER THE 2020 7TH | | | EDITION FBC M PLEASE LABEL THIS OUTDOOR AIR USING THE | | | LATEST CODE. | | | | | | 4) SHEET M002: THE OUTDOOR AIR CALCULATIONS ARE VERY | | | LOW. PLEASE USE FBC M 403.3.1.1 AND TABLE 403.3.1.1 AND | | | NOT THE ARCHITECTURAL OCCUPANT LOAD FOR SPACES TO | | | CALCULATE THE OUTDOOR AIR REQUIRED FOR EACH USE OF | | | SPACE. | | | | | | 5) SHEET M002: PLEASE LABEL ?SPACE USE CLASSIFICATION? | | | BASED ON TABLE 403.3.1.1 (EXAMPLE- WEST TECH | | | POSITION-EAST TECH POSITION) | | | | | | 6) SHEET M101 & M102: PLEASE PROVIDE A DETAIL DRAWING | | | OF THE 1 INCH CONDENSATE LINE CONNECTING TO THE | | | EXISTING STORM WATER PIPING (NOTE 3). | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-26 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-26 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2021-04-26 10:51:09 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040400 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A COMPLETE MECHANICAL EQUIPMENT | | | SIZING CALCULATION INCLUDING ALL OF THE AHU?S. FBC EC | | | 403 | | | | | | 2) THE CONDENSATE FROM THE AHU?S CANNOT DRAIN INTO THE | | | BUILDING DRAIN, IT MUST DRAIN TO STORM DRAINAGE OR AN | | | APPROVED PLACE AT THE EXTERIOR OF THE BUILDING. FBC M | | | 307.2.1 | | | | | | 3) SHEET M103: THE CU-1 MUST ALSO HAVE A GUARD TO | | | PROTECT WORKERS FROM FALLING AS THEY MAINTAIN THE UNIT. | | | FBC M 304.11 | | | | | | 4) PLEASE SHOW ROOF ACCESS ON THE DRAWINGS FOR SERVICE | | | OF THE RTU?S. FBC M 306.5 | | | | | | 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE IN THIS BUILDING. FBC M 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-06-10 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-06-10 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2021-06-10 10:19:40 | CONDENSATE DRAIN HAVE BEEN MODIFIED TO CONNECT TO | | | EXISTING STORM LINES WITH CHECK VALVES AT CONNECTIONS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2021-08-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-11 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-11 |
Time |
06:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-07-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-29 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-29 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-07-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-07 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-07 |
Time |
16:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-21 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-21 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-28 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-28 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-06-17 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-06-17 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-06-17 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-04-28 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-04-28 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2021-04-28 16:45:32 | PLEASE PROVIDE INFORMATION TO CONFIRM THAT NO NEW | | | EQUIPMENT IS BEING INSTALLED ON THE ROOF. IF NEW | | | EQUIPMENT IS BEING INSTALLED ON THE ROOF, SUCH | | | EQUIPMENT SHALL BE SCREEN WITH A SCREEN AS TALL AS THE | | | EQUIPMENT. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|