Plan Review Details - Permit 21040282
Plan Review Stops For Permit 21040282
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 08:05 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 08:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By rmcphers Date 2021-04-20 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2021-04-20 Time 15:54 Sent To  
Notes
2021-04-20 15:55:42PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-09-29 Cont ID  
Sent By rmcphers Date 2021-09-29 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2021-09-29 Time 09:06 Sent To  
Notes
2021-09-29 09:08:53CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING (A-01) SHOWS FLOORING UNDERLAYMENT AS
 (WHISPERMAT CS) - PLEASE REVISE THE DRAWINGS SHOWING
 THE UNDERLAYMENT PRODUCT PROVIDED IN PROJECTDOX. (OR
 PROVIDE WHISPERMAT CS TEST REPORTS)
 2) DRAWINGS SHOULD SHOW THE TYPE OF FLOORING TO BE
 INSTALLED.FBC 107.2 (ARE YOU INSTALLING A WOOD FLOOR, A
 TILE FLOOR ETC.)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 09:38 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 09:38 Sent To  
Notes
2021-06-24 09:46:45CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING (A-01) SHOWS FLOORING UNDERLAYMENT AS
 (WHISPERMAT CS) - PLEASE REVISE THE DRAWINGS SHOWING
 THE UNDERLAYMENT PRODUCT PROVIDED IN PROJECTDOX.
 2) DRAWINGS SHOULD SHOW THE TYPE OF FLOORING TO BE
 INSTALLED.FBC 107.2
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 08:02 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 08:02 Sent To  
Notes
2021-06-14 08:05:51CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 TEST REPORTS PROVIDED INCLUDE A DROP CEILING - TEST
 REPORTS MUST RESEMBLE WHAT IS BEING INSTALLED (FLOORING
 + UNDERLAYMENT + SLAB THICKNESS) SEE COMMENTS BELOW -
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ( [email protected]
 )
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By rmcphers Date 2021-04-20 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2021-04-20 Time 15:55 Sent To  
Notes
2021-04-20 15:56:52CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ( [email protected]
 )
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-08 Cont ID  
Sent By fgiaquin Date 2021-06-08 Time 23:42 Rev Time 0.00
Received By fgiaquin Date 2021-06-08 Time 22:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-25 Cont ID  
Sent By fgiaquin Date 2021-05-25 Time 22:36 Rev Time 0.00
Received By fgiaquin Date 2021-05-25 Time 22:09 Sent To  
Notes
2021-05-25 22:36:40CTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 120/208 IS A 3PHASE WYE SYSTEM. PROVIDE ACCURATE
 PANEL SCHEDULE AND LOAD CALCULATION AS REQUESTED IN
 PREVIOUS PLAN REVIEW COMMENTS. NEC 220 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By fgiaquin Date 2021-04-15 Time 22:41 Rev Time 0.00
Received By fgiaquin Date 2021-04-15 Time 22:02 Sent To  
Notes
2021-04-15 22:41:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALC IS INCORRECT. A 3PHASE LOAD OF 21KW WOULD
 BE AROUND 59AMPS. PROVIDE ACCURATE LOAD CALC PER NEC220
  
 2. AFCI REQUIRED FOR ALL 15-20 AMP CIRCUITS ACCORDING
 TO NEC210.12 NOT 20AMP CIRCUITS ONLY AS ELECTRICAL NOTE
 ON PLAN STATES.
  
 3. SMOKE/CARBON ALARMS MUST BE TIED INTO LOCAL LIGHTING
 CIRCUIT, NOT ON SEPARATE INDIVIDUAL CIRCUIT. FBC-R
 APPENDIX J
  
 4. TAMPER PROOF RECEPTACLES REQUIRED PER NEC 406.12
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By pleduc Date 2021-05-24 Time   Rev Time 0.00
Received By pleduc Date 2021-05-24 Time 14:24 Sent To  
Notes
2021-05-24 14:23:52FIRE PROVISO:
  
 ENSURE SD ARE INSTALLED IN EACH SLEEPING AREA AND
 OUTSIDE EACH SLEEPING AREA.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-12 Cont ID  
Sent By pleduc Date 2021-04-12 Time   Rev Time 0.00
Received By pleduc Date 2021-04-12 Time 10:26 Sent To  
Notes
2021-04-12 10:27:12FIRE PROVISO:
  
 ENSURE SD ARE INSTALLED IN EACH SLEEPING AREA AND
 OUTSIDE EACH SLEEPING AREA.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 11:49 Rev Time 0.00
Received By rmcphers Date 2021-10-04 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-09-29 Cont ID  
Sent By rmcphers Date 2021-09-29 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 08:15 Rev Time 0.00
Received By rmcphers Date 2021-05-21 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By lmarchan Date 2021-05-13 Time 12:08 Rev Time 0.00
Received By lmarchan Date 2021-04-06 Time 16:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-20 Cont ID  
Sent By rmcphers Date 2021-04-20 Time 15:56 Rev Time 0.00
Received By rmcphers Date 2021-04-20 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By medwards Date 2021-04-16 Time 14:03 Rev Time 0.00
Received By medwards Date 2021-04-16 Time 13:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By ccole Date 2021-06-01 Time 11:12 Rev Time 0.00
Received By ccole Date 2021-06-01 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By ccole Date 2021-04-21 Time 12:26 Rev Time 0.00
Received By ccole Date 2021-04-21 Time 11:54 Sent To  
Notes
2021-04-21 12:27:071ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21040282
 4/21/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-01: THE SHOWER PAN DETAIL DOES NOT SHOW THE
 REQUIRED ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT) SLOPE- SECTION 421.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-25 Cont ID  
Sent By jgomez Date 2021-06-25 Time 18:21 Rev Time 0.00
Received By jgomez Date 2021-06-25 Time 18:16 Sent To  
Notes
2021-06-25 18:23:19HARD COPY OF DRAWING 001 MP-001 MECH AND PLUMB PLAN
 SUBMITTED WITH ENGINEER'S EMBOSSED SEAL AND ORIGINAL
 SIGNATURE. JG.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 09:52 Sent To  
Notes
2021-06-24 09:52:33SIGNATURE REVIEW
 DRAWINGS 001 MP-001 MECH AND PLUMB PLAN.PDF DOES NOT
 SHOW AS ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 08:12 Sent To  
Notes
2021-06-14 08:14:58SIGNATURE REVIEW
 DRAWINGS 001 MP-001 MECH AND PLUMB PLAN.PDF DOES NOT
 SHOW AS ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 11:15 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 11:12 Sent To  
Notes
2021-04-12 11:18:01PAPER PLANS BROUGHT TO THE OFFICE ARE A COPY OF THE
 DIGITAL SIGNATURE. WE CAN NOT ACCEPT THIS. PLEASE BRING
 ORIGINAL PAPER SIGNED AND SEALED DRAWINGS TO OUR OFFICE
 OR UPLOAD THE ORIGINAL DIGITALLY SIGNED DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2021-05-12 Cont ID  
Sent By kalexand Date 2021-05-12 Time 08:23 Rev Time 0.00
Received By kalexand Date 2021-05-12 Time 08:23 Sent To I
Notes
***NONE***