| 2021-04-15 11:38:04 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE VALUE OF $4,200.00 IS LOW FOR REPLACING (2) |
| | DOORS AND (14) IMPACT WINDOWS. THE VALUE WILL BE |
| | ADJUSTED WHEN PRODUCT APPROVALS HAVE BEEN SUBMITTED. |
| | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| | VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) SUBMIT PRODUCT APPROVALS FOR EACH OF THE WINDOW, |
| | STRUCTURAL MULLIONS( IF APPLICABLE) AND DOOR TYPES. |
| | CIRCLE OR HI-LIGHT THE SPECIFIC ITEMS AND THEIR DESIGN |
| | PRESSURES ON THE PRODUCT APPROVALS. FBC 107.3.4 - |
| | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| | FLORIDA STATUTE 553.842 (5). PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 3) SUBMIT A FLOOR PLAN OF THE HOUSE WITH THE ROOM TYPES |
| | IDENTIFIED. SPECIFY THE SIZE, TYPE AND LOCATIONS OF THE |
| | WINDOWS AND DOORS ON THE PLAN. FBC 107.2.1 |
| | |
| | 4) SUBMIT A COMPONENT AND CLADDING WINDLOAD CHART FOR |
| | THE BUILDING. FBC 107.2.1 & FBC-R 301 |
| | |
| | |