Plan Review Details - Permit 21040037
Plan Review Stops For Permit 21040037
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-20 Cont ID  
Sent By jleahy Date 2021-05-20 Time 10:29 Rev Time 0.00
Received By jleahy Date 2021-05-20 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By jleahy Date 2021-04-08 Time 13:49 Rev Time 0.00
Received By jleahy Date 2021-04-08 Time 13:12 Sent To  
Notes
2021-04-08 14:17:07FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 [email protected]
  
 SERVICE AND FEEDER CONDUCTORS ARE TO SMALL WHEN NOT
 FEEDING THE ENTIRE LOAD AS STATED IN 310.15(B)(7)(1,2)
 THE FEEDERS DO NOT SERVE ENTIRE LOAD. 310.15(B)(16)
 SHALL BE USED.
  
 (1) FOR A SERVICE RATED 100 THROUGH 400 A, THE SERVICE
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING,
 SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83
 PERCENT OF THE SERVICE RATING.
 (2) FOR A FEEDER RATED 100 THROUGH 400 A, THE FEEDER
 CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A
 ONE-FAMILY DWELLING, OR THE FEEDER CONDUCTORS SUPPLYING
 THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL DWELLING,
 UNIT IN A TWOFAMILY OR MULTIFAMILY DWELLING, SHALL BE
 PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83 PERCENT
 OF THE FEEDER RATING.
  
 NO ADDED VALUE HAS BEEN INCLUDED FOR THE 400AMPERE
 SERVICE, IRRIGATION PUMP, SAUNA.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-20 Cont ID  
Sent By jleahy Date 2021-05-20 Time 11:07 Rev Time 0.00
Received By jleahy Date 2021-05-11 Time 06:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-08 Cont ID  
Sent By jleahy Date 2021-04-08 Time 13:51 Rev Time 0.00
Received By jleahy Date 2021-04-02 Time 17:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-20 Cont ID  
Sent By jleahy Date 2021-05-20 Time 11:07 Rev Time 0.00
Received By jleahy Date 2021-05-20 Time 11:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-08 Cont ID  
Sent By jleahy Date 2021-04-08 Time 13:51 Rev Time 0.00
Received By jleahy Date 2021-04-08 Time 13:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved