| Plan Review Stops For Permit 21031672 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-14 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-14 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-30 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-30 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2021-04-30 08:52:24 | ROOF TOP GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE DETAILS FOR THE REQUIRED GUARD RAIL | | | OR SHOW DETAILS ON THE DRAWINGS THAT A GUARD RAIL IS | | | NOT REQUIRED. FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS | | | AND DEVICES. | | | GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT | | | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF | | | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH | | | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 | | | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD | | | SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND | | | EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE | | | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 | | | INCHES (533 MM) IN DIAMETER. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-04-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-26 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-26 |
Time |
17:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-08-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-08-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-08-24 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-04-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-04-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-04-28 |
Time |
10:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-09-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-13 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-13 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2021-09-13 12:25:16 | 2ND REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21031672 | | | 9/13/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | | 1ST REVIEW ARE LISTED BELOW- PLEASE COMPLY. | | | | | | 2) P2: PROVIDE SUPPORT AND HANGING DETAILS FOR THE GAS | | | PIPING- SECTIONS 404.9, 4107.2, & 415.1 FBC FG. | | | | | | A) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, AND SPACING | | | OF HANGERS TO ATTACH THE PIPE ALONG THE FACE OF THE | | | BUILDING. | | | | | | B) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, SPACING OF | | | SUPPORTS TO ANCHOR THE PIPE ALONG THE ROOF SURFACE. | | | | | | 3) PROVIDE A COPY OF A SURVEY DRAWING MARKED UP TO SHOW | | | THE LOCATION OF THE NEW METER- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-04-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-26 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-26 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2021-04-26 08:25:47 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21031672 | | | 4/26/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1 GAS RISER: | | | A) SHOW THE UTILITY REGULATOR AT METER- SECTION 402.2 | | | FBC FG. | | | B) LIST THE MAKE AND MODEL OF THE REGULATOR AT THE | | | GENERATOR AND SUBMIT MANUFACTURER'S SPECIFICATIONS. | | | PLEASE MARK OR HIGHLIGHT THE SPECS TO SHOW THE SELECTED | | | MODEL, INLET AND OUTLET PIPE SIZES AND PRESSURES- | | | SECTION 410.2. | | | C) INDICATE A TEST TEE FITTING WITH ONE OPENING CAPPED | | | OR PLUGGED WILL BE INSTALLED BETWEEN THE REGULATOR AND | | | THE UPSTREAM SHUTOFF VALVE- SECTION 410.2 (5 & 6). | | | D) INDICATE PIPE UNIONS WILL BE INSTALLED WITHIN 1 FT. | | | OF EITHER SIDE OF THE REGULATOR- SECTION 410.2 (7). | | | | | | 2) P2: PROVIDE SUPPORT AND HANGING DETAILS FOR THE GAS | | | PIPING- SECTIONS 404.9, 4107.2, & 415.1 FBC FG. | | | A) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, AND SPACING | | | OF HANGERS TO ATTACH THE PIPE ALONG THE FACE OF THE | | | BUILDING. | | | B) PROVIDE A DETAIL SHOWING THE TYPE, SIZE, SPACING OF | | | SUPPORTS TO ANCHOR THE PIPE ALONG THE ROOF SURFACE. | | | | | | 3) PROVIDE A COPY OF A SURVEY DRAWING MARKED UP TO SHOW | | | THE LOCATION OF THE NEW METER- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-14 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-23 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-20 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-04-14 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-13 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-13 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-04-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-26 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-26 |
Time |
07:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-09-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-14 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-14 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-04-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-30 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-30 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-09-01 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2021-09-01 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2021-09-01 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2021-09-01 09:12:39 | SEC. 94-109. - DEFINITIONS AND MINIMUM REQUIREMENTS. > | | | PROJECTION, VERTICAL - 1. MECHANICAL EQUIPMENT AND | | | APPURTENANCES NECESSARY TO THE OPERATION OR MAINTENANCE | | | OF THE BUILDING OR STRUCTURE ITSELF SUCH AS, BUT NOT | | | LIMITED TO, COOLING TOWERS, ELEVATORS, STAIRS AND | | | MECHANICAL PENTHOUSES, VENT STACKS AND ANTENNAS SHALL | | | BE ENCLOSED AND SCREENED IN SUCH A MANNER THAT THE | | | ENCLOSURE IS DESIGNED AS AN INTEGRAL PART OF THE | | | OVERALL BUILDING DESIGN. | | | | | | - SCREEN IS REQUIRED FOR THE PROPOSED GAS GENERATOR, | | | THE SCREEN SHALL BE AT A MINIMUM EQUAL IN HEIGHT TO THE | | | GAS GENERATOR ITSELF. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-05-19 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2021-05-19 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2021-05-19 11:38:20 | NEW GAS GENERATOR SHALL BE SCREENED FROM VIEW WITH A | | | SCREEN AS TALL AS THE PROPOSED EQUIPMENT. | | | FOR ADDITONAL INFORMATIION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|