Plan Review Details - Permit 21031645
Plan Review Stops For Permit 21031645
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By cthroop Date 2021-06-22 Time 08:28 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-10 Cont ID  
Sent By cthroop Date 2021-04-10 Time 08:13 Rev Time 0.00
Received By cthroop Date 2021-04-10 Time 08:06 Sent To  
Notes
2021-04-10 08:15:37PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A FLOOR PLAN. IDENTIFY LOCATION OF WINDOWS
 AND DOORS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE THE DESIGN PRESSURES OF EACH OPENING.
  
 FBC 107.3.5.3 PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 NOTE: YOU MAY PROVIDE A SCHEDULE OF OPENINGS OR PLACE
 THE DESIGN PRESSURES NEXT TO EACH OPENING ON YOUR PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2021-08-25 Cont ID  
Sent By fmittner Date 2021-08-25 Time 15:09 Rev Time 0.00
Received By fmittner Date 2021-08-25 Time 15:09 Sent To  
Notes
2021-08-25 15:10:39WENT TO HPB HEARING 8/24/21 RECEIVED APPROVAL WITH
 ADDITIONOF 6/6 GRID AND NEW WINDOW ON FIRST FLOOR WITH
 6/9. CONFIRMED WITH MARY BAYLOR. FHM

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2021-06-15 Cont ID  
Sent By aborngra Date 2021-06-15 Time 11:26 Rev Time 0.00
Received By aborngra Date 2021-06-15 Time 11:02 Sent To  
Notes
2021-06-15 11:26:32THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. REVISE DOOR TO HAVE CLEAR GLASS ONLY. PROPOSED DOOR
 IS NOT APPROPRIATE. REVISE TO BE A 15-LITE DOOR OR
 OTHER VARIANT. ANOTHER OPTION IS A 4-LITE 1/4 WITH TWO
 VERTICAL PANELS BELOW. ANOTHER OPTION IS CREATING A
 6-LITE PATTERN TO THE PROPOSED DOOR. VARIATIONS OF
 THESE MAY BE ACCEPTABLE.
 2. INSUFFICIENT INFORMATION PROVIDED. PROVIDE ALL
 PHOTOS OF THE EXISTING WINDOWS.
 3. INSUFFICIENT INFORMATION PROVIDED. PHOTOS INDICATING
 THE EXISTING CONDITION DO NOT INDICATE WHICH WINDOW OR
 WINDOWS THAT THIS DAMAGE IS ON NOR DOES IT INDICATE
 THAT THE WINDOW CANNOT BE REPAIR. PROVIDE ADDITIONAL
 INFORMATION. ONLY AN EXPERIENCED WINDOW RESTORATION
 INDIVIDUAL OR COMPANY CAN MAKE THE DETERMINATION OF
 FIXABILITY.
 4. CONFIRM THAT THE MARVIN PRODUCT IS THE CURRENT
 PRODUCT. SIW WINDOWS MAKES THEIR OWN WINDOWS. PROVIDE
 MUNTIN DETAIL.
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THE PROPOSED PRODUCT(S) WILL COMPLY WITH THESE
 CONDITIONS.
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-04-02 Cont ID  
Sent By aborngra Date 2021-04-02 Time 08:52 Rev Time 0.00
Received By aborngra Date 2021-04-01 Time 16:55 Sent To  
Notes
2021-04-02 08:52:40THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. PROVIDE A PHOTO OF THE EXISTING DOORS TO BE REPLACED
 AND A GRAPHIC OF THE PROPOSED DOORS. INCLUDE THE DOOR
 ON THE WINDOW AND DOOR SCHEDULE. IF USING A MULTI-LITE
 DOOR SUCH AS 15-LITES. A GRAPHIC IS NOT NECESSARY.
 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS - MATERIAL, EXTERIOR FRAME COLOR,
 GLASS GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION
 WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW
 MARKED. INCLUDE THE ORDER QUOTE DETAIL.
 3. PROVIDE A MUNTIN DETAIL FOR THE MARVIN PRODUCT.
 MUNTIN SHOULD MATCH AS CLOSELY AS POSSIBLE TO THE
 EXISTING MUNTIN.
 4. THE WINDOWS APPEAR TO BE WOOD WINDOWS. DEPENDING ON
 THE EXISTING CONDITION OF THE STRUCTURE
 (ORIGINAL/SIGNIFICANT WINDOWS VS REPLACEMENT WINDOWS),
 AT MINIMUM THE FRONT STREET FACING WINDOWS WILL NEED TO
 BE RETAINED. PLEASE PROVIDE ADDITIONAL INFORMATION AS
 PROVIDED IN THE WINDOW PERMIT APPLICATION EXAMPLE.
 5. INCLUDE A FLOOR PLAN.
  
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE. CONFIRM THAT
 THE PROPOSED PRODUCT(S) WILL COMPLY WITH THESE
 CONDITIONS.
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By cthroop Date 2021-06-22 Time 08:28 Rev Time 0.00
Received By cthroop Date 2021-06-08 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-10 Cont ID  
Sent By cthroop Date 2021-04-10 Time 08:15 Rev Time 0.00
Received By cthroop Date 2021-03-31 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-10 Cont ID  
Sent By cthroop Date 2021-04-10 Time 08:15 Rev Time 0.00
Received By cthroop Date 2021-04-10 Time 08:06 Sent To  
Notes
***NONE***