Plan Review Details - Permit 21031564
Plan Review Stops For Permit 21031564
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 09:38 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 09:38 Sent To  
Notes
2022-01-18 09:38:07REVISION CREATING OFFICE FROM WAREHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE DETAILS FOR THE RESTROOM
 - CLEAR FLOOR SPACE FOR FIXTURES, GRAB BAR LOCATIONS,
 TOILET PAPER HOLDER LOCATIONS, MIRROR LOCATIONS, ETC
 PER FBC ACCESSIBILITY CHAPTER 6
  
 2) RESTROOM DOOR DOES NOT HAVE A CLEAR WIDTH OF 32" PER
 FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-21 Cont ID  
Sent By rmcphers Date 2021-10-21 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2021-10-21 Time 08:17 Sent To  
Notes
2021-10-21 09:11:40REVISION CREATING OFFICE FROM WAREHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) OCCUPANCY CHANGE FROM WAREHOUSE STORAGE TO OFFICE
 "B" - THE LANDING AT THE ADDED EXTERIOR DOORS NEEDS TO
 BE EXTENDED (44" OUT FROM THE DOOR) TO COMPLY WITH FBC
 1010.1.6
  
 2) PLEASE SHOW THE HEIGHT FROM THE FINISHED FLOOR TO
 THE BOTTOM OF THE CEILING DECK ADDED IN FRONT OF THE
 NEW DOOR. FBC 1208.2
  
 3) PLEASE SHOW THE ACCESSIBLE DETAILS FOR THE RESTROOM
 - CLEAR FLOOR SPACE FOR FIXTURES, GRAB BAR LOCATIONS,
 TOILET PAPER HOLDER LOCATIONS, MIRROR LOCATIONS, ETC
 PER FBC ACCESSIBILITY CHAPTER 6
  
 4) RESTROOM DOOR DOES NOT HAVE A CLEAR WIDTH OF 32" PER
 FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2021-06-17 Time 07:46 Sent To  
Notes
2021-06-17 09:43:58REVISION CREATING OFFICE FROM WAREHOUSE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW EXTERIOR WALL FRAMING ATTACHMENTS TO THE
 EXISTING STRUCTURE TO COMPLY WITH THE WIND LOADS FBC
 1609
 2) OCCUPANCY CHANGE FROM WAREHOUSE STORAGE TO OFFICE
 "B" - THE LANDING AT THE ADDED EXTERIOR DOORS NEEDS TO
 BE EXTENDED (44" OUT FROM THE DOOR) TO COMPLY WITH FBC
 1010.1.6
 3) DOOR PRODUCT APPROVAL INSTALLATION INSTRUCTIONS ARE
 EXPIRED - PLEASE PROVIDE THE REVISED (02/04/2019)
 INSTALLATION INSTRUCTIONS FOR THE DOOR. FBC 107
 4) PLEASE PROVIDE THE FLORIDA PRODUCT APPROVAL FRONT
 PAGES FOR THE SHUTTERS (ONLY THE INSTALLATION
 INSTRUCTIONS WERE PROVIDED). FBC 107
 5) PLEASE SHOW THE HEIGHT FROM THE FINISHED FLOOR TO
 THE BOTTOM OF THE CEILING DECK ADDED. FBC 1208.2
 6) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FOR THE
 ADJOINING SPACE - SEPARATION NEEDS TO COMPLY WITH FBC
 508.1
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 15:51 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 15:01 Sent To  
Notes
2021-04-21 15:51:50STAIR SHOP DRAWINGS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW WALL FRAMING DETAILS.
 2) PLEASE SHOW RESTROOMS TO COMPLY WITH FBC
 ACCESSIBILITY PER CHAPTER 6 - USE DIMENSIONS TO SHOW
 (GRAB BAR HEIGHTS, LOCATIONS AND LENGHTS FOR WATER
 CLOSET AND SHOWER) - (DOOR WIDTHS) - (PAPER DISPENSER
 LOCATION AND DISTANCE FROM WATER CLOSET, HEIGHT FROM
 FLOOR) - ( FIXTURE CLEAR FLOOR SPACE) (ETC..)
 3) RESTROOM DOOR NEEDS A CLEAR OPENING BETWEEN ANY TRIM
 OR STOPS OF 32" FBC 404.2.3 CLEAR WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 4) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 08:29 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-01-29 Cont ID  
Sent By jleahy Date 2022-01-29 Time 09:45 Rev Time 0.00
Received By jleahy Date 2022-01-29 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 20:51 Rev Time 0.00
Received By fgiaquin Date 2021-11-06 Time 19:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By equinone Date 2021-05-24 Time 14:38 Rev Time 0.00
Received By equinone Date 2021-05-24 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By equinone Date 2021-04-21 Time 16:22 Rev Time 0.00
Received By equinone Date 2021-04-21 Time 16:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-04-04 Cont ID  
Sent By cwalker Date 2022-04-04 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-04-04 09:57:58FIRE COMMENT:
 THE STREET ADDRESS NUMBER SHALL BE POSTED IN A POSITION
 TO BE PLAINLY LEGIBLE AND VISIBLE FROM THE STREET OR
 ROAD FRONTING THE PROPERTY AND IN CONTRAST WITH THEIR
 BACKGROUND. NFPA 1 10.11.1
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-07 Cont ID  
Sent By pleduc Date 2021-10-07 Time   Rev Time 0.00
Received By pleduc Date 2021-10-07 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-18 Cont ID  
Sent By pleduc Date 2021-06-18 Time   Rev Time 0.00
Received By pleduc Date 2021-06-18 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 08:29 Rev Time 0.00
Received By mpeterso Date 2022-04-01 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-29 Cont ID  
Sent By jleahy Date 2022-01-29 Time 09:45 Rev Time 0.00
Received By jleahy Date 2022-01-06 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-06 Cont ID  
Sent By fgiaquin Date 2021-11-06 Time 20:52 Rev Time 0.00
Received By fgiaquin Date 2021-10-06 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 07:00 Rev Time 0.00
Received By pvalenti Date 2021-05-19 Time 07:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-22 Time   Rev Time 0.00
Received By shill Date 2021-04-06 Time 18:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-08-09 Cont ID  
Sent By rmcphers Date 2021-08-09 Time 08:05 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-01-12 Cont ID  
Sent By medwards Date 2022-01-11 Time 17:25 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By medwards Date 2021-10-15 Time 10:39 Rev Time 0.00
Received By medwards Date 2021-10-15 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-18 Cont ID  
Sent By medwards Date 2021-06-18 Time 08:00 Rev Time 0.00
Received By medwards Date 2021-06-18 Time 08:00 Sent To  
Notes
2021-06-18 08:00:371ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031564
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE AHU. FBC EC C403.2.1
  
 2) PLEASE SHOW THE LOCATION THAT THE CONDENSING UNIT
 WILL BE LOCATED ON THE PROPERTY. FBC 107.2.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THIS
 SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE PROVIDED FOR
 THIS SPACE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-04-07 Cont ID  
Sent By ccole Date 2022-04-07 Time 09:09 Rev Time 0.00
Received By ccole Date 2022-04-07 Time 08:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-01-11 Cont ID  
Sent By ccole Date 2022-01-11 Time 13:55 Rev Time 0.00
Received By ccole Date 2022-01-11 Time 12:51 Sent To  
Notes
2022-01-11 13:56:194TH REVIEW FBC-2017 PLUMBING
 PERMIT- 21031564 (REVISION TO 20100237)
 1/11/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. THIS IS THE 4TH FAILED
 REVIEW OF THE PLUMBING PLANS FOR THE PROJECT. NO
 NARRATIVE WAS PROVIDED IN RESPONSE TO THE 3RD REVIEW
 COMMENT WHICH IS LISTED BELOW. PLEASE HAVE THE
 ARCHITECT REVIEW SECS. 212.3, 213.2 & 213.3 FBC ACC AND
 RESPOND TO THE COMMENTS OR CONTACT ME FOR FURTHER
 INFORMATION.
  
 1) SHEETS A1 & A2: AS NOTED ON SHEET A1 UNDER CODE DATA
 THE PRIVATE BATHROOM SHALL BE DESIGNED AND CONSTRUCTED
 IN COMPLIANCE WITH THE FBC ACC- 2017. PLEASE ADDRESS
 THE FOLLOWING CODE REQUIREMENTS ITEMIZED BELOW AND NOTE
 THAT THERE ARE NO EXCEPTIONS IN THE CODES LISTED THAT
 EXEMPTS PRIVATE OFFICES.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE
 AND TOE CLEARANCES.)
 C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 F) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED
 ON SECTIONS 604.5 & 609.4.
 G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 I) BASED ON SECTIONS 608.2 THE SHOWER COMPARTMENT SHALL
 BE EITHER BE A TRANSFER TYPE DIMENSIONED AT 36X36
 INCHES, OR A STANDARD ROLL-IN TYPE WITH MINIMUM CLEAR
 DIMENSIONS OF 30X60 INCHES.
 K) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR EITHER
 A TRANSFER OR ROLL-IN TYPE SHOWER- SECTIONS 608.2.1 &
 608.2.2.1.
 L) SHOWER GRAB BAR REINFORCEMENT LOCATIONS BASED ON
 SECTIONS 608.3 AND 609.4.
 M) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1 OR 608.5.2.
 N) HEIGHT OF THE KITCHEN SINK- SECTION 606.3. (THE PLAN
 SHOWS 36-INCHES HOWEVER THE CODE DOES NOT PROVIDE AN
 EXCEPTION FOR KITCHEN SINKS FROM MEETING THE MAXIMUM
 34-INCHES FROM THE FINISH FLOOR TO THE HIGHER OF THE
 RIM OF THE SINK OR COUNTER SURFACE).
 O) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 KITCHEN SINK- SECTION 606.2. (ITEM 1 ALLOWS FOR A
 PARALLEL APPROACH BECAUSE THERE IS NO COOKTOP OR
 RANGE).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-10-21 Cont ID  
Sent By ccole Date 2021-10-21 Time 09:51 Rev Time 0.00
Received By ccole Date 2021-10-21 Time 07:22 Sent To  
Notes
2021-10-21 09:51:383RD REVIEW FBC-2017 PLUMBING
 PERMIT- 21031564 (REVISION TO 20100237)
 10/21/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1: THE ARCHITECT'S RESPONSE LETTER TO 2ND
 REVIEW COMMENTS STATE THE OCCUPANCY IS A "PERSONAL
 PRIVATE OFFICE FOR THE BUILDING OWNER WHICH HAS A HDCP
 BATHROOM IN THE BUILDING LESS THAN 100 FT. AWAY".
 PLEASE SHOW THE LOCATION OF THE EXISTING BATHROOM ON
 THE PLANS- SECTION 107.2.1 WPB.
  
 2) SHEETS A1 & A2: AS NOTE ON SHEET A1 UNDER CODE DATA
 THE PRIVATE BATHROOM SHALL BE DESIGNED AND CONSTRUCTED
 IN COMPLIANCE WITH THE FBC ACC- 2017. PLEASE ADDRESS
 THE FOLLOWING CODE REQUIREMENTS ITEMIZED BELOW AND NOTE
 THAT THERE ARE NO EXCEPTIONS IN THE CODES LISTED THAT
 EXEMPTS PRIVATE OFFICES.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE
 AND TOE CLEARANCES.)
 C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 F) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED
 ON SECTIONS 604.5 & 609.4.
 G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 I) BASED ON SECTIONS 608.2 THE SHOWER COMPARTMENT SHALL
 BE EITHER BE A TRANSFER TYPE DIMENSIONED AT 36X36
 INCHES, OR A STANDARD ROLL-IN TYPE WITH MINIMUM CLEAR
 DIMENSIONS OF 30X60 INCHES.
 K) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR EITHER
 A TRANSFER OR ROLL-IN TYPE SHOWER- SECTIONS 608.2.1 &
 608.2.2.1.
 L) SHOWER GRAB BAR REINFORCEMENT LOCATIONS BASED ON
 SECTIONS 608.3 AND 609.4.
 M) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1 OR 608.5.2.
 N) HEIGHT OF THE KITCHEN SINK- SECTION 606.3. (THE PLAN
 SHOWS 36-INCHES HOWEVER THE CODE DOES NOT PROVIDE AN
 EXCEPTION FOR KITCHEN SINKS FROM MEETING THE MAXIMUM
 34-INCHES FROM THE FINISH FLOOR TO THE HIGHER OF THE
 RIM OF THE SINK OR COUNTER SURFACE).
 O) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 KITCHEN SINK- SECTION 606.2. (ITEM 1 ALLOWS FOR A
 PARALLEL APPROACH BECAUSE THERE IS NO COOKTOP OR
 RANGE).
  
 3) A2: THE PLUMBING SPECIFICATIONS INDICATE A
 NON-THERMOSTATIC SHOWER VALVE HOWEVER A
 BALANCED-PRESSURE, THERMOSTATIC OR BALANCED
 PRESSURE/THERMOSTATIC VALVE SHALL BE INSTALLED- SECTION
 424.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-03 Cont ID  
Sent By ccole Date 2021-06-03 Time 11:12 Rev Time 0.00
Received By ccole Date 2021-06-03 Time 09:39 Sent To  
Notes
2021-06-03 11:13:392ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21031564 (REVISION TO 20100237)
 6/3/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLAN INDICATES A CHANGE OF OCCUPANCY
 FROM AN S TO A B OCCUPANCY- STORAGE WAREHOUSE TO
 PRIVATE OFFICE. BASED ON THE PLAN THIS APPEARS TO BE A
 NEW TENANT OCCUPANCY. REFER TO SECTIONS 202, AND 1010.1
 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE B OCCUPANCY IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PLEASE NOTE THAT THE PLAN DOES NOT PROVIDE AN OCCUPANCY
 CLASSIFICATION OR OCCUPANT LOAD, HOWEVER IT APPEARS
 THAT AT A MINIMUM ONE ACCESSIBLE TOILET ROOM FOR BOTH
 MALE AND FEMALE USE WOULD BE REQUIRED PER TABLE 403.1,
 AND THE APPLICABLE SUB- SECTIONS UNDER 403. THE
 PREVIOUS PLAN INDICATED A NEW TOILET ROOM HOWEVER THE
 REQUIRED TOILET ROOM AND REQUIRED FIXTURES HAVE BEEN
 ELIMINATED. PLEASE REVISE THE PLAN TO SHOW THE PLUMBING
 PIPING AND ACCESSIBILITY DETAILS.
  
 2) PLUMBING:
 A) SANITARY AND WATER SUPPLY FLOOR PLAN DRAWINGS AND
 RISERS.
 B) PLUMBING FIXTURE SCHEDULE.
 C) REQUIRED HOT WATER SOURCE AND SUPPLY FOR WASHING,
 CULINARY PURPOSES, CLEANING ETC.
  
 3) ACCESSIBILITY:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 3) THE SUBMITTED ENERGY EFFICIENCY FORM R405 IS USED
 FOR RESIDENTIAL OCCUPANCIES. PLEASE PROVIDE THE
 APPLICABLE COMPLIANCE DOCUMENT- SECTION C101.5.1 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By ccole Date 2021-04-22 Time 10:57 Rev Time 0.00
Received By ccole Date 2021-04-22 Time 10:57 Sent To  
Notes
2021-04-22 10:57:551ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21031564 (REVISION TO 20100237)
 4/21/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED REVISION APPLICATION INDICATES
 "ADDITIONAL PLUMBING" HOWEVER NO PLUMBING PLANS AND
 DETAILS HAVE BEEN SUBMITTED. IN ACCORDANCE WITH
 SECTIONS 107.2.1 & 107.3.5.3.1.3 WPB PLEASE PROVIDE
 COMPLETE PLUMBING DEMOLITION AND RE-WORK PLANS
 INCLUDING:
 A) MINIMUM FIXTURE CALCULATIONS PER TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE INDICATING THE NUMBER OF REQUIRED
 AND PROVIDED PLUMBING FIXTURES BASED ON THE OCCUPANT
 LOAD AND OCCUPANCY CLASSIFICATION OF THE SPACE.
 A) PLUMBING FLOOR PLAN SHOWING LOCATIONS OF ALL, NEW OR
 REPLACED PLUMBING FIXTURES AND PIPING.
 B) SANITARY DRAINAGE AND WATER RISER DRAWINGS.
 C) PLUMBING FIXTURE AND DEVICE SCHEDULES.
 D) WATER HEATER EQUIPMENT SCHEDULE AND SPECS.
 E) PLUMBING PIPING SPECIFICATIONS.
 F) SLAB REPAIR DETAIL.
  
 2) REFER TO SECTION 1003.3.1 FBC P. A NEW KITCHEN IS
 SHOWN ON THE PLAN WHICH MAY REQUIRE INSTALLATION OF A
 GREASE INTERCEPTOR TO RECEIVE THE DRAINAGE FROM
 PLUMBING FIXTURES DISCHARGING GREASE LADED WASTE.
 PLEASE PROVIDE A SCOPE OF WORK FOR COOKING OPERATIONS
 IN THE KITCHEN, A KITCHEN EQUIPMENT PLAN, AND
 CORRELATING EQUIPMENT SCHEDULE.
  
 2) MISSING ACCESSIBILITY DETAILS PER FBC ACC-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 SHOWER-
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTIONS 608.2.1/608.2.2
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTIONS
 608.3.1/608.3.2.
 N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1/608.5.2.
 0) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 P) LOCATION AND INSTALLATION DIMENSIONS FOR AN
 ACCESSIBLE SHOWER SEAT (IF INSTALLED)- SECTIONS 610.3.
  
 DRINKING FOUNTAINS (WHERE REQUIRED AND INSTALLED)-
 Q) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND
 PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH
 TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW
 THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-04-14 Cont ID  
Sent By rmcphers Date 2022-04-14 Time 07:55 Rev Time 0.00
Received By rmcphers Date 2022-04-14 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 09:40 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 09:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-06 Cont ID  
Sent By jleahy Date 2021-10-06 Time 16:08 Rev Time 0.00
Received By jleahy Date 2021-10-06 Time 16:08 Sent To  
Notes
2021-10-06 16:09:17PLANS SENT TO STORAGE JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2021-06-17 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By rmcphers Date 2021-04-21 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 15:52 Sent To  
Notes
***NONE***