Plan Review Details - Permit 21031546
Plan Review Stops For Permit 21031546
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 14:11 Rev Time 0.00
Received By cthroop Date 2021-07-02 Time 11:34 Sent To  
Notes
2021-07-08 14:13:57PROVISOS ON PLAN PAGE 001 AND PHOTOGRAPH OF SUMMER
 KITCHEN.
 1. SEPERATE GAS PERMIT REQUIRED.
 2. CABINET VENTS PER MANUF. INST. INSTRUCTIONS.
 3. PROVIDE GREASE TRAY.
 4. LP TANK COMPARTMENT SHALL BE ISOLATED.
 CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By cthroop Date 2021-04-21 Time 12:33 Rev Time 0.00
Received By cthroop Date 2021-04-19 Time 13:03 Sent To  
Notes
2021-04-21 12:56:22PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: REF. LION GRILLS MANUFACTURERES SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE FOLLOWING:
  
 1. CLEARANCE TO COMBUSTIBLE CONSTRUCTION IS 21 INCHES
 MINIMUM.
 2. CABINET SHALL BE OF MASONRY CONSTRUCTION.
 3. GRILL CANNOT BE LOCATED UNDER ANY COMBUSTIBLE
 CONSTRUCTION. RATED EXHAUST HOOD MAY BE REQUIRED.
 4. UPPER AND GROUND LEVEL VENTS MUST BE PROVIDED FOR
 COMBUSWTION AIR ON BOTH SIDES OF THE CABINET. 20 SQ.
 IN. MINIMUM. SEE PAGE 8 AND PAGE 10 OF INSTRUCTIONS.
  
 NOTICE: PRODUCT INFO. PAGE STATES BUILT IN NATURAL GAS
 GRILL. NOTE STATES GRILL IS TEMPORARILY OUT OF STOCK
 WITH A RECOMMENDATION FOR A PROPANE GAS GRILL.
 PLEASE CLARIFY WHAT GRILL WILL BE INSTALLED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. PROVIDE A SITE PLAN. IDENTIFY LOCATION OF GRILL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. RE-SUBMIT CABINET DRAWINGS THAT COMPLY WITH THE
 MANUF. SPEC'S.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NOTICE: PROVISO ON PLAN PAGE 001: A SEPERATE GAS PERMIT
 IS REQUIRED. CT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-22 Cont ID  
Sent By jleahy Date 2021-07-22 Time 08:24 Rev Time 0.00
Received By jleahy Date 2021-07-22 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-07-06 Cont ID  
Sent By jleahy Date 2021-07-06 Time 05:48 Rev Time 0.00
Received By jleahy Date 2021-07-01 Time 07:31 Sent To  
Notes
2021-07-06 05:49:26SEE REVIEW COMMENTS FROM 4/9/21 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By jleahy Date 2021-04-09 Time 08:07 Rev Time 0.00
Received By jleahy Date 2021-04-09 Time 08:05 Sent To  
Notes
2021-04-09 08:08:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, PLEASE INDICATE ON THE PLAN THE
 ELECTRIC TO BE INSTALLED.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By cthroop Date 2021-04-21 Time 12:29 Rev Time 0.00
Received By cthroop Date 2021-04-19 Time 13:03 Sent To  
Notes
2021-04-21 12:30:16PROVISO ON PLAN PAGE 001: A SEPERATE GAS PERMIT IS
 REQUIRED. CT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 14:15 Rev Time 0.00
Received By cthroop Date 2021-06-30 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By lmarchan Date 2021-04-21 Time 14:59 Rev Time 0.00
Received By lmarchan Date 2021-04-08 Time 13:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-04-09 Cont ID  
Sent By medwards Date 2021-04-09 Time 07:43 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 07:37 Sent To  
Notes
2021-04-09 07:44:54APPROVED WITH PRIVISO: INSTALLATION MUST BE BY
 MANUFACTURES INSTALLATION INSTRUCTIONS AS THE DRAWING
 DOES NOT SHOW ANY CLEARANCES.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-07-08 Cont ID  
Sent By cthroop Date 2021-07-08 Time 14:11 Rev Time 0.00
Received By cthroop Date 2021-07-02 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-21 Cont ID  
Sent By cthroop Date 2021-04-21 Time 12:32 Rev Time 0.00
Received By cthroop Date 2021-04-21 Time 12:32 Sent To  
Notes
2021-04-21 12:33:21PLUMBING ROUGH INSTALLED UNDER MASTER PERMIT 20010670.
 CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-09 Cont ID  
Sent By medwards Date 2021-04-09 Time 07:45 Rev Time 0.00
Received By medwards Date 2021-04-09 Time 07:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-03 Cont ID  
Sent By jroach Date 2021-07-03 Time 13:15 Rev Time 0.00
Received By jroach Date 2021-07-03 Time 13:12 Sent To  
Notes
2021-07-03 13:16:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 07.03.2021
 PERMIT NO.: 21031546
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL IMPROVEMENTS SHALL BE A MINIMUM OF FIVE (5) FEET
 FROM THE SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By jroach Date 2021-04-21 Time 13:35 Rev Time 0.00
Received By jroach Date 2021-04-21 Time 13:35 Sent To  
Notes
2021-04-21 13:37:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 04.21.2021
 PERMIT NO.: 21031546
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY AND/OR FLOOR PLAN SHOWING
 THE LOCATION OF THE PROPOSED IMPROVEMENTS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved