Plan Review Details - Permit 21031467
Plan Review Stops For Permit 21031467
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-06-07 Cont ID  
Sent By cpuell Date 2021-06-07 Time 13:22 Rev Time 0.00
Received By cpuell Date 2021-06-07 Time 13:22 Sent To  
Notes
2021-06-07 13:24:195201 VILLAGE BLVD UNITS A-F RETIRED AND ONLY THE
 PRIMARY ADDRESS REMAINS. UPDATED PERMIT

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By cpuell Date 2021-05-24 Time 16:02 Rev Time 0.00
Received By cpuell Date 2021-05-24 Time 16:02 Sent To  
Notes
2021-05-24 16:05:25PREVIOUS COMMENTS NOT ADDRESSED:
 CURRENTLY BUILDING HAS UNITS A B C D E F WILL THE DEMO
 ERADICATE ALL THESE UNITS? PLEASE RESPOND TO
 [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By cpuell Date 2021-05-03 Time 16:01 Rev Time 0.00
Received By cpuell Date 2021-05-03 Time 16:01 Sent To  
Notes
2021-05-03 16:02:46CURRENTLY BUILDING HAS UNITS A B C D E F WILL THE DEMO
 ERADICATE ALL THESE UNITS? PLEASE RESPOND TO
 [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 15:08 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By rmcphers Date 2021-04-30 Time 13:17 Rev Time 0.00
Received By rmcphers Date 2021-04-30 Time 13:17 Sent To  
Notes
2021-04-30 13:18:03PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2021-06-14 Time 12:44 Sent To  
Notes
2021-06-14 12:49:52DAYCARE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 466.8 CORRIDORS. IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND
 903.3.1.1 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE
 RATED, PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS
 IN ACCORDANCE WITH SECTION 710.
 2) PLEASE SHOW THAT THE EXISTING CORRIDOR WALLS MEET
 THE REQUIREMENTS OF SMOKE PARTITIONS - FBC 710.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
 3) RESTROOMS FOR AGE GROUP 3 & 4 = ADA RESTROOM PAPER
 TOWEL DISPENSER - THE OUTLET OF THE DISPENSER SHOULD BE
 SHOWN TO MEET THE REACH RANGES SEE FBC ACCESSIBILITY
 308.1 (SEE ALSO THE ADVISORY FOR AGE GROUPS) - DRAWING
 P-1 "RESTROOM REFERENCE NOTES" NOTE NUMBER 1 SHOWS THE
 LOW REACH AT 15" - SHOULD BE 20". - THIS SHOULD ALSO BE
 SHOWN ON DRAWING A-1
 4) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR
 HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION
 (FL14237-R5) FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE
 DRAWINGS.
 5) PLEASE SHOW THAT CLOSURES ARE REQUIRED FOR THE EXIT
 DOORS - FBC 466.4 DOOR CLOSURE.
 ANY EXIT DOOR DESIGNED TO BE NORMALLY CLOSED SHALL BE
 KEPT CLOSED AND SHALL COMPLY WITH SECTION 716.5.
 6) PLEASE SHOW WALL FINISH AT THE MOP SINK TO COMPLY
 WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 13:42 Sent To  
Notes
2021-06-03 14:23:46DAYCARE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 466.8 CORRIDORS. IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND
 903.3.1.1 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE
 RATED, PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS
 IN ACCORDANCE WITH SECTION 710.
 2) PLEASE SHOW THAT THE EXISTING CORRIDOR WALLS MEET
 THE REQUIREMENTS OF SMOKE PARTITIONS - FBC 710.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
 3) RESTROOMS FOR AGE GROUP 3 & 4 = ADA RESTROOM PAPER
 TOWEL DISPENSER - THE OUTLET OF THE DISPENSER SHOULD BE
 SHOWN TO MEET THE REACH RANGES SEE FBC ACCESSIBILITY
 308.1 (SEE ALSO THE ADVISORY FOR AGE GROUPS) - DRAWING
 P-1 "RESTROOM REFERENCE NOTES" NOTE NUMBER 1 SHOWS THE
 LOW REACH AT 15" - SHOULD BE 20". - THIS SHOULD ALSO BE
 SHOWN ON DRAWING A-1
 4) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR
 HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION
 (FL14237-R5) FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE
 DRAWINGS.
 5) PLEASE SHOW THAT CLOSURES ARE REQUIRED FOR THE EXIT
 DOORS - FBC 466.4 DOOR CLOSURE.
 ANY EXIT DOOR DESIGNED TO BE NORMALLY CLOSED SHALL BE
 KEPT CLOSED AND SHALL COMPLY WITH SECTION 716.5.
 6) PLEASE SHOW WALL FINISH AT THE MOP SINK TO COMPLY
 WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
 7) LIFE SAFETY PLAN STILL SHOWS BUILDING CONSTRUCTION
 TYPE AS (IV) - SHOULD BE SHOWN AS (VB).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By rmcphers Date 2021-04-30 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2021-04-30 Time 09:21 Sent To  
Notes
2021-04-30 13:12:40DAYCARE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE PREVIOUS USE (OCCUPANCY
 CLASSIFICATION) PER FBC CHAPTER 3
 2) PLEASE SHOW THE TOTAL BUILDING SQUARE FOOTAGE.
 3) PLEASE SHOW ROOM AND CORRIDOR DIMENSIONS FBC 1020.2
 4) PLEASE SHOW THE FIRE RATING OF THE CORRIDOR WALLS TO
 COMPLY WITH FBC 466.8
 5) FIRE RATED PARTITIONS - 708.4 CONTINUITY.
 FIRE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE OR TO THE FIRE-RESISTANCE-RATED FLOOR/CEILING OR
 ROOF/CEILING ASSEMBLY ABOVE, AND SHALL BE SECURELY
 ATTACHED THERETO.
 6) SMOKE BARRIERS - 709.4 CONTINUITY.
 SMOKE BARRIERS SHALL FORM AN EFFECTIVE MEMBRANE
 CONTINUOUS FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, DECK OR SLAB ABOVE, INCLUDING
 CONTINUITY THROUGH CONCEALED SPACES, SUCH AS THOSE
 FOUND ABOVE SUSPENDED CEILINGS, AND INTERSTITIAL
 STRUCTURAL AND MECHANICAL SPACES.
 7) DOORS AND GLAZING IN FIRE PARTITIONS NEED TO HAVE
 FIRE RATINGS THAT COMPLY WITH FBC 716.5
 8) BUILDING CONSTRUCTION TYPE SHOULD BE VB NOT IV AS
 SHOWN ON THE DRAWINGS IN SEVERAL PLACES - SEE FBC
 CHAPTER 6
 9) RESTROOMS 109 AND 112 FBC ACCESSIBILITY 604.9 FOR
 AGE GROUP 3 TO 4 THE SPECIFICATIONS OF ONE AGE GROUP
 SHOULD BE APPLIED CONSISTENTLY IN THE INSTALLATION OF A
 WATER CLOSET AND RELATED ELEMENTS. CENTER LINE FOR
 WATER CLOSET SHOULD BE 12" - THE GRAB BAR MAXIMUM
 HEIGHT SHOULD BE 20" TO THE TOP GRIPING SURFACE NOT THE
 CENTERLINE AS SHOWN.
 10) PLEASE SHOW ADA RESTROOM MIRROR MAXIMUM HEIGHT TO
 THE BOTTOM OF THE REFLECTION FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 11) ADA RESTROOM PAPER TOWEL DISPENSER - THE OUTLET OF
 THE DISPENSER SHOULD BE SHOWN TO MEET THE REACH RANGES
 SEE FBC ACCESSIBILITY 308.1 (SEE ALSO THE ADVISORY FOR
 AGE GROUPS)
 12) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR
 HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION
 (FL14237-R5) FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE
 DRAWINGS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-25 Cont ID  
Sent By equinone Date 2021-05-25 Time 10:00 Rev Time 0.00
Received By equinone Date 2021-05-25 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-28 Cont ID  
Sent By equinone Date 2021-04-28 Time 08:38 Rev Time 0.00
Received By equinone Date 2021-04-28 Time 08:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-06-08 Cont ID  
Sent By pleduc Date 2021-06-08 Time   Rev Time 0.00
Received By pleduc Date 2021-06-08 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By pleduc Date 2021-05-24 Time   Rev Time 0.00
Received By pleduc Date 2021-05-24 Time 13:53 Sent To  
Notes
2021-05-24 13:58:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) 1A) SHEET A 1 - CORRIDOR WALL RATING
  
 THERE APPEARS A WALL TYPE INDICATED WITH A SQUARE
 AROUND AN A BUT NO INDICATION OF TYPE OF THAT IT IS
 SMOKE RATED.
  
 YOUR RESPONSE INDICATED THAT THE CORRIDORS NEED NOT BE
 RATED DUE TO THE FA & FS SYSTEMS; HOWEVER, (2) (A)
 REQUIRES A SMOKE RATING.
  
  
 (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7:
 (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 8.4.
  
  
 PLEASE PROVIDE DETAILS OF THE SMOKE RATING.
  
  
 2) 4) SHEET CS 1 & LS 1 - THERE IS INDICATION OF A FIRE
 SPRINKLER SYSTEM TO BE INSTALLED.
  
 PER FAC FIRE SPRINKLER DOCUMENTS SHALL BE SUBMITTED BY
 AN EOR WITH THIS MASTER PERMIT.
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 THIS PERMIT WILL NPT BE APPROVED WITHOUT FIRE SPRINKLER
 DOCUMENTS PER FAC. A FULL SPRINKLER PLAN SET IS NOT
 NECASSARILY REQUIRED. A SIGNED AND SEALED DOCUMENT WITH
 A WRITTEN NARRATIVE OR BULLET POINTS OF ALL THE FAC
 REQUIRMENTS IS ALL THAT IS REQUIRED WITH THIS MASTER
 PERMIT.
  
 PLEASE REVIEW AND PROVIDE SIGNED AND SEALED DOCUMENTS
 PER FAC.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By pleduc Date 2021-04-27 Time   Rev Time 0.00
Received By pleduc Date 2021-04-26 Time 15:12 Sent To  
Notes
2021-04-27 16:36:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THERE ARE INDICATIONS OF COORIDORS, BUT
 NO DIMENSIONS.
  
 PER NFPA 101 CHAPTER 14, NEW EDUCATIONAL OCCUPANCIES
  
 14.2.3.2.2 EXIT ACCESS CORRIDORS WITH A REQUIRED
 CAPACITY OF LESS THAN
 100 PERSONS SHALL HAVE NOT LESS THAN 44 IN. (1120 MM)
 OF CLEAR WIDTH.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
 1A) SHEET A 1 - CORRIDOR WALL RATING
  
 THERE APPEARS A WALL TYPE INDICATED WITH A SQUARE
 AROUND AN A BUT NO INDICATION OF TYPE OF THAT IT IS
 SMOKE RATED.
  
 14.3.6 CORRIDORS. CORRIDORS SHALL BE SEPARATED FROM
 OTHER PARTS OF THE
 STORY BY WALLS HAVING A 1-HOUR FIRE RESISTANCE RATING
 IN ACCORDANCE WITH
 SECTION 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
 (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL
 SPACES NORMALLY
 SUBJECT TO STUDENT OCCUPANCY HAVE NOT LESS THAN ONE
 DOOR OPENING
 DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR EXIT ACCESS
 BALCONY OR CORRIDOR
 IN ACCORDANCE WITH 7.5.3.
 (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7:
 (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 8.4.
 (B) THE PROVISIONS OF 8.4.3.5 SHALL NOT APPLY TO
 NORMALLY OCCUPIED
 CLASSROOMS.
 (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE
 RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR
 WALLS SHALL BE
 PERMITTED TO TERMINATE AT THE CORRIDOR CEILING.
 (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES
 BY WALLS
 HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE
 WITH SECTION 8.3.
 (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM CORRIDORS,
 PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 9.7.
 (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS
 FORM SMOKE
 PARTITIONS IN ACCORDANCE WITH SECTION 8.4.
  
 PLEASE PROVIDE DETAILS IS COMPLIANCE
  
  
  
 2) SHEET A 1 - THERE ARE DOORS TO CLASSROOMS THAT HAVE
 NO INDICATED HARDWARE.
  
  
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE
 PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF OPERATION
 AND THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS.
 ADDITIONAL INFO IF APPLICABLE....
  
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT
 MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR
 7.2.1.5.10.7.
  
 PLEASE PROVIDE THE EXACT TYPE OF HARDWARE FOR EACH
 CLASSROOM DOOR.
  
  
 ADDITIONAL INFO TO PROVIDE IF APPLICABLE....
  
 PER NFPA 101, CH 14
  
 14.2.2.2.4* CLASSROOM DOOR LOCKING TO PREVENT UNWANTED
 ENTRY.
 (1) THE LOCKING MEANS SHALL BE CAPABLE OF BEING ENGAGED
 WITHOUT
 OPENING THE DOOR.
 (2) THE UNLOCKING AND UNLATCHING FROM THE CLASSROOM
 SIDE OF THE DOOR
 CAN BE ACCOMPLISHED WITHOUT THE USE OF A KEY, TOOL, OR
 SPECIAL
 KNOWLEDGE OR EFFORT.
 (3) THE RELEASING MECHANISM SHALL OPEN THE DOOR LEAF
 WITH NOT MORE
 THAN ONE RELEASING OPERATION.
 (4) THE RELEASING MECHANISM FOR UNLOCKING AND
 UNLATCHING SHALL BE
 LOCATED AT A HEIGHT NOT LESS THAN 34 IN. (865 MM) AND
 NOT EXCEEDING
 48 IN. (1220 MM) ABOVE THE FINISHED FLOOR.
 (5) LOCKS, IF REMOTELY ENGAGED, SHALL BE UNLOCKABLE
 FROM THE CLASSROOM
 SIDE OF THE DOOR WITHOUT THE USE OF A KEY, TOOL, OR
 SPECIAL
 KNOWLEDGE OR EFFORT.
 (6) THE DOOR SHALL BE CAPABLE OF BEING UNLOCKED AND
 OPENED FROM
 OUTSIDE THE ROOM WITH THE NECESSARY KEY OR OTHER
 CREDENTIAL.
 (7) THE LOCKING MEANS SHALL NOT MODIFY THE DOOR CLOSER,
 PANIC HARDWARE,
 OR FIRE EXIT HARDWARE.
 (8) MODIFICATIONS TO FIRE DOOR ASSEMBLIES, INCLUDING
 DOOR HARDWARE,
 SHALL BE IN ACCORDANCE WITH NFPA 80.
 (9) THE EMERGENCY ACTION PLAN, REQUIRED BY 14.7.1,
 SHALL ADDRESS THE
 USE OF THE LOCKING AND UNLOCKING MEANS FROM WITHIN AND
 OUTSIDE
 THE ROOM.
 (10) STAFF SHALL BE DRILLED IN THE ENGAGEMENT AND
 RELEASE OF THE LOCKING
 MEANS, FROM WITHIN AND OUTSIDE THE ROOM, AS PART OF THE
 EMERGENCY
 EGRESS DRILLS REQUIRED BY 14.7.2.
  
  
  
 3) SHEET A 1 - THE DOOR SCHEDULE INDICATES NO HARDWARE
 INFO FOR THE EXISTING EXTERIOR DOORS 1, 6 & 7.
  
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE
 PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF OPERATION
 AND THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS.
 ADDITIONAL INFO IF APPLICABLE....
  
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF WITH NOT
 MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR
 7.2.1.5.10.7.
  
 PLEASE PROVIDE THE EXACT TYPE OF HARDWARE FOR EACH
 EXTERIOR DOOR.
  
  
  
 4) SHEET CS 1 & LS 1 - THERE IS INDICATION OF A FIRE
 SPRINKLER SYSTEM TO BE INSTALLED.
  
 PER FAC FIRE SPRINKLER DOCUMENTS SHALL BE SUBMITTED BY
 AN EOR WITH THIS MASTER PERMIT.
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 PLEASE REVIEW AND PROVIDE SIGNED AND SEALED DOCUMENTS
 PER FAC.
  
  
 4A) THE FIRE SPRINKLER SYSTEM THEN SHALL BE INSTALLED
 PER NFPA 101 CH. 14 & NFPA 13 AND SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 ANY FIRE LINE UNDEREGROUND WORK SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 5) SHEET CS 1 - THERE IS AN INDICATION OF A FIRE ALARM.
  
 ALL FIRE ALARM WORK SHALL BE INSTALLED PER NFPA 101 CH.
 14 & NFPA 72 AND SUBMITTED UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-06-24 Time   Rev Time 0.00
Received By aoliver Date 2021-06-21 Time 10:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-14 Cont ID  
Sent By rmcphers Date 2021-06-14 Time 12:50 Rev Time 0.00
Received By rmcphers Date 2021-06-07 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 15:21 Rev Time 0.00
Received By rmcphers Date 2021-05-21 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 16:41 Rev Time 0.00
Received By medwards Date 2021-04-22 Time 13:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-07-06 Cont ID  
Sent By lmarchan Date 2021-07-06 Time 08:57 Rev Time 0.00
Received By lmarchan Date 2021-06-22 Time 16:34 Sent To  
Notes
2021-07-01 14:06:10RECEIPT MU-2021-031547 - $29,512.56 - PAID
2021-06-22 16:34:186/22/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 15:04 Sent To  
Notes
2021-06-03 15:07:12CHANGE OF OCCUPANCY CLASSIFICATION - FROM A (B) TO(E
 DAY CARE)
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 15:39 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-06-24 Cont ID  
Sent By ccole Date 2021-06-24 Time 11:56 Rev Time 0.00
Received By ccole Date 2021-06-24 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By ccole Date 2021-06-11 Time 09:16 Rev Time 0.00
Received By ccole Date 2021-06-11 Time 07:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-25 Cont ID  
Sent By ccole Date 2021-05-25 Time 18:20 Rev Time 0.00
Received By ccole Date 2021-05-25 Time 13:25 Sent To  
Notes
2021-05-25 18:20:232ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21031467
 5/25/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW HAVE BEEN MARKED AS PASSED OR
 FAILED. NOTES IN CAPS HAVE BEEN ADDED TO FAILED
 COMMENTS FOR FURTHER CLARIFICATION. PLEASE NOTE THAT I
 AM AVAILABLE TO DISCUSS ANY OF THE COMMENTS WITH THE
 DESIGN PROFESSIONALS AND THE CONTRACTOR TO HELP
 EXPEDITE APPROVAL OF THE PLUMBING PLANS.
  
 1) FAILED. SHEETS CS-1, A-1 & P-1: CONCERNING TOILET RM
 113 PLEASE REFER TO SECTION 213.2 EXCEPTION-3 AND THE
 ADVISORY UNDER THE SECTION- ADVISORY 213.2 TOILET ROOMS
 AND BATHING ROOMS EXCEPTIONS 3 AND 4. A "CLUSTER" IS A
 GROUP OF TOILET ROOMS PROXIMATE TO ONE ANOTHER.
 GENERALLY, TOILET ROOMS IN A CLUSTER ARE WITHIN SIGHT
 OF, OR ADJACENT TO, ONE ANOTHER. TOILET RM 113 DOES NOT
 MEET THE EXCEPTION AND SHALL BE DESIGNED TO BE
 ACCESSIBLE IN ACCORDANCE WITH SECTIONS 213.2 AND 603.
 BASED ON TABLE 403.3 AND SECTIONS 403.2 & 403.3 IT
 APPEARS THAT A REQUIRED PUBLIC/EMPLOYEE TOILET ROOM HAS
 BEEN ELIMINATED. THE PREVIOUS PLAN SHOWED THE
 CHILDREN'S SEPARATED BOYS AND GIRLS TOILET ROOMS AND
 ALSO TOILET ROOMS- 108 & 113. THE TWO UNISEX TOILET
 ROOMS APPEARED TO MEET THE REQUIREMENT FOR SEPARATE
 FACILITIES FOR THE PUBLIC AND EMPLOYEES- SECTION 403.3.
 AND ALSO MATCHED THE FIXTURE CALCULATION TABLE ON CS-1
 WHICH INDICATED TWO UNISEX TOILET ROOMS. TOILET ROOM
 113 IS NOW CONVERTED INTO CLOSET 113, AND THE PLUMBING
 FIXTURE CALCULATIONS ON CS-1 HAVE BEEN REVISED TO SHOW
 ONE UNISEX TOILET ROOM. PLEASE REVISE THE PLAN TO SHOW
 THE TWO REQUIRED TOILET ROOMS.
  
 2) FAILED. SHEETS A-1 & P-1: REFER TO SECTION 403.2 FBC
 P AND LABEL TOILET RM 113 AS EITHER MALE OR FEMALE.
 REFER TO ABOVE NOTES ON COMMENT #1. SEPARATE FACILTIES
 ARE REQUIRED HOWEVER IT IS ACCEPTABLE TO LABEL BOTH
 TOILET ROOMS AS UNISEX BASED ON SECTION 403.2.1 FBC P.
 PLEASE REVISE THE PLAN TO SHOW THE LOCATIONS OF THE
 REQUIRED PUBLIC/EMPLOYEE TOILET ROOMS.
  
 ***ADVISORY FOR COMMENTS #1 & 2: THE CURRENT PLAN SHOWS
 COMPLIANCE FOR THE NUMBER OF REQUIRED ACCESSIBLE
 FIXTURES FOR THE BOYS AND GIRLS- TOILET RMS-109 AND
 112. THE FIXTURES IN GIRLS-RM 110 ARE NOT REQUIRED
 WHICH PROVIDES AN OPTION OF REDESIGNING THE ROOM TO
 MEET THE REQUIREMENT FOR THE MISSING ACCESSIBLE
 PUBLIC/EMPLOYEE TOILET ROOM FIXTURES.
  
 3) PASSED. SHEETS A-1 & P-1: REFER TO SECTIONS 604.1,
 604.9, AND ADVISORY 604.9 AND SPECIFICATIONS TABLE-
 "ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN'S USE. THE REQUIREMENTS IN 604.9 ARE TO BE
 FOLLOWED WHERE THE EXCEPTION FOR CHILDREN'S WATER
 CLOSETS IN 604.1 IS USED. THE FOLLOWING TABLE PROVIDES
 ADDITIONAL GUIDANCE IN APPLYING THE SPECIFICATIONS FOR
 WATER CLOSETS FOR CHILDREN ACCORDING TO THE AGE GROUP
 SERVED AND REFLECTS THE DIFFERENCES IN THE SIZE,
 STATURE, AND REACH RANGES OF CHILDREN AGES 3 THROUGH
 12. THE SPECIFICATIONS CHOSEN SHOULD CORRESPOND TO THE
 AGE OF THE PRIMARY USER GROUP. THE SPECIFICATIONS OF
 ONE AGE GROUP SHOULD BE APPLIED CONSISTENTLY IN THE
 INSTALLATION OF A WATER CLOSET AND RELATED ELEMENTS."
 PLEASE REVISE THE FLOOR PLAN AND ELEVATION DRAWINGS ON
 A-1 TO SHOW THE AGE DESIGNATION FOR EACH TOILET ROOM.
  
 4) PASSED. A-1: PROVIDE THE SPOUT HEIGHT FOR THE HIGH-
 STANDING PERSONS DRINKING FOUNTAIN- SECTION 602.7.
 REFER TO FIGURE 602.5 AND SHOW SPOUT LOCATIONS.
  
 5) PASSED. A-1: REFER TO SECTION AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 6) PASSED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE IN
 COMPLIANCE WITH SECTION 405 FBC P.
  
 7) FAILED. P-1 PLUMBING PLAN AND SANITARY RISER- FBC P:
 THE EWC IS NOT LABELED IN THE RISER.
  
 A) FAILED. THE 1-1/4 IN. TRAP FOR THE URINAL CANNOT BE
 APPROVED WITHOUT SUBMITTAL OF URINAL SPECIFICATIONS IN
 THE REQUESTED FIXTURE SCHEDULE- TABLE 709.1. THE
 COMMENT RESPONSE FROM THE ARCHITECT INDICATES THE
 URINAL WILL HAVE A 2 INCH TRAP HOWEVER AN 1-1/4 INCH
 TRAP IS SHOWN.
  
 B) PASSED. SHOW THE REQUIRED CLEANOUT AT THE JUNCTION
 OF THE BUILDING DRAIN AND SEWER- SECTION 708.1.3.
  
 C) PASSED. PROVIDE A VENT FOR THE WATER CLOSET IN 112-
 SECTION 901.2.1.
  
 D) PASSED. PROVIDE AN INDIVIDUAL VENT FOR THE URINAL IN
 112- SECTIONS 911.1 & 912.1.
  
 E) PASSED. THE WYE FITTING BY THE WATER CLOSET IN GIRLS
 110 IS NOT PROPERLY DIRECTING THE FLOW OF DRAINAGE FROM
 THE WATER CLOSET AND THE DRAIN PIPE FROM TOILET RM 113-
 SECTION 706.3.
  
 F) PASSED. PROVIDE THE SIZE OF THE TRAPS AT THE
 3-COMPARTMENT SINK- TABLE 709.1. PLEASE NOTE EACH WELL
 OF A MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR- SECTION 802.1.1.
 PROVIDE A DETAIL AND INDICATE WHICH TYPE OF INDIRECT
 WASTE RECEPTOR WILL BE INSTALLED AND ADD IT TO THE
 FIXTURE SCHEDULE- SECTION 802.4 FBC P.
  
 8) FAILED. P1: PLEASE PROVIDE THE SIZES OF ALL SUPPLY
 PIPES SHOWN IN THE WATER RISER- TABLE 604.5 FBC P.
 PLEASE SHOW A 3/4 INCH SUPPLY LINE TO THE URINAL PER
 THE SLOAN 186- XL-1 FLUSHOMETER SPECIFICATIONS.
  
 9) PASSED. P1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDE AT THE LAVATORIES- SECTION 419.5 AND 607.2.1
 FBC P.
  
 10) PASSED. P1: THE MAXIMUM ALLOWABLE PIPING LENGTH
 FROM THE NEAREST SOURCE OF HEATED WATER TO THE
 TERMINATION OF THE LAVATORY SUPPLY PIPES SHALL BE IN
 ACCORDANCE WITH SECTION C404.5.1 & TABLE C404.5.1 FBC
 EC.
  
 11) PASSED. P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATER INDICATING THE MAKE, MODEL, KW SIZE, AND
 EFFICIENCY RATING OF THE UNIT- TABLE C404.2 FBC EC.
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 12) PASSED. P1: PROVIDE A PIPING DIAGRAM FOR THE WATER
 HEATER- SECTION 502.1 FBC P.
  
 13) PASSED.P1: SHOW LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND PROVIDE A DEVICE SCHEDULE- SECTION 604.9
 FBC P.
  
 14) PASSED. P1: REFER TO TABLE C403.2.10 FBC EC AND
 PROVIDE THE THICKNESSES OF THE HOT WATER PIPE
 INSULATION.
  
 NEW COMMENTS BASED ON REVISED PLANS.
  
 P1 RESTROOM REFERENCE NOTES: PLEASE REMOVE RM 113
 REFERENCES IN THE SCHEDULE. RM 113 HAS BEEN CONVERTED
 TO A CLOSET. A) REMOVE OR REVISE NOTE 7 FROM RM 109. B)
 NOTE 4 HAS BEEN USED TWICE. C) THE TEXT FOR NOTE 5 IS
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-28 Cont ID  
Sent By ccole Date 2021-04-28 Time 13:27 Rev Time 0.00
Received By ccole Date 2021-04-28 Time 09:42 Sent To  
Notes
2021-04-28 13:28:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21031467
 4/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS CS-1, A-1 & P-1: CONCERNING TOILET RM 113
 PLEASE REFER TO SECTION 213.2 EXCEPTION-3 AND THE
 ADVISORY UNDER THE SECTION- ADVISORY 213.2 TOILET ROOMS
 AND BATHING ROOMS EXCEPTIONS 3 AND 4. A "CLUSTER" IS A
 GROUP OF TOILET ROOMS PROXIMATE TO ONE ANOTHER.
 GENERALLY, TOILET ROOMS IN A CLUSTER ARE WITHIN SIGHT
 OF, OR ADJACENT TO, ONE ANOTHER. TOILET RM 113 DOES NOT
 MEET THE EXCEPTION AND SHALL BE DESIGNED TO BE
 ACCESSIBLE IN ACCORDANCE WITH SECTIONS 213.2 AND 603.
  
 2) SHEETS A-1 & P-1: REFER TO SECTION 403.2 FBC P AND
 LABEL TOILET RM 113 AS EITHER MALE OR FEMALE.
  
 3) SHEETS A-1 & P-1: REFER TO SECTIONS 604.1, 604.9,
 AND ADVISORY 604.9 AND SPECIFICATIONS TABLE- "ADVISORY
 604.9 WATER CLOSETS AND TOILET COMPARTMENTS FOR
 CHILDREN'S USE. THE REQUIREMENTS IN 604.9 ARE TO BE
 FOLLOWED WHERE THE EXCEPTION FOR CHILDREN'S WATER
 CLOSETS IN 604.1 IS USED. THE FOLLOWING TABLE PROVIDES
 ADDITIONAL GUIDANCE IN APPLYING THE SPECIFICATIONS FOR
 WATER CLOSETS FOR CHILDREN ACCORDING TO THE AGE GROUP
 SERVED AND REFLECTS THE DIFFERENCES IN THE SIZE,
 STATURE, AND REACH RANGES OF CHILDREN AGES 3 THROUGH
 12. THE SPECIFICATIONS CHOSEN SHOULD CORRESPOND TO THE
 AGE OF THE PRIMARY USER GROUP. THE SPECIFICATIONS OF
 ONE AGE GROUP SHOULD BE APPLIED CONSISTENTLY IN THE
 INSTALLATION OF A WATER CLOSET AND RELATED ELEMENTS."
 PLEASE REVISE THE FLOOR PLAN AND ELEVATION DRAWINGS ON
 A-1 TO SHOW THE AGE DESIGNATION FOR EACH TOILET ROOM.
  
 4) A-1: PROVIDE THE SPOUT HEIGHT FOR THE HIGH- STANDING
 PERSONS DRINKING FOUNTAIN- SECTION 602.7. REFER TO
 FIGURE 602.5 AND SHOW SPOUT LOCATIONS.
  
 5) A-1: REFER TO SECTION AND SHOW HOW THE LOCATIONS OF
 THE FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 6) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE IN
 COMPLIANCE WITH SECTION 405 FBC P.
  
 7) P-1 PLUMBING PLAN AND SANITARY RISER- FBC P:
 A) THE 1-1/4 IN. TRAP FOR THE URINAL CANNOT BE APPROVED
 WITHOUT SUBMITTAL OF URINAL SPECIFICATIONS IN THE
 REQUESTED FIXTURE SCHEDULE- TABLE 709.1.
 B) SHOW THE REQUIRED CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND SEWER- SECTION 708.1.3.
 C) PROVIDE A VENT FOR THE WATER CLOSET IN 112- SECTION
 901.2.1.
 D) PROVIDE AN INDIVIDUAL VENT FOR THE URINAL IN 112-
 SECTIONS 911.1 & 912.1.
 E) THE WYE FITTING BY THE WATER CLOSET IN GIRLS 110 IS
 NOT PROPERLY DIRECTING THE FLOW OF DRAINAGE FROM THE
 WATER CLOSET AND THE DRAIN PIPE FROM TOILET RM 113-
 SECTION 706.3.
 F) PROVIDE THE SIZE OF THE TRAPS AT THE 3-COMPARTMENT
 SINK- TABLE 709.1. PLEASE NOTE EACH WELL OF A
 MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY
 TO A WASTE RECEPTOR- SECTION 802.1.1. PROVIDE A DETAIL
 AND INDICATE WHICH TYPE OF INDIRECT WASTE RECEPTOR WILL
 BE INSTALLED AND ADD IT TO THE FIXTURE SCHEDULE-
 SECTION 802.4 FBC P.
  
 8) P1: PLEASE PROVIDE THE SIZES OF ALL SUPPLY PIPES
 SHOWN IN THE WATER RISER- TABLE 604.5 FBC P.
  
 9) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDE AT
 THE LAVATORIES- SECTION 419.5 AND 607.2.1 FBC P.
  
 10) P1: THE MAXIMUM ALLOWABLE PIPING LENGTH FROM THE
 NEAREST SOURCE OF HEATED WATER TO THE TERMINATION OF
 THE LAVATORY SUPPLY PIPES SHALL BE IN ACCORDANCE WITH
 SECTION C404.5.1 & TABLE C404.5.1 FBC EC.
  
 11) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING THE MAKE, MODEL, KW SIZE, AND
 EFFICIENCY RATING OF THE UNIT- TABLE C404.2 FBC EC.
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 12) P1: PROVIDE A PIPING DIAGRAM FOR THE WATER HEATER-
 SECTION 502.1 FBC P.
  
 13) P1: SHOW LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND PROVIDE A DEVICE SCHEDULE- SECTION 604.9
 FBC P.
  
 14) P1: REFER TO TABLE C403.2.10 FBC EC AND PROVIDE THE
 THICKNESSES OF THE HOT WATER PIPE INSULATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 13:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-03 Cont ID  
Sent By rmcphers Date 2021-06-03 Time 15:16 Rev Time 0.00
Received By rmcphers Date 2021-06-03 Time 15:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 15:45 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 15:45 Sent To  
Notes
2021-04-28 08:40:00ELECTRICAL OK

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-02 Cont ID  
Sent By awooten Date 2021-06-02 Time   Rev Time 0.00
Received By awooten Date 2021-06-02 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-10 Cont ID  
Sent By awooten Date 2021-05-12 Time   Rev Time 0.00
Received By awooten Date 2021-05-12 Time   Sent To  
Notes
2021-05-10 14:51:33**************************ZONING REVIEW
 FAILED****************************
  
 DUMPSTER ENCLOSURE MUST MEET THE CITY'S DETAIL FOR
 ENCLOSURES. CONTACT PLANNING FOR DETAIL.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]