| 2021-04-27 11:12:50 | REVISIONS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTH ENDS OF |
| | THE RAMPS TO COMPLY WITH FBC 505.10.1 RAMP HANDRAILS |
| | SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12 |
| | INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF |
| | RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR |
| | THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE |
| | HANDRAIL OF AN ADJACENT RAMP RUN. |
| | 2) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT TOP OF ALL |
| | STAIR TO COMPLY WITH FBC 505.10.2 AT THE TOP OF A STAIR |
| | FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE |
| | LANDING FOR 12 INCHES (305 MM) MINIMUM BEGINNING |
| | DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL |
| | RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR |
| | SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT |
| | STAIR FLIGHT. |
| | 3) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTTOM OF ALL |
| | STAIR TO COMPLY WITH FBC 505.10.3 AT THE BOTTOM OF A |
| | STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE OF |
| | THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST |
| | EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. |
| | EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE LANDING |
| | SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT STAIR FLIGHT. |
| | 4) HANDRAILS SHALL BE SHOWN ON BOTH SIDES OF RAMPS AND |
| | STAIR PER FBC 1011.11 AND FBC 1012.8 |
| | 5) DRAWING A2.0 - DOORS BETWEEN UNITS IN THE CORRIDOR |
| | WERE TO SWING IN PER APPROVED DRAWINGS AS TO NOT |
| | ENCROACH IN THE EGRESS PATH FBC 1005.7.1 - DOOR SWING |
| | ON ALL OTHER PLANS SHOULD MATCH. |
| | |