| 2021-04-21 14:07:14 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21031438 |
| | |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2-LOT DRAINAGE |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | 1101.1 FBC-EXISTING BUILDING AND THE FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | 3- BEDROOM WINDOWS: SPECIFY SIZE AND TYPE OF EXISTING |
| | WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 |
| | FBC-EXISTING BUILDING. |
| | NOTE: CLARIFY WHY FLOOR PLAN SHOWS WHAT LOOKS LIKE |
| | CASEMENT WINDOWS, WHILE EXTERIOR ELEVATIONS SHOW WHAT |
| | LOOKS LIKE SINGLE HUNG WINDOWS. |
| | |
| | 4- THERE IS AN EXISTING SWIMMING POOL IN THIS PROPERTY. |
| | PROVIDE SPECIFICATIONS SHOWING HOW THE PROPOSED |
| | ADDITION WILL COMPLY WITH THE RESIDENTIAL SWIMMING |
| | BARRIER REQUIREMENT REQUIRED BY SEC. R4501.17 |
| | FBC-RESIDENTIAL. SEC. 1101.1 FBC-EXISTING BUILDING |
| | |
| | 5- DESIGN PRESSURES SHOWN ON SHEET A-2 AND S-2 DON'T |
| | MATCH. ALSO, CLARIFY WHY USING 20 S.F. AS THE TRIBUTARY |
| | AREA. PROVIDE DESIGN PRESSURES FOR EACH EFFECTIVE |
| | TRIBUTARY AREA OR IF USING THE WORST CASE SCENARIO TO |
| | COVER ALL COMPONENTS AND CLADDING DESIGN PRESSURES, |
| | THEN NEED TO USE THE ONE WITH THE LOWEST EFFECTIVE |
| | AREA. SEE FOOTNOTES ON TABLE R301.2(2) FBC-RESIDENTIAL |
| | AND REVISE AS REQUIRED. |
| | SEC. 1101.1 FBC-EXISTING BUILDING. |
| | |
| | |
| | 6- SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR THE NEW |
| | ADDITION. SEC. 1101.1 FBC-EXISTING BUILDING. SEC. |
| | R307.1 FBC-RESIDENTIAL. |
| | |
| | 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY SEC. 1101.1 |
| | FBC-EXISTING BUILDING. FAC 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)ROOF SHINGLES. |
| | B)EXTERIOR SWING DOORS AS SHOWN ON PLANS. |
| | C)SLIDING GLASS AS SHOWN ON PLANS. |
| | D)WINDOWS AS SPECIFIED ON PLANS (COORDINATE WITH ITEM |
| | #3 ABOVE). |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9-PROVIDE STRUCTURAL BUCK DETAILS FOR WINDOWS AND DOORS |
| | (SWING AND SLIDING GLASS DOORS). SPECIFY THE SIZE OF |
| | THE STRUCTURAL BUCK. STRUCTURAL BUCK NEEDS TO PROVIDE |
| | FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC. |
| | R609.7.2.1 FBC-RESIDENTIAL. |
| | SEC. 1101.1 FBC-EXISTING BUILDING. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |