Plan Review Details - Permit 21031410
Plan Review Stops For Permit 21031410
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 15:35 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 15:35 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 08:34 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 08:33 Sent To  
Notes
2021-07-12 08:34:46PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 10:05 Sent To  
Notes
2021-05-20 10:06:03PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-08-17 Cont ID  
Sent By rmcphers Date 2021-08-17 Time 07:35 Rev Time 0.00
Received By rmcphers Date 2021-08-17 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 15:30 Sent To  
Notes
2021-08-12 15:31:26ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ACCESSIBLE RESTROOMS - PLEASE SHOW MIRROR MAXIMUM
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 08:19 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 08:19 Sent To  
Notes
2021-07-12 08:33:46ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ACCESSIBLE RESTROOMS - PLEASE SHOW MIRROR MAXIMUM
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE
 REFLECTIVE SURFACE FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 2) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION
 DIMENSIONS FOR THE REQUIRED GRAB BARS AT THE TOILETS
 FBC 604.5 GRAB BARS.
 GRAB BARS FOR WATER CLOSETS SHALL COMPLY WITH 609. GRAB
 BARS SHALL BE PROVIDED ON THE SIDE WALL CLOSEST TO THE
 WATER CLOSET AND ON THE REAR WALL.
 604.5.1SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 08:29 Sent To  
Notes
2021-05-20 10:05:10ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WHEN RESTROOMS ARE ALTERED OR NEW, THEY NEED TO
 COMPLY WITH FBC ACCESSIBILITY 202.3 - 213.2 - PLEASE
 SHOW ALL DETAIL DIMENSIONS FOR TOILETS, SINKS, GRAB
 BARS, TOILET TISSUE DISPENSERS, FIXTURE FLOOR SPACE,
 DOOR OPENINGS ETC. PER ACCESSIBILITY REQUIREMENTS FBC
 ACCESSIBILITY.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-07-08 Cont ID  
Sent By jleahy Date 2021-07-08 Time 14:14 Rev Time 0.00
Received By jleahy Date 2021-07-08 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By jleahy Date 2021-05-12 Time 16:44 Rev Time 0.00
Received By jleahy Date 2021-05-12 Time 15:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By   Date 2021-06-22 Time   Rev Time 0.00
Received By bdolan Date 2021-06-22 Time 15:01 Sent To  
Notes
2021-06-22 15:02:44SEE PRIOR NOTES FROM 5/19
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By pleduc Date 2021-05-19 Time   Rev Time 0.00
Received By pleduc Date 2021-05-14 Time 12:12 Sent To  
Notes
2021-05-19 10:41:46FIRE PROVISO:
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWING.
  
 ALL ACCESS CONTROL SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 KNOX PADLOCKS ARE RECOMMENDED, NOT REQUIRED, AT
 EACH SWING GATE FOR FD EMERGENCY ACCESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-08-17 Time   Rev Time 0.00
Received By aoliver Date 2021-07-27 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-07-14 Time   Rev Time 0.00
Received By aoliver Date 2021-06-21 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-17 Cont ID  
Sent By medwards Date 2021-06-17 Time 09:18 Rev Time 0.00
Received By medwards Date 2021-03-31 Time 14:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 10:06 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 10:06 Sent To  
Notes
2021-05-20 10:06:45NO NEW AC SPACE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 09:41 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 08:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-08-17 Cont ID  
Sent By ccole Date 2021-08-17 Time 10:04 Rev Time 0.00
Received By ccole Date 2021-08-17 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-14 Cont ID  
Sent By ccole Date 2021-07-14 Time 12:16 Rev Time 0.00
Received By ccole Date 2021-07-13 Time 17:22 Sent To  
Notes
2021-07-14 12:17:162ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21031410
 7/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW. NOTES IN CAPS HAVE BEEN
 ADDED FOR FURTHER CLARIFICATION.
  
 2) FAILED. A200 & A300: THE PLANS ARE INDICATING NON-
 COMPLIANCE FOR REQUIRED CLEAR FLOOR SPACES AT THE NEW
 WATER CLOSETS AND LAVATORIES; AND INSUFFICIENT
 INFORMATION AND DETAILS AS REQUIRED BY THE FBC ACC.
 PLEASE REVIEW THE LIST OF REQUIRED DETAILS BELOW AND
 REVISE THE PLANS TO SHOW COMPLIANCE. THE BATHROOMS
 SHALL BE DESIGNED AND CONSTRUCTED IN FULL COMPLIANCE
 WITH THE FBC ACC. THE EXCEPTION FOR GRAB BARS UNDER
 SECTION 604.5 THAT IS BEING CITED ON A300 IS FOR
 PRIVATE OFFICES. THE PLANS ARE INDICATING OFFICES
 CONVERTED INTO MEN'S AND WOMEN'S LOUNGES AND LOCKER
 ROOMS. FOR CLARITY AND TO HELP EXPEDITE REVIEW PLEASE
 PROVIDE CLEAR DIMENSIONED DRAWINGS OF THE BATHROOMS
 WITHOUT FLOOR TILE OR OTHER FINISH MATERIAL GRAPHICS
 WHICH MAY OBSCURE THE REQUIRED COMPLIANCE DETAILS AND
 DIMENSIONS- SECTION 107.2.1 WPB.
  
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3. THE CLEAR FLOOR
 SPACE SHALL BE MINIMUM 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. NOT PROVIDED.
  
 C) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 T-SHAPE DIMENSIONS NOT PROVIDED.
  
 G) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SECTION 603.3
 INDICATE THE MEASUREMENT TO THE BOTTOM EDGE OF THE
 REFLECTIVE SURFACE.
  
 H) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604. NOT PROVIDED.
  
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONTS OF THE WATER CLOSETS- SECTION
 AND FIGURE 604.7. THE DISPENSER SHALL BE 7 INCHES
 MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
  
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. NOT PROVIDED.
  
 M) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.3 &
 609.4. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE.
  
 O) FAILED. SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION
 608.6. PROVIDE A SHOWER SPRAY UNIT WITH A HOSE 59
 INCHES LONG MINIMUM THAT CAN BE USED BOTH AS A
 FIXED-POSITION SHOWER HEAD AND AS A HAND-HELD SHOWER
 SHALL BE PROVIDED. THE SHOWER SPRAY UNIT SHALL HAVE AN
 ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF. IF AN
 ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120 DEGREES F MAXIMUM.
  
 P) FAILED. LOCATION OF ACCESSIBLE SHOWER SEAT AND
 DIMENSIONS- SECTIONS 610.3 & 610.3.2 (FIGURE 610.3.2).
 PLEASE INDICATE THE SEAT SHALL BE A FOLDING TYPE AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE DRAWING
 SHOWS IT RIGHT TO THE EDGE OF THE OPENING WITH NO
 MARGIN FOR ERROR.
  
 10) FAILED. P1.1 & P7.0: INDICATE HOW THE WATER
 SOFTENER WILL BE PROTECTED AGAINST CONTAMINATION-
 SECTION 608.13 FBC P. PROTECTION FOR THE PWC-1 NOT
 PROVIDED. IDENTIFY THE EQUIPMENT IN THE MECHANICAL ROOM
 BEING SUPPLIED BY THE 1/2 IN. POTABLE WATER LINE FROM
 THE PWC AND PROVIDE A MEANS OF BACKFLOW PREVENTION TO
 PROTECT THE PWC AND THE POTABLE WATER SERVICE- SECTION
 608.3 & 608.17.2 FBC P.
  
 11) FAILED. PROVIDE A SHOWER PAN DETAIL- SECTION
 421.5.2 FBC P. THE NEW DETAIL ON A300 SHOWS A 1/8 IN.
 SLOPE FOR THE PAN, HOWEVER A MINIMUM 1/4 IN. PER FT.
 (2-PERCENT) SLOPE IS REQUIRED.
  
 12) FAILED. P6.0: PROVIDE THE EFFICIENCY RATING OF THE
 NEW WATER HEATER AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- TABLE C404.2 FBC EC. NOT PROVIDED.
  
 NEW COMMENTS:
  
 1) P1.1 & P7.0: PLEASE VERIFY THAT HOT WATER AT A
 TEMPERATURE OF 110 DEGREES F WILL BE PROVIDED TO THE
 DISHWASHER AND LUNCH ROOM SINK, AND THE DEVELOPED
 LENGTH OF THE HOT WATER PIPE DOES NOT EXCEED 50 FT.-
 SECTION 607.2 FBC P.
  
 2) PROVIDE HOT WATER PIPE INSULATION SPECIFICATIONS-
 SECTION 607.5 FBC P.
  
 3) P0.2: PROVIDE MANUFACTURER?S SPECIFICATIONS FOR THE
 WATER METER COVER TO VERIFY IT HAS THE PROPER TRAFFIC
 DUTY RATING TO PROTECT THE METER- SECTION 305.7 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By ccole Date 2021-05-12 Time 14:05 Rev Time 0.00
Received By ccole Date 2021-05-12 Time 09:56 Sent To  
Notes
2021-05-12 14:06:001ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21031410
 5/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS LS100. AD200, A200 & A300: IF THERE IS NO
 EXEMPTION BEING CITED FOR REVIEW, THEN THE PROPOSED
 BATHROOMS SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE FBC- 2020 7TH EDITION ACCESSIBILITY
 CODE. PLEASE REVISE THE APPLICABLE CODE DATA ON LS100.
  
 2) A200 & A300: THE PLANS ARE INDICATING NON-
 COMPLIANCE FOR REQUIRED CLEAR FLOOR SPACES AT THE NEW
 WATER CLOSETS AND LAVATORIES; AND INSUFFICIENT
 INFORMATION AND DETAILS AS REQUIRED BY THE FBC ACC.
 PLEASE REVIEW THE LIST OF REQUIRED DETAILS BELOW AND
 REVISE THE PLANS TO SHOW COMPLIANCE:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINKS RIMS FROM THE FINISHED
 FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 SHOWERS:
 L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.2.
 M) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2.
 N) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2.
 O) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 P) LOCATION OF ACCESSIBLE SHOWER SEAT AND DIMENSIONS-
 SECTIONS 610.3 & 610.3.2 (FIGURE 610.3.2).
  
 4) A400: THE FINISH SCHEDULE SPECIFICATIONS INDICATE
 GWB FOR THE RESTROOM AND SHOWER WALLS. GWB IS
 NON-COMPLIANT MATERIAL FOR BOTH THE ROOM WALLS AND
 SHOWER WALLS- SEE SECTION 310.3 FBC P, AND SECTIONS
 1210.2.2 & 12102.3 FBC B.
  
 5) PD101: SHOW AREAS OF SLAB DEMOLITION AND PROVIDE
 SLAB REPAIR DETAILS- SECTION 107.2.1 WPB.
  
 6) P01, PD1.1, & P1.1: WHAT DO THE WATER LINE SYMBOL
 ABBREVIATIONS A.C AND B.F INDICATE? THEY ARE NOT
 DEFINED ON ANY OF THE PLANS THAT I SEE- SECTION 107.2.1
 WPB.
  
 7) P02: PLACE A NOTE ON THE PLAN THAT THE RPZ WILL BE
 INSTALLED UNDER A SEPARATE PERMIT AS REQUIRED BY THE
 CITY OF WEST PALM BEACH BUILDING DEPT- SECTION 105.1 &
 107.2.1 WPB.
  
 8) P02: THERE IS NOTE REFERENCING A CIVIL UTILITY SITE
 PLAN WHICH HAS NOT BEEN SUBMITTED. PLEASE PROVIDE THE
 PLAN FOR CLARIFICATION- SECTION 107.2.1 WPB.
  
 9) P10: PROVIDE A CLEANOUT AT THE JUNCTION OF THE
 WOMEN'S BUILDING DRAIN/SEWER JUNCTION- SECTION 708.1.3
 FBC P.
  
 10) P1.1 & P7.0: INDICATE HOW THE WATER SOFTENER WILL
 BE PROTECTED AGAINST CONTAMINATION- SECTION 608.13 FBC
 P.
  
 11) PROVIDE A SHOWER PAN DETAIL- SECTION 421.5.2 FBC P.
  
 12) P6.0: PROVIDE THE EFFICIENCY RATING OF THE NEW
 WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 TABLE C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By rmcphers Date 2021-08-12 Time 15:35 Rev Time 0.00
Received By rmcphers Date 2021-08-12 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By rmcphers Date 2021-07-12 Time 08:39 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 08:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 10:15 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 10:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-16 Cont ID  
Sent By kalexand Date 2021-06-16 Time 13:17 Rev Time 0.00
Received By kalexand Date 2021-06-16 Time 13:17 Sent To I
Notes
2021-06-16 13:33:42AS STAMPED ON PLANS, A SEPARATE PERMIT IS REQUIRED FOR
 APPROVAL OF NEW FENCE.