Plan Review Details - Permit 21031397
Plan Review Stops For Permit 21031397
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By pvalenti Date 2021-04-27 Time 14:13 Rev Time 0.00
Received By pvalenti Date 2021-04-27 Time 14:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By rmcphers Date 2021-04-19 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2021-04-19 Time 11:06 Sent To  
Notes
2021-04-19 11:07:40PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-07-19 Cont ID  
Sent By rmcphers Date 2021-07-19 Time 07:59 Rev Time 0.00
Received By rmcphers Date 2021-07-19 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 09:54 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 09:39 Sent To  
Notes
2021-07-02 09:40:02CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DOCUMENT LABELED "TRUMP PLAZA GHP4 CALCS
 (06.21.2021) - SS.PDF" WINDOW / DOOR CALCULATIONS SHOW
 THAT SOME OF THE PRODUCT APPROVALS PROVIDED DO NOT MEET
 THE REQUIRED PRESSURES. A COMMENT ON THE CALCULATIONS
 SAY THAT IT IS OK TO BE WITHIN 5% OF THE DESIGN
 PRESSURE - PLEASE HAVE THE ENGINEER EXPLAIN IN WRITING
 WHERE THAT IS ALLOWED PER THE FBC
 2) PRODUCT APPROVALS NEED TO MEET THE REQUIRED DESIGN
 LOADS FBC 1609.1.1
 3) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 12:27 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 12:02 Sent To  
Notes
2021-06-22 12:21:54CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE SWING DOOR NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 FBC WPB 107.3.4
 2) PLEASE PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING
 THE SIZES AND TYPES OF EXTERIOR WINDOWS AND DOORS.
 3) FLOORING TEST REPORTS PROVIDED SHOW A DROP CEILING
 AS PART OF THE ASSEMBLY TESTED. (EXISTING BUILDING MAY
 NOT HAVE A DROP CEILING SIMULAR TO THE TEST REPORT).
 4) FLOORING TEST REPORTS PROVIDED ARE FOR AN 8"
 CONCRETE SLAB - PLEASE HAVE THE DESIGNER STATE ON THE
 DRAWINGS THE THICKNESS OF THE EXISTING CONCRETE SLAB OR
 THE DESIGNER CAN REVIEW AND MARK THE TEST REPORTS
 APPROVED FBC WPB 107.3.4
  
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: FOR
 THE NEW TILE FLOOORING
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 10:03 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 09:54 Sent To  
Notes
2021-05-24 10:01:47CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVAL FOR THE NEW EXTERIOR SWING DOORS. MAYBE THE
 SWING DOORS SHOWN FROM THE BEDROOMS ARE CASEMENT
 WINDOWS - PLEASE PROVIDE A WINDOW AND DOOR SCHEDULE
 SHOWING THE SIZES AND TYPES OF EXTERIOR WINDOWS AND
 DOORS.
 2) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER WHO DESIGNED THEM. FBC WPB 107.1
 3) DRAWING A-13 SHOWS THE ELEVATOR LOBBY DOORS REMOVED
 - PLEASE REVISE TO MATCH ALL OTHER DRAWINGS.
 4) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 FOR THE NEW TILE FLOOORING
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 5) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By rmcphers Date 2021-04-19 Time 12:01 Rev Time 0.00
Received By rmcphers Date 2021-04-19 Time 09:15 Sent To  
Notes
2021-04-19 12:01:53CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVAL FOR THE NEW EXTERIOR SWING DOORS.
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE ARCHITECT OF RECORD.
 3) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER WHO DESIGNED THEM. FBC WPB 107.1
 4) PLEASE SHOW WALL FRAMING DETAILS AND MATERIAL TO
 COMPLY WITH FBC 603
 5) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE SHOW
 DESIGN PER THE CODE IN EFFECT (FBC 2020 USING ASCE
 7-16)
 6) PLEASE SHOW THE ELEVATOR HOISTWAY PROTECTION PER FBC
 3006.3
 7) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 FOR THE NEW TILE FLOOORING
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-17 Cont ID  
Sent By jleahy Date 2021-05-17 Time 16:48 Rev Time 0.00
Received By jleahy Date 2021-05-17 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By jleahy Date 2021-04-19 Time 15:35 Rev Time 0.00
Received By jleahy Date 2021-04-19 Time 15:19 Sent To  
Notes
2021-04-19 15:37:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) RISER SHOWS 250A FUSES ON 4/0 NEEDS TO BE 225A FUSES
 OR 250 KCMIL WIRE.
  
 2) WEST SIDE BALCONIES REQUIRE OUTLETS WP/GFCI. 210.52

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By jleahy Date 2021-05-19 Time 12:12 Rev Time 0.00
Received By jleahy Date 2021-05-19 Time 12:12 Sent To  
Notes
2021-05-19 12:12:56TV'S ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By pleduc Date 2021-04-21 Time   Rev Time 0.00
Received By pleduc Date 2021-04-20 Time 10:17 Sent To  
Notes
2021-04-20 10:25:22FIRE PROVISO:
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER SYSTEMS
 SHALL BE MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD, INCLUDING DEMO.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-19 Cont ID  
Sent By rmcphers Date 2021-07-19 Time 08:01 Rev Time 0.00
Received By rmcphers Date 2021-07-08 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 12:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 12:27 Rev Time 0.00
Received By rmcphers Date 2021-06-08 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 10:04 Rev Time 0.00
Received By rmcphers Date 2021-05-06 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 07:59 Rev Time 0.00
Received By rmcphers Date 2021-03-31 Time 08:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-19 Cont ID  
Sent By rmcphers Date 2021-04-19 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-04-19 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-04 Cont ID  
Sent By medwards Date 2021-05-14 Time 08:01 Rev Time 0.00
Received By medwards Date 2021-05-14 Time 08:01 Sent To  
Notes
2021-05-14 08:01:23 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By medwards Date 2021-04-19 Time 13:01 Rev Time 0.00
Received By medwards Date 2021-04-19 Time 11:03 Sent To  
Notes
2021-04-19 13:01:471ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21031397
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE CONSULTING ENGINEER MUST STAMP AND SIGN THE
 MECHANICAL DRAWINGS OR THE MECHANICAL CONTRACTOR THAT
 HAS THE SUB PERMIT TO INSTALL THE MECHANICAL SYSTEM CAN
 PRINT AND SIGN THEIR NAME ON THE DRAWINGS. F.S.
 471.003(H)
  
 2) PLEASE PROVIDE SPECS. FOR THE KITCHEN STOVE AND THE
 KITCHEN HOOD. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-12 Cont ID  
Sent By lcrespo Date 2021-05-12 Time 14:16 Rev Time 0.00
Received By lcrespo Date 2021-05-12 Time 14:16 Sent To  
Notes
2021-05-12 14:17:0605/12/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-20 Cont ID  
Sent By lcrespo Date 2021-04-20 Time 11:29 Rev Time 0.00
Received By lcrespo Date 2021-04-20 Time 09:54 Sent To  
Notes
2021-04-20 11:30:0704/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM REQUIRED FOR
 THE AREAS WHERE CHANGES ARE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 2. THE 2017 6TH EDITION IS REFERENCED ON THE TITLE
 SHEET, AND ON THE MEP PAGE, THE 2020 7TH EDITION IS
 REFERENCED. PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ON THIS PAGE, THERE ARE ACCECIBLITY NOTES
 WHICH ARE NOT REQUIRED FOR A UNIT IN A BUILDING IN THE
 BATHROOM, SO PLEASE DELETE THEM IF THEY DON?T PERTAIN
 TO THIS RENOVATION FOR FIELD CLARITY.
  
 3. WHERE OR IF THE FLOOR WILL BE CUT TO ACCOMMODATE
 PIPING, PLEASE PROVIDE DETAIL FOR THE REPAIR OF THE
 CONCRETE DECK PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
 5.
  
 6. SUGGESTED VERBIAGE FOR SHOWER PAN PER THE 2020 FBC
 SECTION P 421.5.2 SHOWER LINING. FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6. SUCH LINERS SHALL TURN UP ON ALL
 SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED
 THRESHOLD LEVEL. LINERS SHALL BE RECESSED AND FASTENED
 TO AN APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE
 REQUIRED FOR WALL COVERING, AND SHALL NOT BE NAILED OR
 PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE
 THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
  
 7. SUGGESTED VERBIAGE FOR TUBS VALVES PER THE 2020 FBC
 SECTION P 412.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES.
 THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL
 BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF
 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 412.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By rgathrig Date 2021-06-22 Time 17:39 Rev Time 0.00
Received By rgathrig Date 2021-06-22 Time 17:39 Sent To  
Notes
2021-06-22 17:40:34PRIVATE PROVIDER INSPECTIONS ONLY ******* APPROVED
  
 RICHARD GATHRIGHT
 561 805 6679
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-07-19 Cont ID  
Sent By pvalenti Date 2021-07-19 Time 15:51 Rev Time 0.00
Received By pvalenti Date 2021-07-19 Time 15:50 Sent To  
Notes
2021-07-19 15:55:07 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW APPROVED BY SUBMITTAL OF ORIGINAL HAND
 SIGNED/SEALED BY REGISTERED ARCHITECT (JEROME BAUMOEHL)
 PAPER PLAN SHEET A-12.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-07-19 Cont ID  
Sent By rmcphers Date 2021-07-19 Time 07:59 Rev Time 0.00
Received By rmcphers Date 2021-07-19 Time 07:59 Sent To  
Notes
2021-07-19 08:01:26SIGNATURE REVIEW
 DRAWING A12 DOES NOT SHOW AS ELECTRONICALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES NOT
 HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP
 OFF THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 TO THE FRONT DESK IN THE BUILDING DIVISION AT THE CITY
 HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 09:57 Sent To  
Notes
2021-07-02 09:57:46SIGNATURE REVIEW
 SEVERAL DRAWINGS ARE NOT SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1
 SEVERAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 12:26 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 12:22 Sent To  
Notes
2021-06-22 12:26:51SIGNATURE REVIEW
 SEVERAL DRAWINGS ARE NOT SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1
 SEVERAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED
 IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 10:04 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 10:04 Sent To  
Notes
2021-05-24 10:04:26SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By rmcphers Date 2021-04-19 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-04-19 Time 11:08 Sent To  
Notes
2021-04-19 11:09:06SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL