Plan Review Details - Permit 21031299
Plan Review Stops For Permit 21031299
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-26 Cont ID  
Sent By rmcdouga Date 2021-05-26 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2021-05-26 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 11:33 Sent To  
Notes
2021-04-07 11:36:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRE-FABRICATED GENERATOR PAD DRAWINGS HAVE
 SEVERAL REFERENCES TO THE FBC SIXTH EDITION (2017). THE
 FBC SEVENTH EDITION (2020) WENT INTO EFFECT ON DECEMBER
 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE 2020
 FBC SEVENTH EDITION. FS CHAPTER 553
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-06 Cont ID  
Sent By jleahy Date 2021-04-06 Time 13:11 Rev Time 0.00
Received By jleahy Date 2021-04-06 Time 09:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2021-05-27 Cont ID  
Sent By lmarchan Date 2021-05-27 Time 15:30 Rev Time 0.00
Received By lmarchan Date 2021-05-27 Time 15:30 Sent To  
Notes
2021-05-27 15:30:41GAS SUBMITTED SEPARATELY 21051585
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 16:12 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 15:09 Sent To  
Notes
2021-05-18 16:13:002ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21031299
 5/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 NFPA 58
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW PRINTED BELOW WERE NOT ADDRESSED- NO GAS PLANS,
 RISER, OR TANK/EQUIPMENT SPECIFICATIONS WERE SUBMITTED.
  
 1) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB.
 REFER TO NFPA 58 AND PROVIDE:
 A) TYPES AND SIZES OF PIPING TO BE INSTALLED.
 B) DELIVERY PRESSURE AT THE TANK.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES (IF APPLICABLE).
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 3) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW
 THE TANK WILL BE ANCHORED TO PREVENT FLOTATION,
 COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58.
 PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT
 SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND
 THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM
 CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED
 CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA
 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODE, INLET
 AND OUTLET PRESSURES AND PIPE SIZES- SECTION 6.10.1
 NFPA 58.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By ccole Date 2021-04-15 Time 12:10 Rev Time 0.00
Received By ccole Date 2021-04-15 Time 11:54 Sent To  
Notes
2021-04-15 12:11:131ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 21031299
 4/15/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB.
 REFER TO NFPA 58 AND PROVIDE:
 A) TYPES AND SIZES OF PIPING TO BE INSTALLED.
 B) DELIVERY PRESSURE AT THE TANK.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES (IF APPLICABLE).
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 3) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW
 THE TANK WILL BE ANCHORED TO PREVENT FLOTATION,
 COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58.
 PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT
 SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND
 THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION
 BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM
 CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED
 CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA
 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODE, INLET
 AND OUTLET PRESSURES AND PIPE SIZES- SECTION 6.10.1
 NFPA 58.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-08 Cont ID  
Sent By lmarchan Date 2021-06-08 Time 12:07 Rev Time 0.00
Received By lmarchan Date 2021-05-11 Time 06:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2021-03-27 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 16:16 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 15:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By ccole Date 2021-04-15 Time 12:00 Rev Time 0.00
Received By ccole Date 2021-04-15 Time 11:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-26 Cont ID  
Sent By rmcdouga Date 2021-05-26 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2021-05-26 Time 15:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 11:33 Sent To  
Notes
2021-04-07 11:35:15THE PRE-FABRICATED GENERATOR PAD DETAILS DO NOT HAVE
 THE ENGINEER'S DIGITAL SIGNATURE. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By kalexand Date 2021-06-07 Time 09:12 Rev Time 0.00
Received By kalexand Date 2021-06-07 Time 09:12 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By kalexand Date 2021-04-21 Time 15:13 Rev Time 0.00
Received By kalexand Date 2021-04-21 Time 15:13 Sent To I
Notes
***NONE***