Plan Review Details - Permit 21031237
Plan Review Stops For Permit 21031237
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By rmcphers Date 2021-05-13 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2021-05-13 Time 14:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By rmcphers Date 2021-04-08 Time 13:52 Rev Time 0.00
Received By rmcphers Date 2021-04-08 Time 13:52 Sent To  
Notes
2021-04-08 13:53:17PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By rmcphers Date 2021-05-13 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2021-05-13 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By rmcphers Date 2021-04-08 Time 13:53 Rev Time 0.00
Received By rmcphers Date 2021-04-08 Time 13:53 Sent To  
Notes
2021-04-08 13:59:21REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) IS THE UNIT ON THE FIRST FLOOR? IS THERE A UNIT
 BELOW THIS UNIT? - IF NO UNIT BELOW THIS ONE WRITE ON
 THE DRAWINGS THAT THERE IS NO UNIT BELOW THIS UNIT.
 FBC 1207.2AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
 FBC 1207.3STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS AND
 SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR SLEEPING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS RATING OF NOT
 LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, WHEN
 TESTED IN ACCORDANCE WITH ASTM E492.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 11:36 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-29 Cont ID  
Sent By pleduc Date 2021-04-29 Time   Rev Time 0.00
Received By pleduc Date 2021-04-29 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By pleduc Date 2021-04-08 Time   Rev Time 0.00
Received By pleduc Date 2021-04-08 Time 12:58 Sent To  
Notes
2021-04-08 13:05:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) FLOOR PLAN SHEET - THERE IS NO ADDRESS INDICATED ON
 THE FLOOR PLAN.
  
 PLEASE PROVIDE.
  
  
 2) FLOOR PLAN SHEET - THERE APPEARS TO BE INDICATORS
 WITHIN THE LAUNDRY ROOM; HOWEVER, THERE IS NOTHING
 INDICATED WITHIN THE SCOPE OF WORK.
  
 PLEASE PROVIDE CLARIFICATIONS.
  
 2A) FLOOR PLAN SHEET - ARE ALL WALLS EXISTING? ARE ANY
 WALLS RELOCATED?
  
 PLEASE PROVIDE CLARIFICATIONS.
  
  
 3) FLOOR PLAN SHEET - THERE IS CEILING WORK INDICATED.
  
 ALL FIRE SPRINKLERS SHALL BE PROTECTED FROM
 DAMAGE/PAINT AND REMAIN FUNCTIONAL THROUGHOUT DEMO AND
 CONSTRUCTION.
  
 ANY FIRE SPRINKLER, EVEN SPRINKLER HEAD REPLACEMENT,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWING.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-27 Cont ID  
Sent By jesmith Date 2021-05-27 Time 08:38 Rev Time 0.00
Received By jesmith Date 2021-05-27 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-13 Cont ID  
Sent By rmcphers Date 2021-05-13 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2021-04-28 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-13 Cont ID  
Sent By jesmith Date 2021-04-13 Time 15:20 Rev Time 0.00
Received By jesmith Date 2021-04-13 Time 15:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-04-08 Cont ID  
Sent By rmcphers Date 2021-04-08 Time 13:59 Rev Time 0.00
Received By rmcphers Date 2021-04-08 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 07:29 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 07:26 Sent To  
Notes
2021-04-12 07:29:41NO MECHANICAL WORK SHOWN ON THIS PROJECT. ME

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By jesmith Date 2021-05-27 Time 08:37 Rev Time 0.00
Received By jesmith Date 2021-05-27 Time 08:33 Sent To  
Notes
2021-05-27 08:37:4721031237 630 S SAPODILLA AVE STE 111
  
 PLUMBING APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 THE OWNER AND DESIGNER OF RECORD HAVE PROVIDED A
 NOTARIZED AFFIDAVIT STATING THAT THE OWNER AGREES TO
 REVERT THE UNIT BACK TO COMPLIANCE WITH THE
 REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES AT THE TIME OF SALE IF REQUESTED BY THE
 BUYER.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By lcrespo Date 2021-05-06 Time 12:54 Rev Time 0.00
Received By lcrespo Date 2021-05-06 Time 10:51 Sent To  
Notes
2021-05-06 12:54:5105/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS UNIT WAS BUILT UNDER THE FAIR HOUSING ACT OF
 MARCH 6, 1991, AND SHALL COMPLY WITH FAIR HOUSING ACT
 (7) (2) (A). IT HAS A SIDE APPROACH THAT WILL MAKE IT A
 B-TYPE UNIT. PLEASE SHOW THE CLEAR FLOOR SPACE IN FRONT
 OF THE SHOWER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. THE CABINET MUST BE A MAXIMUM OF 34" UNDER THE FAIR
 HOUSING ACT DESIGN MANUAL PAGE 7.52. YOU MAY CHOOSE TO
 OMIT THIS CHANGE. THE CITY OF WEST PALM BEACH BUILDING
 DEPARTMENT PROVIDES AN OPTION FOR CHANGING AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 COMPLIANCE AT THE TIME OF SALE IF REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER-TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER, AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected], AND I WILL SEND A COPY OF
 THE FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-13 Cont ID  
Sent By jesmith Date 2021-04-13 Time 15:03 Rev Time 0.00
Received By jesmith Date 2021-04-13 Time 13:51 Sent To  
Notes
2021-04-13 14:57:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21031237 630 S SAPODILLA AVE STE 111
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER
 TO PROVIDE DIGITAL SIGNATURE IN ACCORDANCE WITH FAC AND
 FS OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT
 PRIOR TO PERMIT ISSUANCE. CALL 561-805-6724 FOR
 ADDITIONAL INFORMATION
 SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
  
 2.PER WPB FBC 107.2.1, SHOW ON EXISTING FLOOR PLAN ALL
 ORIGINAL PLUMBING FIXTURES ON THE PLAN INCLUDING
 KITCHEN SINK, WATER CLOSET, LAVATORY AND BATHTUB. THIS
 APPEARS TO BE ON THE FIRST FLOOR.PLEASE CONFIRM.
 ADDITIONALLY CLARIFY IF IT IS THE GROUND FLOOR (SLAB ON
 GRADE) OR AN ELEVATED FLOOR (I.E. ABOVE A PARKING
 GARAGE).
  
 3. PER WPB FBC 107.2.1, SHOW ON PROPOSED FLOOR PLAN ALL
 PLUMBING FIXTURES ON THE PLAN INCLUDING KITCHEN SINK,
 WATER CLOSET, LAVATORY AND SHOWER. SHOW DIMENSIONS OF
 SHOWER TO COMPLY WITH FBC PL 421.4.
  
 4. PER FBC PL 412.3, SHOWER CONTROL VALVE SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 5. PER WPB FBC 107.2.1, PROVIDE ELEVATION VIEW OF
 SHOWER WALL/CURB/LINER SHOWING THE FOLLOWING IN
 COMPLIANCE WITH FBC PL 421.3, 421.4.1 AND 421.5 THROUGH
 421.5.2.6 (SECTIONS NOTED BELOW FOR REFERENCE)
 INCLUDING BUT NOT LIMITED TO:
 A. DRAIN
 B. HEIGHT OF WALL TILE
 C. FLOOR SURFACE
 D. SUPPORT
 E. CURB/THRESHOLD
 F. SLOPED LINER
 G. LINER BACKING
 H. LINER MATERIAL
  
 REFERENCE
 421.3 SHOWER WASTE OUTLET.
 WASTE OUTLETS SERVING SHOWERS SHALL BE NOT LESS THAN
 11/2 INCHES (38 MM) IN DIAMETER AND, FOR OTHER THAN
 WASTE OUTLETS IN BATHTUBS, SHALL HAVE REMOVABLE
 STRAINERS NOT LESS THAN 3 INCHES (76 MM) IN DIAMETER
 WITH STRAINER OPENINGS NOT LESS THAN 1/4 INCH (6.4 MM)
 IN LEAST DIMENSION. WHERE EACH SHOWER SPACE IS NOT
 PROVIDED WITH AN INDIVIDUAL WASTE OUTLET, THE WASTE
 OUTLET SHALL BE LOCATED AND THE FLOOR PITCHED SO THAT
 WASTE FROM ONE SHOWER DOES NOT FLOW OVER THE FLOOR AREA
 SERVING ANOTHER SHOWER. WASTE OUTLETS SHALL BE FASTENED
 TO THE WASTE PIPE IN AN APPROVED MANNER.
  
 421.4.1 FLOOR AND WALL AREA.
 BATHTUB FLOORS, SHOWER FLOORS, WALL AREAS ABOVE
 BUILT-IN TUBS THAT HAVE INSTALLED SHOWER HEADS AND
 WALLS IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED OF
 SMOOTH, CORROSION-RESISTANT AND NONABSORBENT WATERPROOF
 MATERIALS. WALL MATERIALS SHALL EXTEND TO A HEIGHT OF
 NOT LESS THAN 6 FEET (1829 MM) ABOVE THE ROOM FLOOR
 LEVEL, AND NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE
 DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A
 WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE
 TUB OR SHOWER FLOOR.
  
 421.5 SHOWER FLOORS OR RECEPTORS.
 FLOOR SURFACES SHALL BE CONSTRUCTED OF IMPERVIOUS,
 NONCORROSIVE, NONABSORBENT AND WATERPROOF MATERIALS.
  
 421.5.1 SUPPORT.
 FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE
 LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE.
  
 421.5.2 SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 421.5.2.1 THROUGH 421.5.2.6. SUCH LINERS
 SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 INCHES (51
 MM) ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. THE
 COMPLETED LINER SHALL BE TESTED IN ACCORDANCE WITH
 SECTION 312.9.
 EXCEPTIONS:
 . 1.FLOOR SURFACES UNDER SHOWER HEADS PROVIDED FOR
 RINSING LAID DIRECTLY ON THE GROUND ARE NOT REQUIRED TO
 COMPLY WITH THIS SECTION.
 . 2.WHERE A SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANE IS INSTALLED AS THE SHOWER LINING,
 THE MEMBRANE SHALL NOT BE REQUIRED TO BE RECESSED.
 . 3.SHOWER COMPARTMENTS WHERE THE FINISHED SHOWER DRAIN
 IS DEPRESSED A MINIMUM OF 2 INCHES (51 MM) BELOW THE
 SURROUNDING FINISHED FLOOR ON THE FIRST FLOOR LEVEL AND
 THE SHOWER RECESS IS POURED INTEGRALLY WITH THE
 ADJOINING FLOOR.
  
 421.5.2.1PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL MEET
 THE REQUIREMENTS OF ASTM D4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 421.5.2.2CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL
 MEET THE REQUIREMENTS OF ASTM D4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 421.5.2.3SHEET LEAD.
 SHEET LEAD SHALL WEIGH NOT LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M2) AND SHALL BE COATED WITH AN
 ASPHALT PAINT OR OTHER APPROVED COATING. THE LEAD SHEET
 SHALL BE INSULATED FROM CONDUCTING SUBSTANCES OTHER
 THAN THE CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT
 FELT OR AN EQUIVALENT. SHEET LEAD SHALL BE JOINED BY
 BURNING.
  
 421.5.2.4SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B152 AND SHALL WEIGH
 NOT LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M2).
 THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR AN EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
  
 421.5.2.5SHEET-APPLIED, LOAD-BEARING, BONDED,
 WATERPROOF MEMBRANES.
 SHEET-APPLIED, LOAD-BEARING, BONDED, WATERPROOF
 MEMBRANES SHALL MEET REQUIREMENTS OF ANSI A118.10 AND
 SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 421.5.2.6LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING,
 BONDED WATERPROOF MATERIALS.
 LIQUID-TYPE, TROWEL-APPLIED, LOAD-BEARING, BONDED
 WATERPROOF MATERIALS SHALL MEET THE REQUIREMENTS OF
 ANSI A118.10 AND SHALL BE APPLIED IN ACCORDANCE WITH
 THE MANUFACTURER?S INSTRUCTIONS
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.2.1, A PAPER PLAN
 WITH WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A
 PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-04-08 Cont ID  
Sent By rmcphers Date 2021-04-08 Time 14:00 Rev Time 0.00
Received By rmcphers Date 2021-04-08 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-04-12 Cont ID  
Sent By eschneid Date 2021-04-12 Time 11:29 Rev Time 0.00
Received By eschneid Date 2021-04-12 Time 11:29 Sent To  
Notes
***NONE***