Plan Review Details - Permit 21031014
Plan Review Stops For Permit 21031014
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-03-29 Cont ID  
Sent By jwitmer Date 2021-03-29 Time 17:15 Rev Time 0.00
Received By jwitmer Date 2021-03-29 Time 17:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By jwitmer Date 2021-05-18 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2021-05-18 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By jwitmer Date 2021-04-30 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2021-04-30 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-29 Cont ID  
Sent By jwitmer Date 2021-03-29 Time 18:09 Rev Time 0.00
Received By jwitmer Date 2021-03-29 Time 17:14 Sent To  
Notes
2021-03-29 17:48:45WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21031014
 ADD: 1200 S. FLAGLER DR. # PH-4
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: ON. MARCH 29TH/ 2021
 ACTION: DENIED
  
 1) THE COVER SHEET UNDER THE HEADING PROJECT DATA:
  
 1A) THE LIST OF CODES THIS PLAN WAS DEVELOPED WAS THE
 2017 FLORIDA FAMILY OF CODES. PLEASE BE AWARE THE 2020
 FLORIDA FAMILY OF CODES WAS ADOPTED STATEWIDE ON DEC.
 31/ 2020. PLEASE UPDATE YOUR PLANS.
  
 1B) UNDER THE HEADING THE CONSTRUCTION TYPE LISTED IS
 V-B UN-PROTECTED, UN-SPRINKLERED MAIN HOUSE. PLEASE
 UPDATE PLANS UNDER THE 2020 FLORIDA BUILDING CODE 7TH
 EDITION THIS BUILDING IS CONSIDERED A HIGHRISE AND
 CONSTRUCTION TYPE I-A, SPRINKLERED.
  
  
 2) DEMOLITION PLAN. THE FLOOR PLAN INDICATES STRUCTURAL
 WORK ON THE BALCONY SLABS, CONCRETE AND STEEL COLUMN
 REPAIR WITH TRIANON CONDOMINIUM ASSOCIATION. PLEASE
 NOTE THIS WORK WOULD BE UNDER A SEPARATE PERMIT, REVIEW
 WITH ASSOCIATED FEES. THIS BUILDING IS A THRESHOLD
 BUILDING AND REQUIRE THRESHOLD DOCUMENTS/ FORMS
 SUBMITTED WITH CONCRETE REPAIR PERMIT.
  
 3) SHEET DOORS & FINISH SCHEDULES. THE FINISH SCHEDULE
 FOR THE FLOORS INDICATES WOOD FLOORING WHEREAS THE
 FLOOR INSULATION SUBMITTED WHISPER MAT CS IS FOR
 PORCELAIN TILE NOT WOOD. FLOOR INSULATION (FBC-B 2020)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-25 Cont ID  
Sent By fgiaquin Date 2021-05-25 Time 20:21 Rev Time 0.00
Received By fgiaquin Date 2021-05-25 Time 19:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By fgiaquin Date 2021-05-04 Time 23:08 Rev Time 0.00
Received By fgiaquin Date 2021-05-04 Time 22:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-31 Cont ID  
Sent By fgiaquin Date 2021-03-31 Time 22:19 Rev Time 0.00
Received By fgiaquin Date 2021-03-31 Time 21:06 Sent To  
Notes
2021-03-31 22:19:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATON. FBC 107.2.1 NEC220
  
 2. NO SMOKE AND CARBON MONOXIDE ALARMS SHOWN. PROVIDE
 LOCATIONS PER FBC-RE 314 AND 315
  
 3. PROVIDE PANEL SCHEDULE. FBC 107.2.1
  
 4. PROVIDE NOTE ON PLAN FOR ARC-FAULT 210.12 (A) (B)
  
 5. PROVIDE NOTE FOR TAMPERPROOF RECEPTACLES PER NEC
 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By pleduc Date 2021-05-18 Time   Rev Time 0.00
Received By pleduc Date 2021-05-18 Time 14:57 Sent To  
Notes
2021-05-18 14:57:50FIRE PROVISO:
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTIANED THROUGHOUT
 CONSTRUCTION, INCLUDING DEMO
  
 ALL FIRE ALARM WORK, INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 ENSURE SD'S ARE PLACED IN BEDROOM AND OUTSIDE BEDROOM
 PER NFPA
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-29 Cont ID  
Sent By pleduc Date 2021-04-29 Time   Rev Time 0.00
Received By pleduc Date 2021-04-29 Time 13:35 Sent To  
Notes
2021-04-29 13:41:39FIRE PROVISO:
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTIANED THROUGHOUT
 CONSTRUCTION, INCLUDING DEMO
  
 ALL FIRE ALARM WORK, INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 ENSURE SD'S ARE PLACED IN BEDROOM AND OUTSIDE BEDROOM
 PER NFPA
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-29 Cont ID  
Sent By pleduc Date 2021-03-29 Time   Rev Time 0.00
Received By pleduc Date 2021-03-29 Time 12:50 Sent To  
Notes
2021-03-29 12:58:38FIRE PROVISO:
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTIANED THROUGHOUT
 CONSTRUCTION, INCLUDING DEMO
  
 ALL FIRE ALARM WORK, INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 ENSURE SD'S ARE PLACED IN BEDROOM AND OUTSIDE BEDROOM
 PER NFPA
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-08 Cont ID  
Sent By medwards Date 2021-06-08 Time 15:50 Rev Time 0.00
Received By medwards Date 2021-05-27 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 14:20 Rev Time 0.00
Received By medwards Date 2021-05-17 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-05-05 Time   Rev Time 0.00
Received By aoliver Date 2021-04-28 Time 10:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-08 Time   Rev Time 0.00
Received By ccarvaja Date 2021-03-24 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-06-08 Cont ID  
Sent By medwards Date 2021-06-08 Time 15:48 Rev Time 0.00
Received By ccole Date 2021-06-08 Time 16:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 14:20 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 16:59 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 16:59 Sent To  
Notes
2021-05-04 17:00:471ST CYCLE COMMENTS ADDRESSED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By hmoser Date 2021-04-05 Time 13:40 Rev Time 0.00
Received By hmoser Date 2021-04-05 Time 11:22 Sent To  
Notes
2021-04-05 13:40:17PLAN DENIED
 1) REFER TO SECTION 505.1 DOMESTIC KITCHEN EXHAUST
 EQUIPMENT. 2020 FBC (M)
 EXHAUST DUCT SHALL HAVE A SMOOTH INNER WALLS, SHALL BE
 AIR TIGHT, SHALL BE EQUIPPED
 WITH A BACKDRAFT DAMPER AND SHALL BE INDEPENDENT OF ALL
 OTHER EXHAUST SYSTEMS.
 2) REFER TO SECTION 607.5.5 SHAFT INCLOSURE'S EXCEPTION
 1.1 2020 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-26 Cont ID  
Sent By ccole Date 2021-05-26 Time 10:41 Rev Time 0.00
Received By ccole Date 2021-05-26 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By ccole Date 2021-05-05 Time 13:44 Rev Time 0.00
Received By ccole Date 2021-05-05 Time 12:11 Sent To  
Notes
2021-05-05 13:45:272ND REVIEW FBC-2020 PLUMBING
 PERMIT-21031014
 5/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: THE REVISED P-1 RISER PLAN SHOWS A 1-1/2
 IN.FIXTURE DRAIN WITH NO TRAP FOR THE ICE MAKER
 CONNECTING TO THE SANITARY STACK. CLARIFY IF THE DRAIN
 IS MAKING A DIRECT CONNECTION TO THE ICE MAKER OR IF AN
 INDIRECT CONNECTION IS BEING MADE USING A FLOOR DRAIN.
 PLEASE NOTE THAT FLOOR DRAINS SHALL HAVE A DRAIN OUTLET
 NOT LESS THAN 2 INCHES IN DIAMETER. IF A FLOOR DRAIN IS
 TO BE INSTALLED THE FLOOR MAY HAVE TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO
 VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
  
 2) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB TO INSTALL A FLOOR DRAIN WILL REQUIRE FIRESTOPPING
 TO SEAL THE ANNULAR SPACE AROUND THE PIPING. IF
 APPLICABLE PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P, AND SECTION 714.4.1.2 FBC B.
  
 3) P1.1: CLARIFY WHAT LIQUID IS BEING DRAINED FROM THE
 ICE MAKER- CONDENSATION FROM COOLING COILS OR ICE MELT
 DRAINAGE? PLEASE NOTE THAT CONDENSATION FROM COOLING
 COILS IS PROHIBITED FROM DRAINING INTO THE SANITARY
 SYSTEM PER SECTION 90-126 WPB CODE OF ORDINANCES.
  
 4) P1.1: THE WATER RISER DOES NOT SHOW A SUPPLY
 CONNECTION TO THE NEW ICE MAKER. PLEASE SHOW THE
 CONNECTION AND REQUIRED DEVICES- WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTER- SECTION 604.9 AND 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-05-05 13:44:362ND REVIEW FBC-2020 PLUMBING
 PERMIT-21031014
 5/5/2021
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) SHEET P1.1: THE REVISED P-1 RISER PLAN SHOWS A 1-1/2
 IN.FIXTURE DRAIN WITH NO TRAP FOR THE ICE MAKER
 CONNECTING TO THE SANITARY STACK. CLARIFY IF THE DRAIN
 IS MAKING A DIRECT CONNECTION TO THE ICE MAKER OR IF AN
 INDIRECT CONNECTION IS BEING MADE USING A FLOOR DRAIN.
 PLEASE NOTE THAT FLOOR DRAINS SHALL HAVE A DRAIN OUTLET
 NOT LESS THAN 2 INCHES IN DIAMETER. IF A FLOOR DRAIN IS
 TO BE INSTALLED THE FLOOR MAY HAVE TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO
 VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
 2) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB TO INSTALL A FLOOR DRAIN WILL REQUIRE FIRESTOPPING
 TO SEAL THE ANNULAR SPACE AROUND THE PIPING. IF
 APPLICABLE PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P, AND SECTION 714.4.1.2 FBC B.
 3) P1.1: CLARIFY WHAT LIQUID IS BEING DRAINED FROM THE
 ICE MAKER- CONDENSATION FROM COOLING COILS OR ICE MELT
 DRAINAGE? PLEASE NOTE THAT CONDENSATION FROM COOLING
 COILS IS PROHIBITED FROM DRAINING INTO THE SANITARY
 SYSTEM PER SECTION 90-126 WPB CODE OF ORDINANCES.
 4) P1.1: THE WATER RISER DOES NOT SHOW A SUPPLY
 CONNECTION TO THE NEW ICE MAKER. PLEASE SHOW THE
 CONNECTION AND REQUIRED DEVICES- WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTER- SECTION 604.9 AND 608.3 FBC P.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 14:58 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 13:04 Sent To  
Notes
2021-04-08 14:58:241ST REVIEW FBC-2020 PLUMBING
 PERMIT-21031014
 4/8/2019
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: PROVIDE A SCOPE OF WORK ON THE PLAN FOR
 THE REMODELED KITCHEN AND BATHS. PROVIDE A LIST OF
 FIXTURES, APPLIANCES, FAUCETS, VALVES AND PIPES BEING
 REPLACED OR RELOCATED- SECTION 107.2.1 WPB.
  
 2) P1.1: PROVIDE SHOWER PAN DETAILS- SECTION 421.5 FBC
 P.
  
 3) P1.1: PROVIDE SHOWER FLOOR AND WALL FINISH DETAILS
 AND DIMENSIONS- SECTION 421.4.1 FBC P.
  
 4) P1.1: ADD THE ICE MAKER DRAIN LINE TO THE ISOMETRIC
 DRAWING- SECTION 107.3.5.3.1 WPB.
  
 5) P1.1: PROVIDE WATER SUPPLY RISER DRAWING SHOWING THE
 TYPES AND SIZES OF WATER PIPES, POINTS OF HW AND CW
 CONNECTIONS, AND LOCATIONS OF WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS- SECTIONS 604.9, 607.1, AND
 608.3 FBC P.
  
 6) P1.1: REFER TO SECTION 1002.1 FBC P: VERIFY THE
 HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE NEW
 SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE INLET OF
 THE EXISTING TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A
 NOTE ON THE PLAN INDICATING COMPLIANCE.
  
 7) P1.1: RELOCATING THE TUB AND SHOWER DRAIN OUTLETS
 MAY REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO
 LOCATE REINFORCING STEEL OR POST STRESSED FLOOR
 TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO VERIFY
 COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
  
 8) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P, AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-08 Cont ID  
Sent By medwards Date 2021-06-08 Time 15:50 Rev Time 0.00
Received By medwards Date 2021-06-08 Time 15:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-05-26 Cont ID  
Sent By ccole Date 2021-05-26 Time 10:47 Rev Time 0.00
Received By ccole Date 2021-05-26 Time 10:47 Sent To  
Notes
2021-05-26 10:48:373RD REVIEW FBC-2020 SIGNATURE
 PERMIT- 21031014
 5/26/2021
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED
 2ND SIGNATUIRE REQUEST.
  
 1) SHEET M1.1 IS NOT DIGITALLY SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD AS REQUIRED BY FL STATUTE 481.221
 AND SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
 ALL OTHER UPDATED SHEETS ARE APPROVED.
 SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By ccole Date 2021-05-05 Time 13:45 Rev Time 0.00
Received By ccole Date 2021-05-05 Time 12:11 Sent To  
Notes
2021-05-05 13:46:512ND REVIEW FBC-2020 SIGNATURE
 PERMIT- 21031014
 5/5/2021
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED
 2ND SIGNATUIRE REQUEST.
  
 1) THE PLANS ARE NOT DIGITALLY SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD AS REQUIRED BY FL STATUTE 481.221
 AND SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
 SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 13:58 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 13:04 Sent To  
Notes
2021-04-08 14:08:471ST REVIEW FBC-2020 SIGNATURE
 PERMIT- 21031014
 4/8/2021
  
 CODES IN EFFECT:
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE PLANS ARE NOT DIGITALLY SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD- FL STATUTE 481.221 AND SECTION
 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
 SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  