| 2021-04-13 12:32:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21030997 1177 CLARE AVE # 7 |
| | MASTER PERMIT #21020517 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR PROPOSED WATER |
| | HEATER AND PROVIDE A SCHEDULE FOR THE SAME NOTING |
| | MANUFACTURER, MODEL NUMBER, TYPE (TANKLESS OR TANK |
| | TYPE), ENERGY SOURCE (ELECTRICAL WITH ELECTRICAL |
| | CHARACTERISTICS-WATTAGE-VOLTAGE-PHASE OR GAS WITH BTU |
| | DEMAND), GPM OR STORAGE CAPACITY. |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR INSTALLATION |
| | OF WATER HEATER; INCLUDE CONNECTIONS, MOUNTING AND |
| | APPLICABLE REQUIREMENTS OF FBC PL 503 AND 504 (IF TANK |
| | TYPE). |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE DIMENSIONS OF BATHROOM; |
| | SHOW WHEELCHAIR TURNING SPACE, WATER CLOSET AND VANITY |
| | CLEAR FLOOR SPACES COMPLYING WITH FBC ACC 604.3.1, 304 |
| | AND 305. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE DETAIL OF VANITY |
| | SHOWING KNEE AND TOE SPACE COMPLYING WITH FBC ACC 306. |
| | |
| | 5. PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 4 TO READ |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH FBC ACC 309.4 |
| | AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN |
| | FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| | THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | |
| | 6. PER WPB FBC 107.2.1, ADD THE FOLLOWING NOTES TO THE |
| | PLUMBING NOTES. |
| | . A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL |
| | OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION PER FBC ACC 604.2 |
| | . B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | . C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | . D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | . E. FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| | . F. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| | FBC ACC 604.4. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |