| Plan Review Stops For Permit 21030991 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
5 |
Status |
P |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-08-01 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-08-01 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2022-08-01 08:07:04 | HALF ADDRESS READDRESSED TO 250 MALVERNE RD |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
F |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-19 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-19 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2022-07-19 15:45:46 | SPOKE WITH OWNER PROPOSED THE ADDRESS OF 250 MALVERNE | | | RD, STATED THEY WOULD GET BACK TO ME, AT THIS TIME HALF | | | ADDRESS ISSUES HAVE NOT BEEN ADDRESSED. PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2022-05-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-07 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-07 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2022-05-07 09:48:23 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-31 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-31 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2022-03-31 12:57:10 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-03-22 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-03-22 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2021-03-22 08:05:09 | HALF ADDRESS VIOLATION ON PROPERTY THE EAST BLDG NEEDS | | | TO BE READDRESSED. PLEASE HAVE OWNER CONTACT | | | [email protected] TO DISCUSS ADDRESSING OPTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-12 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-08-12 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2022-08-12 13:50:32 | THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-08 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-08 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2022-07-08 08:34:17 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) OK, MODEL # RXSW200A3, 22KW, 445 POUNDS AS PER | | | SUBMITTED MANUAL. | | | | | | 2) NOT RESOLVED. PROVIDE DETAILS OF THE EXISTING | | | GENERATOR SLAB AND SPECIFY THE NUMBER, TYPE AND SIZE OF | | | THE FASTENERS THAT WILL BE USED TO ANCHOR THE GENERATOR | | | TO THE SLAB TO RESIST WIND LOADS. FBC AMENDMENTS | | | 107.2.1 | | | | | | 3) NOT RESOLVED. SHOW THAT THE GENERATOR IS LOCATED 5 | | | FEET FROM THE WALLS OF ANY BUILDING. FBC? FUEL GAS | | | 616.1 POWERED EQUIPMENT. PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION ENGINES AND | | | TURBINES SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER?S INSTRUCTIONS AND NFPA 37. STATIONARY | | | ENGINE GENERATOR ASSEMBLIES SHALL MEET THE REQUIREMENTS | | | OF UL 2200. | | | | | | 4) NOT RESOLVED. SHOW THAT THE GENERATOR EXHAUST IS AT | | | LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | FBC?R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 5) NOT RESOLVED. THE VALUE FOR THIS PROJECT OF $2350.00 | | | APPEARS TO BE LOW. FOR PERMITTING PURPOSES THE | | | VALUATION IS REQUIRED TO INCLUDE THE COSTS OF THE | | | LABOR, MATERIALS, OVERHEAD AND PROFIT AS WOULD BE | | | CHARGED BY A CONTRACTOR. PROVIDE A COMPLETE SCOPE OF | | | WORK WITH A COST BREAKDOWN. FBC AMENDMENTS 109.3 | | | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, | | | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE | | | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHEDDATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES | | | (MARSHALL?SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE?SUBMITTAL FORM. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-04-25 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-25 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2022-04-25 17:18:03 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT RESOLVED. [SUBMIT DETAILED SPECIFICATIONS FOR | | | THE GENERATOR MODEL THAT WILL BE INSTALLED.] SUBMIT THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE NEW GENERATOR. | | | SPECIFY THE MODEL NUMBER AND KW OF THE NEW GENERATOR. | | | FBC AMENDMENTS 107.2.1 | | | | | | 2) NOT RESOLVED. PROVIDE DETAILS OF THE EXISTING | | | GENERATOR SLAB AND SPECIFY THE NUMBER, TYPE AND SIZE OF | | | THE FASTENERS THAT WILL BE USED TO ANCHOR THE GENERATOR | | | TO THE SLAB TO RESIST WIND LOADS. FBC AMENDMENTS | | | 107.2.1 | | | | | | 3) NOT RESOLVED. SHOW THAT THE GENERATOR IS LOCATED 5 | | | FEET FROM THE WALLS OF ANY BUILDING. FBC- FUEL GAS | | | 616.1 POWERED EQUIPMENT. PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION ENGINES AND | | | TURBINES SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER'S INSTRUCTIONS AND NFPA 37. STATIONARY | | | ENGINE GENERATOR ASSEMBLIES SHALL MEET THE REQUIREMENTS | | | OF UL 2200. | | | | | | 4) NOT RESOLVED. SHOW THAT THE GENERATOR EXHAUST IS AT | | | LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. | | | FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 5) NOT RESOLVED. THE VALUE FOR THIS PROJECT OF $2350.00 | | | APPEARS TO BE LOW. FOR PERMITTING PURPOSES THE | | | VALUATION IS REQUIRED TO INCLUDE THE COSTS OF THE | | | LABOR, MATERIALS, OVERHEAD AND PROFIT AS WOULD BE | | | CHARGED BY A CONTRACTOR. PROVIDE A COMPLETE SCOPE OF | | | WORK WITH A COST BREAKDOWN. FBC AMENDMENTS 109.3 | | | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, | | | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE | | | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-04-07 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-04-07 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2021-04-07 10:08:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | | GENERATOR. SPECIFY THE MODEL NUMBER AND KW OF THE NEW | | | GENERATOR. FBC AMENDMENTS 107.2.1 | | | | | | 2) PROVIDE DETAILS OF THE EXISTING GENERATOR SLAB AND | | | SPECIFY THE NUMBER, TYPE AND SIZE OF THE FASTENERS THAT | | | WILL BE USED TO ANCHOR THE GENERATOR TO THE SLAB TO | | | RESIST WIND LOADS. FBC AMENDMENTS 107.2.1 | | | | | | 3) SHOW THAT THE GENERATOR IS LOCATED 5 FEET FROM THE | | | WALLS OF ANY BUILDING. FBC- FUEL GAS 616.1 POWERED | | | EQUIPMENT. PERMANENTLY INSTALLED EQUIPMENT POWERED BY | | | INTERNAL COMBUSTION ENGINES AND TURBINES SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S | | | INSTRUCTIONS AND NFPA 37. STATIONARY ENGINE GENERATOR | | | ASSEMBLIES SHALL MEET THE REQUIREMENTS OF UL 2200. | | | | | | 4) SHOW THAT THE GENERATOR EXHAUST IS AT LEAST 10 FEET | | | FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE | | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS. | | | | | | 5) THE VALUE FOR THIS PROJECT OF $2350.00 APPEARS TO BE | | | LOW. FOR PERMITTING PURPOSES THE VALUATION IS REQUIRED | | | TO INCLUDE THE COSTS OF THE LABOR, MATERIALS, OVERHEAD | | | AND PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. PROVIDE | | | A COMPLETE SCOPE OF WORK WITH A COST BREAKDOWN. FBC | | | AMENDMENTS 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-17 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-17 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2022-07-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-30 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-30 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2022-07-30 15:24:20 | 7K MAY COVER THE COST OF THE EQUIPMENT BUT NOT BOTH | | | MATERIAL AND LABOR.. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-05-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-15 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-15 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2022-05-15 15:39:05 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE OF THE WORK IS NOT IN CONFORMANCE WITH INDUSTRY | | | STANDARDS. PLEASE SUBMIT A COST BREAKDOWN OF ALL | | | MATERIALS AND LABOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-04-19 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-04-19 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2022-04-19 11:58:11 | ELECTRIC REVIEW FAILED | | | | | | 1 NO ELECTRIC PLANS INCLUDED FOR REVIEW. PLEASE SUBMIT | | | ALL DRAWINGS, CALCULATIONS AND SPECIFICATIONS AS | | | REQUIRED . FBC 107.2 AND NEC 215.5 | | | | | | 2) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, | | | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR | | | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-03-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-03-25 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-03-25 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2021-03-25 14:59:02 | PLAN REVIEW GENERATOR / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER | | | SWITCH. ? ATS | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2) PROVIDE NEW LOAD CALCULATIONS. INCLUDE LOAD SHARING. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3) PROVIDE CURRENT COPY OF GENERATOR MANUFACURERS | | | SPECIFICATIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4) PROVIDE CABLE SIZING BETWEEN ATS AND MDP, ATS AND | | | GENERATOR, INCLUDE CONTROL CIRCUIT WIRING. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5) PROVIDE ELECTRICAL RISER DIAGRAHM. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-04 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-04 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-08-12 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-18 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-08 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-05 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-25 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-30 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-22 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-23 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-04 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-04 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-03-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-24 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-24 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-07-27 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-07-27 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-07-27 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-04-05 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-04-05 |
Time |
16:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-04-21 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-04-21 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-04-21 09:04:55 | PROVISO: | | | | | | GENERATORS CANNOT ENCROACH MORE THAN 4 FEET INTO ANY | | | SETBACK | | | | | | | | | RAFAELA THERMIDOR | | | ASSOCIATE PLANNER, [email protected] |
|
|