Plan Review Details - Permit 21030959
Plan Review Stops For Permit 21030959
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-26 Cont ID  
Sent By rmcphers Date 2021-04-26 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2021-04-26 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-05 Cont ID  
Sent By rmcphers Date 2021-04-05 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2021-04-05 Time 13:48 Sent To  
Notes
2021-04-05 13:53:45BATH REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FOR THE TILE FLOORING REPLACEMENT PLEASE PROVIDE THE
 FOLLOWING DOCUMENTS -
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ([email protected])
  
 2) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - (JOB VALUE IS MATERIAL AND LABOR)
 FBC 109.3 - PLEASE PROVIDE A SIGNED CONTRACT SHOWING
 THE JOB VALUE.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-26 Cont ID  
Sent By rmcphers Date 2021-04-26 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-06 Cont ID  
Sent By jesmith Date 2021-04-06 Time 15:17 Rev Time 0.00
Received By jesmith Date 2021-04-06 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By abelisle Date 2021-04-20 Time 17:34 Rev Time 0.00
Received By abelisle Date 2021-04-20 Time 16:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By jesmith Date 2021-04-06 Time 15:16 Rev Time 0.00
Received By jesmith Date 2021-04-06 Time 15:15 Sent To  
Notes
2021-04-06 15:16:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.P1 APPEARS TO INDICATE THAT THE EXISTING BATHTUB IS
 TO BE REPLACED WITH A NEW BATHTUB. PER WPB FBC 107.2.1,
 CLARIFY WHETHER OR NOT THIS IS CORRECT. IF SO THEN
 CLARIFY THAT IT IS THE SAME CONFIGURATION AS THE
 ORIGINAL BATHTUB AND WILL NOT REQUIRE A NEW SLAB
 PENETRATION FOR THE DRAIN. PLEASE BE SPECIFIC.
  
 2.PER WPB FBC 107.2.1, CLARIFY WHETHER OR NOT A SHOWER
 HEAD WILL BE PROVIDED.
  
 3. ARE YOU REPLACING THE EXISTING CONTROL VALVE? IF
 PROVIDING A NEW CONTROL VALVE, PER WPB FBC 107.2.1,
 SPECIFY THE NEW VALVE AND PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL. VALVE SHALL COMPLY
 WITH FBC PL 412.3. A ROUGH IN INSPECTION WILL BE
 REQUIRED FOR THE IN-WALL PLUMBING.
  
 4. PER WPB FBC 107.2.1 PROVIDE DETAIL OR SCHEDULE
 SHOWING WALL AREAS ABOVE BUILT-IN TUBS THAT HAVE
 INSTALLED SHOWER HEADS AND WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL
 EXTEND TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) ABOVE THE DRAIN OF THE TUB OR SHOWER. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB OR SHOWER FLOOR AS REQUIRED BY
 FBC PL 421.4.1.
  
 5.VALUE OF JOB SEEMS LOW WHEN COMPARED TO ENTIRE SCOPE
 OF WORK. PROVIDE AN ACCURATE VALUATION OF ALL WORK AND
 COST. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL (1)CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030959 610 CLEMATIS ST 515

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-03-22 Cont ID  
Sent By equinone Date 2021-03-22 Time 12:14 Rev Time 0.00
Received By equinone Date 2021-03-22 Time 12:14 Sent To  
Notes
***NONE***