| 2021-04-02 16:39:06 | 04/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET GI0.1; |
| | A. PLEASE PROVIDE THE APPLICABLE CODE AND VOLUME BEING |
| | USED PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3 |
| | APPLICATION OF REFERENCES. |
| | |
| | B. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS INTERIOR |
| | BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | C. PLEASE GIVE THE LEVEL OF ALTERATION PER 2020 FLORIDA |
| | EXISTING BUILDING CODE 301.1. |
| | |
| | IT IS NOTED THAT ON ALS1.0 SOME OF THIS INFORMATION IS |
| | THERE BUT PLEASE COPY TO THIS PAGE AND PLUMBING IF |
| | POSSIBLE BUT NOT NECESSARY. |
| | |
| | 2. ON SHEET ALS0.1; |
| | 3. SOME OF THESE COMMENTS MAY BE IN A4.0, BUT THEY ARE |
| | NOT CONSISTENT OR REFERENCED TO EACH OTHER. YOU MAY |
| | CHOOSE TO COMBINE OR CORRECT. |
| | |
| | A. ON DETAIL NINE, PLEASE SHOW THE MIRROR DIMENSIONS OF |
| | 40" TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. |
| | 603.3. |
| | |
| | B. PLEASE SHOW THE DIMENSION OF THE TOILET 17" INCHES |
| | TO 19" INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT |
| | PER THE 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | C. GRAB BARS ON THE HORIZONTAL NEED TO BE MEASURED |
| | CENTER TO CENTER PER THE 2020 FBC SEC. 604.5.2 REAR |
| | WALL. PLEASE ALSO SHOW THE SIDE WALL PER THE 2020 FBC |
| | SEC. 604.5.1 SIDE WALL. |
| | |
| | D. PROVIDE DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO THE |
| | WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC |
| | SEC. 602.2 CLEAR FLOOR SPACE AND PLEASE SHOW KNEE AND |
| | TOE CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE |
| | 2020 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH |
| | 2020 FBC ACC SEC. 307.2 PROTRUSION LIMITS. |
| | |
| | E. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES ON |
| | LAVS, URINAL, SINKS TOILETS, AND DRINKING FOUNTAIN PER |
| | FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE. |
| | |
| | F. PLEASE SHOW DETAILS OF THE BACKING FOR GRAB BARS |
| | REINFORCEMENT THAT MUST BE SUFFICIENT TO PERMIT THE |
| | INSTALLATION OF REAR AND SIDE WALL GRAB BARS THAT FULLY |
| | MEET ALL ACCESSIBILITY REQUIREMENTS, INCLUDING, BUT NOT |
| | LIMITED TO, REQUIRED LENGTH, INSTALLATION HEIGHT, AND |
| | STRUCTURAL STRENGTH. |
| | |
| | G. DETAIL 10 HAS THE HORIZONTAL GRAB BARS TO THE EDGES |
| | OF THE DIMENSION, AND THEY NEED TO BE TO THE CENTER. |
| | |
| | IT IS NOTED THAT THE FBC ACC IS IN REFERENCE BUT CAN |
| | THE YEAR BE ADDED TO IT, PLEASE. |
| | |
| | 4. ON SHEET A1.0; |
| | A. THE DRINKING FOUNTAIN IS IN A BREAK ROOM THAT IS NOT |
| | CLEAR IF THE BREAK ROOM IS FOR PATIENTS. IF SO, PLEASE |
| | PROVIDE SIGN-AGE TO THE DRINKING FOUNTAIN LOCATION |
| | SOMEWHERE IN THE LOBBY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. PLEASE SHOW ALL ACCESSIBLE, CLEAR FLOOR SPACE FOR |
| | FIXTURE CLEARANCES PER FLORIDA BUILDING CODE AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | |
| | C. PLEASE CLEARLY SHOW THE COOLER ON THE PLANS AND |
| | ACCESSIBILITY REQUIREMENTS INCLUDING CLEAR FLOOR SPACE |
| | APPROACH AND REACH RANGES TO CONTROLS 2017 FBC ACC SEC. |
| | 305 & 308. |
| | |
| | D. AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH |
| | TYPE PROVIDED IN EACH ACCESSIBLE ROOM PER THE 2020 FBC |
| | ACC SEC. 212.3 SINKS. |
| | |
| | 5. ON SHEET A4.0; |
| | A. DETAIL A, THE DOOR SWING INTO THE CLEAR FLOOR SPACE |
| | OR CLEARANCE OF 30? X 48? PER THE 2020 FBC-ACC SEC. |
| | 604.8.1.2. |
| | |
| | B. ELEMENTS ARE MISSING IS MANY DETAILS AND DIMENSION; |
| | FOR EXAMPLE, THE MIRROR INS THE ACCESSIBLE COMPARTMENT |
| | NOT SHOW AND NO DIMENSION FOR THE LAV ON IN THE OPEN |
| | AREA, THE GRAB BARS HAVE NO DIMENSIONS. |
| | |
| | C. THE TOILET SHOWS A DIMENSION OF 1"-6" AND NEEDS TO |
| | ADD THE 1" -8" MAX PER THE 202 FBC ACC SEC. 604.2. |
| | |
| | D. DOOR HANDLES HARDWARE SHOULD BE NOTED ON BOTH SIDES |
| | OF THE DOOR PER THE 2017 FBC ACC SEC. 404.2.7. |
| | |
| | E. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | F. PLEASE SHOW CLEAR FLOOR SPACE FOR URINAL PER THE |
| | 2020 FBC-ACC SEC. 604.8.1.2. |
| | |
| | G. ON DETAIL TWO, THE TOILET HANDLE ON THE WRONG SIDE, |
| | 2020 FBC ACC 604.6. |
| | |
| | H. PLEASE SHOW THE CLEAR FLOOR SPACE DIMENSION FOR BOTH |
| | RESTS ROOMS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | I. ON DETAIL D, PLEASE SHOW THE CLEAR FLOOR SPACE FOR |
| | THE BREAK-ROOM PER THE 2017 FBC ACC SEC. 602. |
| | |
| | J. SEAT NEEDS TO BE OPEN FRONT, 2017 FBC P 420.3 WATER |
| | CLOSET SEATS. |
| | |
| | 6. ON SHEET A4.3; |
| | A. THE TOILET SHOWS A DIMENSION OF 1"-6" AND NEEDS TO |
| | ADD THE 1" -8" MAX PER THE 202 FBC ACC SEC. 604.2. |
| | |
| | B. PLEASE SHOW THE DIMENSION OF THE TOILET 17" INCHES |
| | TO 19" INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT |
| | PER THE 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | C. PLEASE SHOE ALL ACCESSIBLE, CLEAR FLOOR SPACE FOR |
| | FIXTURE CLEARANCES PER FLORIDA BUILDING CODE AND |
| | FLORIDA ACCESSIBILITY CODE. |
| | |
| | D. PLEASE SHOW THE TURNING SPACE DIAMETER- SECTION |
| | 304.3. |
| | |
| | E, PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE EXAM ROOM |
| | OF THE SINK PER THE 2020 FBC SEC. 602. |
| | |
| | 7. ON SHEET P2.0; |
| | A. PLEASE PROVIDE A VENT BETWEEN MS1 AND FD PER THE |
| | 2020 FBC SEC. 901.2. |
| | |
| | B. THE DRINKING FOUNTAIN NEEDS TO BE DOWNSTREAM OF THE |
| | WET VENT'S BATHROOM GROUPS PER THE 2020 FBC SEC. 912.1 |
| | HORIZONTAL WET VENTS PERMITTED. |
| | |
| | C. PLEASE SHOW THE TRAP PRIMER FOR THE FLOOR DRAIN PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. ON SHEET P2.1; |
| | A. THE RECIRCULATING MANIFOLD TO THE HOT WATER LINES |
| | MAY NEED TO BE CLOSER TO THE OUTLET SOURCE; PLEASE |
| | REFER TO THE 2020 FBC ENERGY CODE TABLE C404.5.1. |
| | |
| | B. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | INLINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. |
| | |
| | 9. ON SHEET P3.0; |
| | A. THE RELIEF LINE SHALL TERMINATE IN THE PAN, AND THE |
| | PAN IN MOP SINK PET THE 2020 FBC SEC P FBC P 504.7.2. |
| | |
| | B. PLEASE PROVIDE DETAIL OF THE INSULATION TYPE FOR THE |
| | RECIRCULATION SYSTEM PER THE 2020 FBC CE 404.4. IF YOU |
| | LIKE TO SET UP A ZOOM MEETING, IF SOME OF THESE |
| | COMMENTS ARE NOT CLEAR, FEEL FREE TO-CONTACT ME. THANK |
| | YOU. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-67200 |
| | |
| | |