Plan Review Details - Permit 21030892
Plan Review Stops For Permit 21030892
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By cpuell Date 2021-04-20 Time 08:42 Rev Time 0.00
Received By cpuell Date 2021-04-20 Time 08:42 Sent To  
Notes
2021-04-20 08:45:48FRONT PROPERTY HAD TWO UNITS 745 NEWARK ST AND 745 1/2
 NEWARK ST UNITS ARE TO BE COMBINED ELIMINATING THE HALF
 ADDRESS. REAR GARAGE IS ACCESSORY UNIT NO ADDRESS
 NEEDED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-25 Cont ID  
Sent By cpuell Date 2021-03-25 Time 09:30 Rev Time 0.00
Received By cpuell Date 2021-03-25 Time 09:30 Sent To  
Notes
2021-03-25 09:31:27BLDG CURRENTLY HAS TWO ADDRESSES 745 NEWARK ST AND 745
 1/2 NEWARK ST, WILL THIS DEMO AND REMODEL BE REMOVING
 THE ADDITIONAL UNIT? PLEASE RESPOND TO [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 09:31 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 12:45 Sent To  
Notes
2021-11-15 12:59:26SFR ADDITION AND SEPARATE GARAGE (PERMITS 21030892 AND
 21060942)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) ROOFING PRODUCT APPROVAL PROVIDED FOR THE LIQUID
 ROOFING SYSTEM STATES THAT "THIS IS NOT A WATER
 PROOFING SYSTEM" SEE NOTE NUMBER 4 ON THE PRODUCT
 APPROVAL (NOA18-0321.09) - MANUFACTURES NOTES - PLEASE
 PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS FOR THE ROOFING SYSTEMS. (TILE AND LOW SLOPE
 ROOF DECKS)
  
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE
 PRODUCT APPROVAL NUMBERS NEED TO BE SHOWN ON THE
 DRAWINGS.
  
 3) PLEASE SHOW ROOF DRAINAGE SYSTEM ON THE ROOF PLAN TO
 COMPLY WITH FBC R903.4
  
 4) PLEASE SHOW THE REQUIRED OVERFLOW SCUPPERS TO COMPLY
 WITH FBC R903.4.1
  
 5) PLEASE SHOW ROOF VENTILATION TO COMPLY WITH FBC
 R806.1
  
 6) PLEASE SHOW THE STEP RISER HEIGHT AND TREAD DEPTH TO
 COMPLY WITH FBC R311.7.5
  
 7) PLEASE SHOW TUB AND SHOWER WALL AREAS TO COMPLY WITH
 FBC R702.4.2
  
 8) PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-01 Cont ID  
Sent By cthroop Date 2021-10-01 Time 08:59 Rev Time 0.00
Received By cthroop Date 2021-10-01 Time 08:51 Sent To  
Notes
2021-10-01 08:50:47NOTICE: COMMENTS APPLY TO PRIMARY PERMIT 21030892 AND
 1-CAR GARAGE PERMIT 21060942
  
 BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 COMMENTS FROM 1ST REVIEW BY ROGER MCPHEARSON ON
 4/15/2021.
  
 SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW FREE STANDING GARAGE NEEDS TO BE ON A SEPARATE
 PERMIT - PLEASE ACKNOWLEDGE THIS ON THE DRAWING.
 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS
 AND ROOFING SYSTEMS.
 3) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE
 PRODUCT APPROVAL NUMBERS NEED TO BE SHOWN ON THE
 DRAWINGS.
 4) PLEASE SHOW ROOF DRAINAGE SYSTEM ON THE ROOF PLAN TO
 COMPLY WITH FBC R903.4
 5) PLEASE SHOW THE REQUIRED OVERFLOW SCUPPERS TO COMPLY
 WITH FBC R903.4.1
 6) PLEASE SHOW ROOF VENTILATION TO COMPLY WITH FBC
 R806.1
 7) PLEASE SHOW THE STEP RISER HEIGHT AND TREAD DEPTH TO
 COMPLY WITH FBC R311.7.5
 8) PLEASE SHOW TUB AND SHOWER WALL AREAS TO COMPLY WITH
 FBC R702.4.2
 9) ROOFING SYSTEMS AND WINDOW AND DOOR PRODUCT
 APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS
 TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 COMMENTS FROM REVIEW OF 1-CAR GARAGE PERMIT 21060942 BY
 C THROOP ON 9/28/2021. NO DUPLICATIONS.
  
 10, PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE
 WITH FBC R401.3 DRAINAGE.
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 11. PROVIDE DESIGN PRESSURES PER FIGURE R301.2(7)
 COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 12. PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 15:25 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 12:51 Sent To  
Notes
2021-04-15 14:57:20SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW FREE STANDING GARAGE NEEDS TO BE ON A SEPARATE
 PERMIT - PLEASE ACKNOWLEDGE THIS ON THE DRAWING.
 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS
 AND ROOFING SYSTEMS.
 3) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR THE
 PRODUCT APPROVAL NUMBERS NEED TO BE SHOWN ON THE
 DRAWINGS.
 4) PLEASE SHOW ROOF DRAINAGE SYSTEM ON THE ROOF PLAN TO
 COMPLY WITH FBC R903.4
 5) PLEASE SHOW THE REQUIRED OVERFLOW SCUPPERS TO COMPLY
 WITH FBC R903.4.1
 6) PLEASE SHOW ROOF VENTILATION TO COMPLY WITH FBC
 R806.1
 7) PLEASE SHOW THE STEP RISER HEIGHT AND TREAD DEPTH TO
 COMPLY WITH FBC R311.7.5
 8) PLEASE SHOW TUB AND SHOWER WALL AREAS TO COMPLY WITH
 FBC R702.4.2
 9) ROOFING SYSTEMS AND WINDOW AND DOOR PRODUCT
 APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS
 TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By fgiaquin Date 2021-12-07 Time 22:26 Rev Time 0.00
Received By fgiaquin Date 2021-12-07 Time 22:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-31 Cont ID  
Sent By fgiaquin Date 2021-03-31 Time 23:19 Rev Time 0.00
Received By fgiaquin Date 2021-03-31 Time 22:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2021-11-15 Cont ID  
Sent By ccole Date 2021-11-15 Time 12:05 Rev Time 0.00
Received By ccole Date 2021-11-15 Time 11:04 Sent To  
Notes
2021-11-15 12:05:46SEPARATE PERMIT AND PLANS REQUIRED FOR GAS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 17:29 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 16:27 Sent To  
Notes
2021-04-08 17:30:331ST REVIEW FBC-2020 RES.
 PERMIT- 21030892
 4/8/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P2: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE RANGE SHOWING THE BTU LOAD AND INPUT PRESSURE-
 SECTION G2447.1 FBC RES. PLEASE NOTE THAT THE SPECS AND
 INSTALL MANUAL MAY BE DEFERRED AND ONSITE AT TIME OF
 INSPECTION- SECTION 107.3.4.1 WPB.
  
 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES.
  
 3) P2: UPDATE THE FBC- 2017 CODE REFERENCE IN NOTE #1.
 THE FBC-2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/2020.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-04-08 17:29:531ST REVIEW FBC-2020 RES.
 PERMIT- 21030892
 4/8/2021
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
 1) P2: PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE RANGE SHOWING THE BTU LOAD AND INPUT PRESSURE-
 SECTION G2447.1 FBC RES. PLEASE NOTE THAT THE SPECS AND
 INSTALL MANUAL MAY BE DEFERRED AND ONSITE AT TIME OF
 INSPECTION- SECTION 107.3.4.1 WPB.
 2) P2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SECTION- G2407.1 FBC RES.
 3) P2: UPDATE THE FBC- 2017 CODE REFERENCE IN NOTE #1.
 THE FBC-2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/2020.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-03-30 Cont ID  
Sent By fmittner Date 2021-03-30 Time 12:09 Rev Time 0.00
Received By fmittner Date 2021-03-30 Time 12:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-19 Cont ID  
Sent By mpeterso Date 2022-07-19 Time 15:31 Rev Time 0.00
Received By mpeterso Date 2022-07-15 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 09:32 Rev Time 0.00
Received By rmcphers Date 2022-04-20 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-24 Cont ID  
Sent By lmarchan Date 2022-03-24 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2021-11-03 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2021-03-24 Time 17:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-08-12 Cont ID  
Sent By lmarchan Date 2022-08-12 Time 11:36 Rev Time 0.00
Received By lmarchan Date 2022-07-19 Time 15:51 Sent To  
Notes
2022-08-12 11:36:46NO FEES PER IMPACT OFFICE. LEM
2022-07-19 15:51:517/19/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 15:28 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 15:28 Sent To  
Notes
2021-04-15 15:30:24PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-09-16 Cont ID  
Sent By hmoser Date 2021-04-06 Time 09:10 Rev Time 0.00
Received By hmoser Date 2021-04-06 Time 08:34 Sent To  
Notes
2021-04-06 09:10:44 
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-15 Cont ID  
Sent By ccole Date 2021-11-15 Time 12:04 Rev Time 0.00
Received By ccole Date 2021-11-15 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By ccole Date 2021-04-08 Time 16:46 Rev Time 0.00
Received By ccole Date 2021-04-08 Time 15:44 Sent To  
Notes
2021-04-08 16:47:081ST REVIEW FBC-2020 RES.
 PERMIT- 21030892
 4/8/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: UPDATE THE FBC- 2017 CODE REFERENCE IN
 NOTE #1. THE FBC-2020 7TH EDITION CODES WENT INTO
 EFFECT ON 12/31/2020.
  
 2) P1 NOTES: PLEASE PROVIDE PLUMBING PIPING
 SPECIFICATIONS FOR ABOVE AND UNDERGROUND INSTALLATIONS-
 SECTION P2609.1 FBC RES.
  
 2) P1: THE SAN. RISER SHOWS A NON-COMPLIANT WET VENT IN
 THE COMMON BATHROOM. NOT MORE THAN ONE WET-VENTED
 FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION- SECTION P3108.2.1
 FBC RES.
  
 3) P1: PROVIDE SHOWER PAN DETAILS- SECTIONS P2709.1 &
 P2709.2 FBC RES.
  
 4) P1: PROVIDE WALL AND FLOOR FINISH DETAILS FOR THE
 SHOWER AND BATHTUB- SECTION R307.2 FBC RES.
  
 5) P2: INDICATE THE TYPE OF UNDERGROUND WATER PIPING
 AND HOW IT WILL BE PROTECTED FROM CORROSION- SECTION
 P2603.3 FBC RES.
  
 6) P2: SHOW LOCATIONS OF WATER HAMMER ARRESTORS FOR
 WATER SUPPLY LINES TO THE WASHING MACHINE, DISHWASHER,
 AND ICE MAKER LINE- SECTION P2903.5 FBC RES.
 ALTERNATELY PLEASE PLACE A NOTE ON THE PLAN TO CLARIFY.
  
 7) SUBMIT A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 09:31 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 09:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 12:59 Sent To  
Notes
2021-11-15 13:00:06SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 15:27 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 15:27 Sent To  
Notes
2021-04-15 15:28:05SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By mpeterso Date 2022-07-19 Time 15:31 Rev Time 0.00
Received By mpeterso Date 2022-07-19 Time 09:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-05-02 Cont ID  
Sent By rmcphers Date 2022-05-02 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2022-05-02 Time 09:28 Sent To  
Notes
2022-05-02 09:31:35SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS A200, G100, A100, A201, A101, A301, A302,
 A303, A401, A402, A501, A502, E101, M.1 AND THE SOIL
 REPORT DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER
 -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 13:08 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By rmcphers Date 2021-04-15 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2021-04-15 Time 15:26 Sent To  
Notes
2021-04-15 15:27:38THE STRUCTURAL AND MECHANICAL DRAWINGS = SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-23 Cont ID  
Sent By fmittner Date 2022-03-23 Time 10:58 Rev Time 0.00
Received By fmittner Date 2022-03-23 Time 10:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By fmittner Date 2021-03-30 Time 12:09 Rev Time 0.00
Received By fmittner Date 2021-03-30 Time 12:09 Sent To  
Notes
2021-10-01 09:02:46COMMENTS FROM 1-CAR GARAGE PERMIT 21060942 BY FM ON
 9/10/2021. CT
  
 ZONING - NEED SURVEY/SITE PLAN SHOWING 15' OFF CENTER
 LINE OF ALLEY AND SIDE PROPERTY LINES.
2021-03-30 12:10:15NEED SEPERATE LANDSCAPE PERMIT


Account Summary | Usage Policy | Privacy Policy