Plan Review Details - Permit 21030889
Plan Review Stops For Permit 21030889
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-19 Cont ID  
Sent By rmcdouga Date 2022-12-19 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2022-12-19 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-04-02 Cont ID  
Sent By rmcdouga Date 2021-04-02 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2021-04-02 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-12-20 Cont ID  
Sent By mpeterso Date 2022-12-20 Time 13:33 Rev Time 0.00
Received By mpeterso Date 2022-12-20 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By ppetty Date 2021-06-15 Time 08:50 Rev Time 0.00
Received By ppetty Date 2021-06-15 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-30 Cont ID  
Sent By ppetty Date 2021-03-30 Time 09:23 Rev Time 0.00
Received By ppetty Date 2021-03-30 Time 09:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By lcrespo Date 2021-03-23 Time 09:57 Rev Time 0.00
Received By lcrespo Date 2021-03-23 Time 09:57 Sent To  
Notes
2021-03-23 09:58:13GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-20 Cont ID  
Sent By mpeterso Date 2022-12-20 Time 13:33 Rev Time 0.00
Received By mpeterso Date 2022-12-17 Time 19:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-16 Cont ID  
Sent By rmcdouga Date 2022-12-16 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2022-12-16 Time 07:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-08 Cont ID  
Sent By jgomez Date 2022-12-08 Time 09:42 Rev Time 0.00
Received By jgomez Date 2022-12-01 Time 08:27 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 10:08 Rev Time 0.00
Received By rmcdouga Date 2021-06-09 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2021-03-22 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-12-20 Cont ID  
Sent By rwbrown Date 2022-12-20 Time 05:52 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-05 Cont ID  
Sent By rwbrown Date 2022-12-05 Time 06:29 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 12:39 Rev Time 0.00
Received By lcrespo Date 2021-06-23 Time 12:30 Sent To  
Notes
2021-06-23 12:39:5406/23/21 2 ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. SECOND REQUEST; PLEASE SUBMIT THE POOL PUMP CURVE.
 IDENTIFY THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO
 THE PUMP BEING INSTALLED ON THIS POOL AND SHOW IT IN A
 BAR GRAPH. THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM
 FLOW FROM THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7
 - 2013 SECS. 4.4.9, 4.4.9.1.
  
 3. SECOND REQUEST; PLEASE PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PUMP, FILTER, CHLORINATOR, AND
 GAS HEATER PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. SECOND REQUEST; PLEASE PROVIDE DOCUMENTATION THAT
 THE GAS AND SPA HEATERS SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82 % FOR HEATERS MANUFACTURED ON OR AFTER
 APRIL 16, 2013, WHEN TESTED IN ACCORDANCE WITH ANSI Z
 21.56. POOL HEATERS FIRED BY NATURAL OR LP GAS SHALL
 NOT HAVE CONTINUOUSLY BURNING PILOT LIGHTS PER THE 2017
 FBC-ENERGY ? SEC. R403.10.4.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-23 Cont ID  
Sent By lcrespo Date 2021-03-23 Time 09:44 Rev Time 0.00
Received By lcrespo Date 2021-03-23 Time 09:43 Sent To  
Notes
2021-03-23 09:56:0603/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS
 PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. PLEASE SUBMIT THE POOL PUMP CURVE. IDENTIFY THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL AND SHOW IT IN A BAR GRAPH. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 3. PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PUMP, FILTER, CHLORINATOR, AND GAS HEATER PER THE
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. PLEASE PROVIDE DOCUMENTATION THAT THE GAS AND SPA
 HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82 %
 FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013,
 WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL
 HEATERS FIRED BY NATURAL OR LP GAS SHALL NOT HAVE
 CONTINUOUSLY BURNING PILOT LIGHTS PER THE 2017
 FBC-ENERGY ? SEC. R403.10.4.
  
 5. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-12-19 Cont ID  
Sent By rmcdouga Date 2022-12-19 Time 09:33 Rev Time 0.00
Received By rmcdouga Date 2022-12-19 Time 09:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-12-16 Cont ID  
Sent By rmcdouga Date 2022-12-16 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2022-12-16 Time 14:37 Sent To  
Notes
2022-12-16 14:38:36THE PLANS ARE NOT DIGITALLY SIGNED BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-12-08 Cont ID  
Sent By jgomez Date 2022-12-08 Time 09:35 Rev Time 0.00
Received By jgomez Date 2022-12-08 Time 09:29 Sent To  
Notes
2022-12-08 09:40:321- DRAWINGS SUBMITTED DON'T HAVE THE SIGNATURE OF THE
 ENGINEER OF RECORD. PLANS/DOCUMENTS NEED TO HAVE THE
 ORIGINAL SEAL/SIGNATURE OF THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471 F.S.
 WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
 THIS IS AN ELECTRONIC SUBMITTAL. SUBMIT PLANS/DOCUMENTS
 WITH ENGINEER'S VERIFIABLE DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 10:03 Sent To  
Notes
2021-06-24 10:05:05THE ELECTRONIC SIGNATURES CAN NOT BE VERIFIED.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15
  
 NOTE: DRAWING 4 OF 4 WAS NOT WITH THE OTHER DRAWINGS IN
 THE SIGNATURE FILE. ALSO IF THE DRAWINGS ARE ROTATED OR
 OTHERWISE CHANGED FROMM THE WAY THEY ARE SENT FROM THE
 ENGINEER THE ELECTRONIC SIGNATURE WILL BE COMPROMISED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-02 Cont ID  
Sent By rmcdouga Date 2021-04-02 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2021-04-02 Time 14:23 Sent To  
Notes
2021-04-02 14:24:53ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By rthermid Date 2021-06-22 Time   Rev Time 0.00
Received By rthermid Date 2021-06-22 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By rthermid Date 2021-04-21 Time   Rev Time  
Received By rthermid Date 2021-04-21 Time   Sent To I
Notes
***NONE***