| 2021-03-22 10:54:37 | 03/22/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW |
| | THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. |
| | THE CALCULATION SHOWS THE PIPE, FITTINGS, VALVES, |
| | FILTER, BUT THERE IS NO FRICTION LOSS ASSOCIATED HEATER |
| | AND CHLORINATOR PLEASE ADD THESE ITEMS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 3. PLEASE SUBMIT SPECIFICATION THE HEAT PUMP POOL |
| | HEATERS HAVE A MINIMUM COP OF 4.0 WHEN TESTED IN |
| | ACCORDANCE WITH AHRI 1160, TABLE 2, STANDARD RATING |
| | CONDITIONS - LOW AIR TEMPERATURE. A TEST REPORT FROM AN |
| | INDEPENDENT LABORATORY IS REQUIRED TO VERIFY PROCEDURE |
| | COMPLIANCE PER THE 2017 FBC-ENERGY SEC. R 403.10.5 |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |