Plan Review Details - Permit 21030845
Plan Review Stops For Permit 21030845
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 09:26 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-19 Cont ID  
Sent By shill Date 2021-03-19 Time 10:11 Rev Time 0.00
Received By shill Date 2021-03-19 Time 10:11 Sent To  
Notes
2021-03-19 10:11:49PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By rmcphers Date 2021-05-26 Time 13:54 Rev Time 0.00
Received By rmcphers Date 2021-05-26 Time 13:53 Sent To  
Notes
2021-05-26 14:08:43 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 09:01 Sent To  
Notes
2021-04-13 09:24:52COMMERCIAL BUILDING INTERIOR ALT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE ROOF TOP AC CURB OR STAND MOUNTING
 DETAILS TO COMPLY WITH FBC 1510.10 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10.
 2) PLEASE PROVIDE A STATEMENT FROM THE ARCHITECT OR
 ENGINEER TO ADDRESS THE ADDITIONAL WEIGHT OF THE ADDED
 AC SYSTEM ON THE ROOF - FBC E707.2 ADDITION OR
 REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT.
 WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT
 OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS,
 STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR
 EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 3) PLEASE PROVIDE A ROOF PLAN SHOWING THE LOCATION OF
 THE ADDED MECHANICAL EQUIPMENT AND GUARDS IF REQUIRED
 FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By equinone Date 2021-04-16 Time 13:39 Rev Time 0.00
Received By equinone Date 2021-04-16 Time 13:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-03-22 Time   Rev Time 0.00
Received By cwalker Date 2021-03-22 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-06-07 Time   Rev Time 0.00
Received By aoliver Date 2021-06-03 Time 10:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-01 Cont ID  
Sent By shill Date 2021-06-01 Time 09:59 Rev Time 0.00
Received By shill Date 2021-05-20 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-19 Cont ID  
Sent By medwards Date 2021-04-19 Time 08:05 Rev Time 0.00
Received By medwards Date 2021-03-22 Time 09:29 Sent To  
Notes
2021-03-30 09:30:11TO BLDG AUDIT
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By shill Date 2021-03-23 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2021-03-18 Time 13:56 Sent To  
Notes
2021-03-19 10:16:17ROUTED TO FIRE REVIEW
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 14:00 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By medwards Date 2021-04-19 Time 08:05 Rev Time 0.00
Received By medwards Date 2021-04-15 Time 14:47 Sent To  
Notes
2021-04-19 08:05:371ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030845
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.0: THE NEW WALK-IN REF. SHOWN ON THIS SHEET
 SHALL REQUIRE A SEPARATE SUBMITTAL WITH A PERMIT AND
 REVIEW. PLEASE PROVIDE A STATEMENT ON THE PLANS
 REFLECTING THIS.
  
 2) SHEET M2.0: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE 2020 FBC M SECTION 403.3.1.1
 AND TABLE 403.3.1.1. PLEASE USE THESE TWO SECTIONS TO
 CALCULATE THE REQUIRED OUTDOOR AIR FOR THE USE OF THIS
 SPACE, NOT THE ARCHITECT OCCUPANT COUNT. (EXAMPLE) THE
 FLORIST AREA APPEARS TO BE A SALES AREA. THIS WOULD BE
 FIGURED BY USING THE (RETAIL STORES, SALES FLOORS AND
 SHOWROOM FLOORS).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-16 Cont ID  
Sent By tklarge Date 2021-04-16 Time 13:48 Rev Time 0.00
Received By tklarge Date 2021-04-16 Time 13:24 Sent To  
Notes
2021-04-16 13:49:14ALL PLUMBING FIXTURES AND TOILET ROOMS ARE SHOWN AS
 EXISTING. NO NEW PLUMBING WORK IS SHOWN.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2021-06-01 Cont ID  
Sent By shill Date 2021-06-01 Time 09:59 Rev Time 0.00
Received By shill Date 2021-06-01 Time 09:19 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2021-03-19 Cont ID  
Sent By shill Date 2021-03-19 Time 10:12 Rev Time 0.00
Received By shill Date 2021-03-19 Time 10:12 Sent To  
Notes
2021-03-19 10:15:56NOTICE TO BUILDING OFFICIAL FOR PLAN REVIEW AND
 INSPECTIONS RECEIVED
 AFFIDAVIT RECEIVED, WILL NEED NEW AFFIDAVIT IF PLANS
 CHANGE
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By shill Date 2021-03-18 Time 14:07 Rev Time 0.00
Received By shill Date 2021-03-18 Time 14:07 Sent To  
Notes
2021-03-18 14:18:34SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS553, USE OF PRIVATE PROVIDER IS NOT CLEAR. A PLAN
 REVIEW AFFIDAVIT AND PLANS STAMPED REVIEWED BY PRIVATE
 PROVIDER WERE SUBMITTED, BUT THE NOTICE TO BUILDING
 OFFICIAL IS FOR INSPECTIONS ONLY.
  
 EITHER CONFIRM THAT THIS IS INSPECTIONS ONLY AND
 REQUEST THAT THE PLAN REVIEW AFFIDAVIT BE REMOVED FROM
 THE RECORD, OR SUBMIT A NOTICE TO BUILDING OFFICIAL FOR
 PLAN REVIEW AND INSPECTIONS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-07 Cont ID  
Sent By ccole Date 2021-06-07 Time 12:38 Rev Time 0.00
Received By ccole Date 2021-06-07 Time 12:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-26 Cont ID  
Sent By rmcphers Date 2021-05-26 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2021-05-26 Time 14:09 Sent To  
Notes
2021-05-26 14:10:20INTERIOR RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS ADDED TO PROJECTDOX ON 5/19/2021 NEED TO BE
 SIGNED AND SEALED BY THE DESIGNER. (DRAWING A1.0 AND
 CURB DETAIL 1 AND 2) FBC 107.1
 DRAWINGS ADDED TO PROJECTDOX ON 5/19/2021 = SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-29 Cont ID  
Sent By medwards Date 2021-03-18 Time 13:11 Rev Time 0.00
Received By medwards Date 2021-03-18 Time 12:52 Sent To  
Notes
2021-03-18 13:13:22 
  