| Plan Review Stops For Permit 21030802 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-04-22 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-04-22 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2021-04-22 07:58:11 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107, PLEASE PROVIDE ENGINEER?S SIGNATURE & SEAL | | | ON PLAN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-04-06 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-04-06 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2021-04-06 14:26:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107, PLEASE PROVIDE ENGINEER'S SIGNATURE & SEAL | | | ON PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2021-04-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-04-01 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-01 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2021-04-01 06:50:32 | NON-ILLUMINATED SIGN JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-04-22 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-04-08 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-04-07 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-03-26 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-04-22 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-04-22 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2021-04-22 08:01:38 | SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL | | | SIGNED/SEALED PAPER ORIGINAL TO: | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-04-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-04-06 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-04-06 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2021-04-06 14:18:02 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN OR YOU CAN MAIL AN ORIGINAL | | | SIGNED/SEALED PAPER ORIGINAL TO: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-04-15 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2021-04-15 |
Time |
13:47 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2021-04-15 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2021-04-15 13:44:40 | FASCIA SIGN | | | | | | 1) THIS IS A SECOND FASCIA SIGN FOR THE STOREFRONT | | | WHICH THE ROSEMARY SQUARE TENANT SIGN ONLY PERMIT ON A | | | CASE BY CASE BASIS. SIGNS PERMITTED ON A CASE BY CASE | | | BASIS REQUIRE A WAIVER I APPROVAL LETTER FROM CITYPLACE | | | RETAIL, LLC. | | | | | | 2) THE PROPOSED LOCATION OF THIS FASCIA SIGN IS NOT IN | | | THE STOREFRONT TYPE 2 FASCIA SIGN LOCATION. ALTERNATIVE | | | HORIZONTAL AND VERTICAL PLACEMENTS OF FASCIA SIGNS ARE | | | PERMITTED IF GRANTED A WAIVER I APPROVAL LETTER FROM | | | CITYPLACE RETAIL, LLC. PLEASE NOTE THAT THIS LOCATION | | | REQUIRES A WAIVER FOR BOTH THE HORIZONTAL AND VERTICAL | | | PLACEMENT. | | | | | | 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE THE | | | STUD MOUNTS TO BE SERIES 316 STAINLESS STEEL ANCHOR | | | BOLTS. THE PLANS SHOW ALUMINUM STUDS, WHICH ARE NOT | | | PERMITTED. | | | | | | 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE | | | THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT | | | LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED | | | SIGN AREA. WHILE THE PLANS SHOW SUFFICIENT DIMENSION TO | | | MEET THE REQUIREMENT, IT IS NOT CLEARLY DEMONSTRATED ON | | | THE PLANS. PROVIDE VERIFICATION THAT THE REQUIREMENT IS | | | MET. | | | | | | 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE | | | NON-INTERNALLY ILLUMINATED FASCIA SIGNS CONSISTING OF | | | INDIVIDUAL LETTERS BE AT LEAST ONE-HALF INCH THICK. THE | | | PROPOSED THICKNESS DOES NOT MEET THIS REQUIREMENT. | | | | | | 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE | | | THAT PEG MOUNTED, NON-INTERNALLY ILLUMINATED, | | | INDIVIDUAL LETTERS FOR FASCIA SIGNS BE MOUNTED A | | | MINIMUM OF ONE (1) INCH FROM THE WALL. PROVIDE | | | VERIFICATION THAT THE REQUIREMENT IS MET. | | | | | | PERMITTED AREA: 70 SF | | | PERMIT 21030800 AREA: 14.1 SF | | | PROPOSED AREA: 4 SF | | | TOTAL AREA: 18.1 SF | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2021-04-07 |
Time |
10:23 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2021-04-07 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2021-04-07 10:34:38 | FAILED | | | | | | 1) THIS TENANT LOCATION IS DESIGNATED AS A STOREFRONT | | | TYPE 2, SINGLE HEIGHT TENANT WITH LOWER AND UPPER LEVEL | | | ARCADE, IN THE ROSEMARY SQUARE SIGN CRITERIA. THE | | | STOREFRONT TYPE 2 ONLY PERMITS FASCIA IDENTITY SIGNS ON | | | THE EXTERIOR FACADE OF THE BUILDING (SUBJECT TO A | | | WAIVER I APPROVAL BY CITYPLACE RETAIL, LLC), NOT ON THE | | | FACADE UNDER THE ARCADE. THE PROPOSED SIGN LOCATION IS | | | NOT PERMITTED BY THE ROSEMARY SQUARE SIGN CRITERIA AND | | | THERE IS NO WAIVER PROCESS INCLUDED TO PERMIT THIS SIGN | | | LOCATION. | | | | | | 2) STAFF HAS NOT REVIEWED THE SIGN DESIGN AS THIS IS | | | NOT A PERMITTED SIGN. | | | | | | 3) THE ONLY TYPES OF SIGNS PERMITTED BY THE ROSEMARY | | | SQUARE SIGN CRITERIA WITHIN THE ARCADE ARE SIGN TYPE 2A | | | OR 2B BLADE SIGN (WALL OR CEILING), SIGN TYPE 3 WINDOW | | | GRAPHICS AND FLOOR ENTRY SIGNS. NOTE: BASED ON THE | | | ELEVATION DRAWING SUBMITTED WITH THE PERMIT, IT APPEARS | | | THAT A GRAPHIC OF THE SAME SIZE AS THE NOT PERMITTED | | | WALL SIGN COULD BE APPLIED TO THE WINDOW ADJACENT TO | | | THE DOOR. ALL OF THE PERMITTED SIGN TYPES REQUIRE SIGN | | | PERMIT REVIEW AND APPROVAL. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] | | | |
|
|