Plan Review Details - Permit 21030797
Plan Review Stops For Permit 21030797
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-05-10 Cont ID  
Sent By rmcdouga Date 2021-05-10 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2021-05-10 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By rmcdouga Date 2021-04-22 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2021-04-22 Time 09:08 Sent To  
Notes
2021-04-22 09:29:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A DIMENSIONED DRAWING OF THE STOREFRONT LIKE
 THE ONE THAT WAS CROSSED OUT ON THE CONTRACT. FBC
 AMENDMENTS107.2.1
  
 2) SPECIFY THE REQUIRED WIND LOAD PRESSURES FOR THIS
 STOREFRONT DOOR OPENING IN 170 MPH VULT EXPOSURE C. FBC
 BUILDING SECTION 1609
  
 3) CIRCLE OR HI-LIGHT THE ITEMS LISTED IN THE PRODUCT
 APPROVAL (INCLUDING THE DESIGN PRESSURES) THAT APPLY TO
 THIS PROJECT. FBC AMENDMENTS107.2.1
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-10 Cont ID  
Sent By rmcdouga Date 2021-05-10 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2021-05-05 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcdouga Date 2021-04-22 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2021-04-09 Time 13:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-05-10 Cont ID  
Sent By rmcdouga Date 2021-05-10 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2021-05-10 Time 11:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By rmcdouga Date 2021-04-22 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2021-04-22 Time 09:08 Sent To  
Notes
2021-04-22 09:43:14WILL BE REVISITED WHEN WIND LOAD PRESSURES ARE
 SUBMITTED. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT?S OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT?S OR
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15, FS 481 & 61G1