| Plan Review Stops For Permit 21030764 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-19 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-19 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-07 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-07 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2021-04-07 12:13:33 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-19 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-19 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-07 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-07 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2021-04-07 12:14:32 | OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROOM LABELED 711 CAFE - PLEASE SHOW THE COUNTER | | | HEIGHTS, REACH RANGES AND FLOOR SPACE REQUIREMENTS TO | | | COMPLY WITH FBC ACCESSIBILITY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-07 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-07 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-04-14 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-04-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-04-13 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2021-04-14 10:14:52 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LIEUTENANT | | | BRIAN DOLAN, BUREAU OF FIRE PREVENTION, WEST PALM BEACH | | | FIRE RESCUE: | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-06-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-01 |
Time |
06:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-27 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-21 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-19 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-04-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-22 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-23 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-07 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-07 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-06-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-01 |
Time |
06:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-01 |
Time |
06:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2021-05-25 07:08:22 | 3RD REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030764 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON FBC | | | M 403.3.1.1 AND TABLE 403.3.1.1 NOT THE ARCHITECTURAL | | | OCCUPANT COUNT. | | | OFFICE- 2798/1000= 2.798 X5 X 5 = 69.95 + 2798 X .06 = | | | 167.88; 69.95 + 167.88 = 237.83 (238 CFM) | | | HUDDLE ROOMS- 265/1000 = 0.265 X50 X 5 = 66.25 + 265 X | | | .06 = 15.9; 66.25 + 15.9 = 82.15 (82 CFM) 238 + 82 = | | | 320 CFM REQUIRED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-07 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-07 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2021-05-07 06:36:49 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030764 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR BOTH THE | | | OFFICE AREAS AND THE CONFERENCE ROOM. PLEASE SEE | | | SECTION 403.3.1.1 ( CANNOT USE ARCHITECTURAL OCCUPANT | | | LOAD FOR THIS CALCULATION). PLEASE SEE TABLE 403.3.1.1 | | | FOR OFFICE AND CONFERENCE ROOMS TO COMPUTE THE | | | CALCULATIONS FOR THE OUTDOOR AIR. IF YOU HAVE ANY | | | QUESTIONS PLEASE DON?T HESITATE TO CALL ME. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-04-07 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-04-07 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2021-04-07 15:00:03 | PLAN DENIED | | | REFER TO TABLE 403.3.1.1 MINIMUM VENTILATION RATES 2020 | | | FBC (M) | | | PROVIDE FRESH AIR CALCULATIONS. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-05-07 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-05-07 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2021-05-07 07:11:22 | NO PLUMBING REVIEW OR PERMIT REQUIRED | | | CCOLE- 5/7/21 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-07 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-07 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2021-04-07 18:07:01 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21030764 | | | 4/7/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) NO PLUMBING PLANS HAVE BEEN SUBMITTED HOWEVER THE | | | CONSTRUCTION PLAN SHOWS A NEW CAFE. PLEASE CLARIFY IF A | | | NEW SINK AND ANY OTHER PLUMBING FIXTURES WILL BE | | | INSTALLED. PROVIDE PLUMBING PLANS AND RISER DRAWINGS IF | | | APPLICABLE- SECTIONS 107.2.1 & 107.3.5.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-06-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-01 |
Time |
06:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-01 |
Time |
06:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-07 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-07 |
Time |
06:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-07 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-07 |
Time |
12:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-04-21 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-04-21 |
Time |
|
Sent To |
I |
|
| Notes |
|
|