Plan Review Details - Permit 21030748
Plan Review Stops For Permit 21030748
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 07:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By jwitmer Date 2021-04-06 Time 12:46 Rev Time 0.00
Received By jwitmer Date 2021-04-06 Time 11:44 Sent To  
Notes
2021-04-06 12:45:30TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-06 Cont ID  
Sent By jwitmer Date 2021-04-06 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2021-04-06 Time 11:44 Sent To  
Notes
2021-04-06 12:44:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030748
 ADD: 1700 PALM BEACH LAKES BLVD. SUITE: 130
 CONT: NEW LIVING CONSTRUCTION, INC.
 TEL: 305-761-4444
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 06TH/ 2021
 ACTION: DENIED
  
 1) SHEET GENERAL NOTES -ACCESSIBILITY NOTE 21 FOR GRAB
 BARS INDICATES SEE 3/A.04 FOR MOUNTING HEIGHTS.
 SHEET A.04 HAS NO DETAILS FOR GRAB BARS ADJACENT TO A
 WATER CLOSET.
 2020 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE SIDE
 WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2) THE LIFE SAFETY FLOOR PLAN SHOWS TO CHANGING ROOMS
 114 & 115 BUT THERE IS NOT AN ACCESSIBLE CHANGING ROOM/
 DRESSING ROOM AS REQUIRED BY THE 2020 FBC-ACCESSIBILITY
 CODE SECTION 222. 1 SEE EXCEPTION FOR A SINGLE UNISEX
 CHANGING ROOM. SECTION 803.1-803.5 WILL PROVIDE THE
 REQUIREMENTS FOR WITHIN THE CHANGING/ DRESSING ROOM.
  
 3) SHEET AO.16 THE FINISH SCHEDULE FOR THE TOILET ROOMS
 102 & 103 BOTH SHOW A PAINT FINISH FOR ALL 4 RESTROOM
 WALLS. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN RESTROOMS & SERVICE SINK
 AREAS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
  
 A) 2020 FBC-B1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET
 OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE
 A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF
 NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 B) 2020 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
 4) THE LIFE SAFETY PLAN SHOW AN AREA CALLED A CAF? BUT
 I DID NOT SEE A ELEVATION VIEW OF THE CABINETRY AND
 SINK SHOWING COMPLIANCE WITH THE 2020 ACCESSIBILITY
 CODE SECTIONS:
  
 4A) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4B) 606 LAVATORIES AND SINKS> 2020 FBC-ACCESSIBILITY
 CODE SECTION 606.3 HEIGHT. LAVATORIES AND SINKS SHALL
 BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4C) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN.
  
 4D) MICROWAVE IN COMPLIANCE WITH:
 4D)(1) 308 REACH RANGES 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 4D)(2) 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 (22.2 N) MAXIMUM.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-01 Cont ID  
Sent By equinone Date 2021-04-01 Time 15:56 Rev Time 0.00
Received By equinone Date 2021-04-01 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-07 Cont ID  
Sent By bdolan Date 2021-04-07 Time   Rev Time 0.00
Received By bdolan Date 2021-04-07 Time 16:00 Sent To  
Notes
2021-04-07 16:00:47THIS PLAN WAS REVIEWED AND PASSED WITH COMMENTS,
 SUBMITTED BY LIEUTENANT BRIAN DOLAN, BUREAU OF FIRE
 PREVENTION, WEST PALM BEACH FIRE RESCUE:
  
 1. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3. THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-28 Cont ID  
Sent By hmoser Date 2021-04-28 Time 09:49 Rev Time 0.00
Received By hmoser Date 2021-04-23 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-14 Cont ID  
Sent By hmoser Date 2021-04-14 Time 15:15 Rev Time 0.00
Received By hmoser Date 2021-03-26 Time 20:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-28 Cont ID  
Sent By hmoser Date 2021-04-28 Time 09:48 Rev Time 0.00
Received By hmoser Date 2021-04-28 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-14 Cont ID  
Sent By hmoser Date 2021-04-14 Time 15:12 Rev Time 0.00
Received By hmoser Date 2021-04-07 Time 15:11 Sent To  
Notes
2021-04-14 15:12:46PLAN DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PRE
 TABLE 403.3.1.1 MINIMUM VENTILATION RATES
 2020FBC (M)
 2) HOW ARE YOU GOING TO CONTROL THE TEMPERATURE
 IN CORRIDOR # 110
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-28 Cont ID  
Sent By hmoser Date 2021-04-28 Time 09:50 Rev Time 0.00
Received By hmoser Date 2021-04-28 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-14 Cont ID  
Sent By hmoser Date 2021-04-14 Time 15:15 Rev Time 0.00
Received By hmoser Date 2021-04-14 Time 15:15 Sent To  
Notes
***NONE***