| Plan Review Stops For Permit 21030687 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-03-17 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-03-17 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-03-17 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2021-03-17 09:00:32 | WORK TO BE DONE ON SUITE 202, CREATED IN THE SYSTEM |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-03-15 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-03-15 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2021-03-15 12:22:39 | WE HAVE A FEW SUITES ASSOCIATED WITH THIS BUILDINGS, IS | | | THE WORK GOING TO BE DONE INA ONE OF THE SUITES, PLEASE | | | EMAIL [email protected] |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-04-13 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-04-13 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-03-21 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-03-21 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2021-03-21 15:13:27 | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-04-13 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-04-13 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-03-21 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-03-21 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2021-03-21 15:12:34 | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SUN. MARCH 21ST/ 2021 | | | ACTION: DENIED | | | | | | 1) NEITHER A1.02 OR A1.03 PROVIDE ANY DETAIL OF THE | | | LUNCH AREA. IF THERE IS ANY SINKS AND OR COUNTER SPACE | | | AND OR USE OF MICRO-WAVES. THE CURRENT PLAN CAN NOT | | | DETERMINE IF THERE ARE CODE VIOLATIONS OF THE 2020 | | | FBC-ACCESSIBILITY CODE. | | | | | | FLORIDA ACCESSIBILITY CODE SECTION: DISPROPORTIONATE | | | COST 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET | | | DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE | | | DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW | | | THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE | | | FUNDS ($88,000.00 X 0.20= $17,600.00 DOLLARS IN | | | ACCESSIBLE UPGRADES) LISTED FOR EACH ELEMENT WHERE THE | | | FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN | | | SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2020 | | | ACCESSIBILITY CODE. | | | | | | 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO | | | PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED | | | AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL | | | ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE | | | ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY | | | BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN | | | ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST | | | ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN | | | ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST | | | ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS | | | INSTALLING GRAB BARS, ENLARGING TOILET STALLS, | | | INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET | | | CONTROLS; (III) COST ASSOCIATED WITH PROVIDING | | | ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE | | | TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION | | | DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV) | | | COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING | | | FOUNTAIN. | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 | | | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ | | | RETIRED. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-03-29 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-03-29 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-03-29 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-04-13 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2021-04-13 09:58:42 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | | | | 3) THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER | | | SYSTEMS SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-03-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-03-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-03-17 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2021-03-17 14:55:46 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | | | | | | 3) THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER | | | SYSTEMS SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE DEPARTMENT | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-21 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-12 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-30 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-16 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-21 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-21 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-30 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-30 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2021-03-30 14:27:01 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030687 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE | | | OF SPACE ACCORDING TO TABLE 403.3.1.1 I.E. OFFICE | | | SPACE, CONFERENCE ROOM, BREAKROOM. PLEASE BREAK THE | | | OUTDOOR AIR DOWN TO EACH MECHANICAL SYSTEM ACCORDING TO | | | THE SPACE BEING CONDITIONED. FBC M 403.3.1.1 | | | | | | 2) THE AIR SYSTEM SIZING SUMMARY IS FOR AHU-1 ONLY | | | PLEASE SUBMIT AN EQUIPMENT SIZING CALCULATION FOR EACH | | | MECHANICAL SYSTEM IN THIS TENANT SPACE. FBC EC C403.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-21 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-21 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-30 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-30 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2021-03-29 10:01:44 | DIGITAL CERTFICATE (PEDRO PABLO COTO P.E.) FOR | | | ELECTRICAL AND MECHANICAL DRAWINGS EXPIRED ON 3/17/2021 |
|
|