| 2021-03-17 11:22:59 | RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21030642 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING |
| | WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING |
| | UNDERLAYMENT SEC. 1507.1.1.1 FBC-BUILDING. |
| | |
| | 2- CONTRACTOR NEEDS TO UPLOAD TO PROJECTDOX THE |
| | COMPLETE FLORIDA PRODUCT APPROVAL FOR SHINGLES AND |
| | ROOFING UNDERLAYMENT. ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE WAS UPLOADED. NEED TO UPLOAD THE |
| | INSTALLATION INSTRUCTIONS ALSO. |
| | FAC 61G20.3.001. |
| | |
| | 3- NEED TO SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING |
| | AS REQUIRED BY THE CITY POLICY FOR ALL ROOFING PERMITS. |
| | NOTE: THIS IS A THREE STORY BUILDING. TYPICALLY, |
| | SHINGLES MAY NOT BE ABLE TO BE INSTALLED WHERE THE MEAN |
| | ROOF HEIGHT EXCEEDS 33FT, EXCEPT WHEN THE PRODUCT |
| | APPROVAL ALLOWS IT. SEE RAS115. |
| | |
| | 4- NEED TO SPECIFY THE ROOF PITCH AS REQUIRED BY THE |
| | CITY POLICY FOR ALL ROOFING PERMITS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |