| 2021-04-19 09:30:34 | 2ND REVIEW FBC-2020 RES. |
| | PERMIT- 21030608 |
| | 4/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | NFPA- 58 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED RISER DRAWINGS FOR THE FROM THE TWO GAS |
| | CONTRACTORS ON THE PROJECT DO NOT MATCH. THE RISER BY |
| | THE GAS PIPING JERIMIAH CAY PLUMBING SHOWS A TOTAL LOAD |
| | OF 1,363,000 BTUS, HOWEVER THE RISER BY THE TANK |
| | INSTALLATION CONTRACTOR ROBERT PETTET SHOWS A TOTAL |
| | LOAD OF 524 BTUS. BOTH OF THESE RISERS ARE INCORRECT |
| | AND DO NOT MATCH THE APPROVED RISER DRAWING UNDER THE |
| | MASTER GAS PERMIT 20111027 WHICH SHOWS A FUTURE |
| | GENERATOR LOAD OF 730,000 BTUS. |
| | |
| | 2) JERIMIAH CAY RISER: |
| | A) SHOW THE DELIVERY PRESSURE AT THE TANK AND FIRST |
| | STAGE REGULATOR- SECTION 6.10.1.1 NFPA 58. |
| | B) SHOW THE LOCATION OF THE SECOND-STAGE REGULATOR THAT |
| | IS DELIVERING THE 2 PSI PRESSURE TO THE BRANCH |
| | SUPPLYING THE TWO TANKLESS WATER HEATERS AND GAS DRYER- |
| | SECTION 6.10.2.1 NFPA 58. |
| | C) THE TOTAL 1,363,000 BTU LOAD LISTED ON THE DRAWING |
| | DOES NOT MATCH THE RISER WHICH SHOWS A TOTAL LOAD |
| | 618,000 BTUS. PLEASE NOTE THE APPROVED RISER UNDER |
| | PERMIT 20111027 SHOWS A BRANCH LINE TO A 730,000 BTU |
| | FUTURE GENERATOR. THE REVISED RISER DOES NOT INCLUDE |
| | THE FUTURE GENERATOR- SECTION 6.11.2 NFPA 58. |
| | D) LIST THE MAKES AND MODELS OF THE REGULATORS ON THE |
| | DRAWING AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTION 6.10.1.4 NFPA 58. |
| | E) THE 1/2 IN. SCHEDULE 40 METALLIC BRANCH PIPE FROM |
| | THE LOW PRESSURE REGULATOR TO THE COOKTOP OUTLET SHALL |
| | BE SIZED AT 3/4 IN. THE BRANCH PIPE TO THE FIREPLACE |
| | CAN REMAIN AT 1/2 IN.- TABLE 402.4(28) FBC FG. |
| | F) PLEASE PROVIDE THE EHD OF THE CSST PIPES SHOWN ON |
| | ALL BRANCHES OF THE RISERS- TABLES 402.4(32) (33) FBC |
| | FG. |
| | G) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS SIGNATURE ON IT- SECTION 107.2.1 WPB, |
| | AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | 3) ROBERT PETTET RISER: |
| | A) SHOW THE BRANCH LINE TO THE GENERATOR- SECTION |
| | 6.11.2 NFPA 58. |
| | B) CORRECT THE INDIVIDUAL AND TOTAL BTU LOADS TO MATCH |
| | THE LOADS SHOWN ON THE REVISED RISER BY JERIMIAH CAY- |
| | SECTION 107.2.1 WPB. |
| | C) SHOW THE DELIVERY PRESSURES AT FIRST STAGE AND |
| | SECOND STAGE REGULATORS- SECTIONS 6.10.1.1 & 6.10.2.1 |
| | NFPA 58. |
| | D) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS SIGNATURE ON IT- SECTION 107.2.1 WPB, |
| | AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | 4) PROVIDE A SURVEY DRAWING SHOWING THE LOCATION OF THE |
| | NEW LP TANK WITH CLEARANCE DISTANCES FROM THE BUILDING |
| | AND PROPERTY LINES SHOWN- TABLE 6.4.1.1 NFPA 58. |
| | A) REFER TO SECTION 6.10.1.7 NFPA 58 AND INDICATE THE |
| | REQUIRED CLEARANCES FOR REGULATOR PRESSURE RELIEF VENT |
| | DISCHARGES TO OPERABLE OPENINGS INTO THE BUILDING, |
| | MECHANICAL AIR INTAKES, AND ANY SOURCE OF IGNITION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |