| 2021-04-05 14:57:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21030566 2300 PALM BEACH LAKES BLVD # 312 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | A. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3 PROVIDE |
| | PLANS SHOWING ANY OF THE FOLLOWING AS APPLICABLE: |
| | |
| | 1. MINIMUM PLUMBING FACILITIES |
| | A) PROVIDE PLUMBING FIXTURES AND A FIXTURE SCHEDULE, |
| | COMPLY WITH THE OCCUPANCY REQUIREMENTS OF FBC PL 403.1, |
| | TABLE 403.1, 404.1 AND 410. |
| | |
| | 2. FIXTURE REQUIREMENTS |
| | A) COMPLY WITH FBC PL CHAPTER 4 |
| | B) SHOW COMPLIANCE WITH FBC ACC CHAPTERS 3 AND 6. |
| | PROVIDE PLAN AND ELEVATION DETAILS FOR REQUIRED |
| | ACCESSIBLE PLUMBING FIXTURES AND ACCESSORIES. |
| | |
| | 3. WATER SUPPLY PIPING |
| | A) PROVIDE PLAN VIEW AND RISER DIAGRAM OF HOT AND COLD |
| | WATER; SHOW SIZING, VALVES, REQUIRED BACKFLOW |
| | PREVENTERS, WATER HAMMER ARRESTORS AND OTHER PLUMBING |
| | APPURTENANCES. INDICATE FIXTURES AND EQUIPMENT BEING |
| | SERVICED OR INCORPORATED INTO THE SYSTEM (IE. WATER |
| | HEATER, RECIRC PUMP, TRAP PRIMERS). |
| | B) SEE FBC PL E607.5 REGARDING INSULATION OF HOT WATER |
| | PIPING. COMPLY AS IS APPLICABLE. |
| | C) PROVIDE TABLES USED FOR CALCULATIONS FOR SIZING; SEE |
| | TO FBC PL CHAPTER 6 AND APPENDIX E. |
| | |
| | 4. SANITARY DRAINAGE |
| | A) PROVIDE PLAN VIEW AND RISER DIAGRAM OF SANITARY |
| | DRAINS, WASTE AND VENTS; COMPLY WITH FBC PL CHAPTERS 7, |
| | 8, 9 AND 10. INDICATE FIXTURES, ANY FLOOR DRAINS AND |
| | EQUIPMENT BEING SERVICED. SHOW SIZING. PROVIDE TRAP |
| | PRIMERS FOR FLOOR DRAINS AND PROVIDE DETAIL. |
| | |
| | 5. WATER HEATERS |
| | A) SHOW WATER HEATER LOCATION |
| | B) PROVIDE SCHEDULE WITH MANUFACTURER, MODEL NUMBER, |
| | SIZE/CAPACITY, ELECTRICAL CHARACTERISTICS OR FUEL |
| | GAS/BTUS |
| | C) PROVIDE DETAIL WITH MANUFACTURER, MODEL NUMBER, |
| | SIZE/CAPACITY, ELECTRICAL CHARACTERISTICS OR FUEL |
| | GAS/BTUS, PIPING INCLUDING CW, HW, VALVES (INCLUDING |
| | VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) , |
| | THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P |
| | DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN |
| | AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1; |
| | COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, |
| | 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | |
| | 6. VENTS |
| | A) SEE SANITARY DRAINAGE |
| | |
| | 7. ROOF DRAINAGE |
| | A) IF APPLICABLE, COMPLY WITH FBC PL CHAPTER 11. |
| | |
| | 8. BACKFLOW PREVENTION |
| | A) PROVIDE SCHEDULE AND SPECIFICATIONS |
| | |
| | 9. IRRIGATION |
| | A) AS APPLICABLE |
| | |
| | 10. LOCATION OF WATER SUPPLY LINE |
| | A) SHOW ON PLANS |
| | |
| | 11. GREASE TRAPS |
| | A) IF APPLICABLE COMPLY WITH FBC PL CHAPTER 10. PROVIDE |
| | CALCULATIONS, TYPE AND DETAIL |
| | |
| | 12. ENVIRONMENTAL REQUIREMENTS |
| | A) AS REQUIRED BY BUILDING DEPARTMENT |
| | |
| | 13. PLUMBING RISER (SANITARY AND WATER) |
| | A) SEE COMMENTS IN WATER SUPPLY PIPING AND SANITARY |
| | DRAINAGE |
| | |
| | 14. DESIGN FLOOD ELEVATION |
| | A) AS REQUIRED BY BUILDING DEPARTMENT |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS |
| | FROM THE PRIOR REVIEW. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21030566 2300 PALM BEACH LAKES BLVD # 312 |