| 2021-06-04 10:14:28 | 06/04/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 3. THE ISOMETRIC DRAWING CLEARLY SHOWS THE LENGTH OF |
| | ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. SECS. |
| | G2413.4.1, G2413.4.2. |
| | |
| | 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. FOR FUTURE GENERATOR, PLEASE PROVIDE AN |
| | ESTIMATED SIZE AND SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | 7. PLEASE INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) |
| | ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| | |
| | 8. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 9. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE INSPECTION TIME PER THE 2020 FBC |
| | RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 10. PLEASE PROVIDE THE SIZING TABLE USED IN THE DESIGN |
| | FOR THE GAS SYSTEM OR PLACE A NOTE ON SETS OF PLANS |
| | LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| | STANDARD USED IN THE DESIGN OF THIS SYSTEM PER THE 2020 |
| | FBC RES. SEC. G2413.3. |
| | |
| | 11. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| | BUILDING PERMITS VALUATIONS. |
| | |
| | 12. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |