Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 15:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 15:02 Sent To  
Notes
2021-03-11 15:00:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REVISE NOTE ON SURVEY. THE GENERATOR EXHAUST IS
 REQUIRED TO BE 10 FEET FROM OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SUBMIT GENERATOR SPECIFICATIONS AND CUT SHEETS. FBC
 AMENDMENTS 107.2.1
  
 3) SUBMIT GENERATOR PAD AND ANCHORING DETAILS, FBC
 AMENDMENTS 107.2.1
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-18 Cont ID  
Sent By jleahy Date 2021-06-18 Time 16:11 Rev Time 0.00
Received By jleahy Date 2021-06-18 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By cthroop Date 2021-03-16 Time 07:58 Rev Time 0.00
Received By cthroop Date 2021-03-15 Time 15:55 Sent To  
Notes
2021-03-16 08:03:04PLAN REVIEW GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ? 200 AMP ATS S.E. RATED M.C.B.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
 2) PROVIDE CURRENT COPY OF GENERATOR MANUFACURERS
 SPECIFICATIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-06-30 Cont ID  
Sent By ccole Date 2021-06-30 Time 17:03 Rev Time 0.00
Received By ccole Date 2021-06-30 Time 17:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By ccole Date 2021-06-24 Time 12:49 Rev Time 0.00
Received By ccole Date 2021-06-24 Time 11:05 Sent To  
Notes
2021-06-24 12:49:522ND REVIEW FBC-2020 RES. GAS
 PERMIT- 21030362
 6/23/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NEW PLAN SUBMITTED.
  
 1) GAS RISER: PROVIDE A COMPLETE RISER DRAWING THAT
 INCLUDES THE NEW AND EXISTING GAS PIPING AND APPLIANCES
 AT THE RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES.
 REFER TO FBC RES. CHAPTER 24 FUEL GAS AND PROVIDE:
 A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 B) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
  
 2) GAS RISER: PLACE A NOTE TO INDICATE THE PIPING ON
 THE ROOF WILL BE ELEVATED NOT LESS THAN 3-1/2 INCHES
 ABOVE THE ROOF SURFACE- SECTION G2415.9 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 11:58 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-28 Cont ID  
Sent By jleahy Date 2021-06-28 Time 11:11 Rev Time 0.00
Received By jleahy Date 2021-06-15 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-14 Cont ID  
Sent By cthroop Date 2021-04-14 Time 09:08 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By ccole Date 2021-06-24 Time 12:47 Rev Time 0.00
Received By ccole Date 2021-06-24 Time 11:05 Sent To  
Notes
2021-06-24 12:47:51 
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-05 Cont ID  
Sent By ccole Date 2021-04-05 Time 11:58 Rev Time 0.00
Received By ccole Date 2021-04-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcdouga Date 2021-06-24 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2021-06-24 Time 15:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-11 Cont ID  
Sent By rmcdouga Date 2021-03-11 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 15:00 Sent To  
Notes
2021-03-11 15:02:07SIGNATURES WILL BE VERIFIED WHEN REQUESTED DOCUMENTS
 ARE SUBMITTED.

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By awooten Date 2021-06-28 Time   Rev Time 0.00
Received By awooten Date 2021-06-28 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-13 Cont ID  
Sent By awooten Date 2021-04-13 Time   Rev Time  
Received By awooten Date 2021-04-13 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved