| 2021-05-10 12:06:22 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROPERTY APPEARS TO HAVE TWO HABITABLE STRUCTURES. |
| | IDENTIFY BUILDING THAT THE WINDOWS WILL BE INSTALLED |
| | IN. IF BOTH BUILDINGS ARE TO RECIEVE WINDOWS, A SECOND |
| | PERMIT WILL BE REQUIRED. |
| | UPDATE ON 5/10/21. SPOKE WITH OWNER, SAYS THE SECOND |
| | STRUCTURE IS NOT ON MERCER AVE. SURVEY INDICATES IT IS. |
| | PROVIDED OWNER WITH CAROLIN PUELL'S PHONE NUMBER TO |
| | WORK ON ADDRESSING. |
| | |
| | 2. PROVIDE ROUGH OPENING DEMENSIONS AND DESIGN WIND |
| | PRESSURES OF EACH OPENING. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | NOTE: YOU MAY PROVIDE A SCHEDULE OF OPENINGS OR PLACE |
| | THE DESIGN PRESSURES NEXT TO EACH OPENING ON YOUR PLAN. |
| | |
| | 3. PROVIDE A SITE PLAN, FLOOR PLAN OR BUILDING SKETCH. |
| | IDENTIFY LOCATION OF PROPOSED WINDOWS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |