Plan Review Details - Permit 21030338
Plan Review Stops For Permit 21030338
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-05-28 Cont ID  
Sent By cthroop Date 2021-05-28 Time 16:08 Rev Time 0.00
Received By cthroop Date 2021-05-28 Time 16:08 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-05-19 Cont ID  
Sent By equinone Date 2021-05-19 Time 08:31 Rev Time 0.00
Received By equinone Date 2021-05-19 Time 08:31 Sent To  
Notes
2021-05-19 08:32:05TO THE BUILDING CONTRACTOR:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-04 Cont ID  
Sent By jwitmer Date 2021-04-04 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2021-04-04 Time 11:12 Sent To  
Notes
2021-04-04 11:42:20TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-04-04 Cont ID  
Sent By jwitmer Date 2021-04-04 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2021-04-04 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By equinone Date 2021-05-18 Time 09:28 Rev Time 0.00
Received By equinone Date 2021-05-18 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By equinone Date 2021-04-08 Time 11:59 Rev Time 0.00
Received By equinone Date 2021-04-08 Time 11:59 Sent To  
Notes
2021-04-08 12:00:12CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) NOTE INDICATING AFCI PROTECTION DOES NOT COVER ALL
 NEC REQUIREMENTS: "ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED." PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
  
 2) ENERGY CODE RESIDENTIAL R404.1REQUIRES THAT "NOT
 LESS THAN 90 PERCENT OF THE LAMPS IN PERMANENTRLY
 INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY OF AT LEAST
 45 LUMENS-PER-WATT OR
 SHALL UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAT
 65 LUMENTS-PER-WATT. A NOTE WILL SUFFICE.
  
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. THE RESUBMITTAL FORM CAN BE FOUND AT
 THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
  
 PHONE: 561-805-6746.
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-17 Cont ID  
Sent By pleduc Date 2021-03-17 Time   Rev Time 0.00
Received By pleduc Date 2021-03-17 Time 13:11 Sent To  
Notes
2021-03-17 13:13:24FIRE PROVISO:
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-28 Cont ID  
Sent By cthroop Date 2021-05-28 Time 16:08 Rev Time 0.00
Received By cthroop Date 2021-05-20 Time 07:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-19 Cont ID  
Sent By equinone Date 2021-05-19 Time 08:32 Rev Time 0.00
Received By equinone Date 2021-04-27 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By jesmith Date 2021-04-15 Time 14:54 Rev Time 0.00
Received By jesmith Date 2021-04-15 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By jesmith Date 2021-05-27 Time 12:44 Rev Time 0.00
Received By jesmith Date 2021-05-27 Time 12:37 Sent To  
Notes
2021-05-27 12:44:2721030338 529 S FLAGLER DR # 31E
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By jesmith Date 2021-05-13 Time 16:47 Rev Time 0.00
Received By jesmith Date 2021-05-13 Time 16:09 Sent To  
Notes
2021-05-13 16:47:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030338 529 S FLAGLER DR # 31E
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1) SECOND REQUEST: PER WPB FBC 107.2.1, INDICATE ON THE
 PLANS THE NUMBER OF SHOWER CONTROL VALVES AND HEADS ON
 EXISTING CONDITIONS AND ON PROPOSED CONDITIONS. TO BE
 CLEAR, SPECIFICALLY NOTE THE ACTUAL QUANTITY OF VALVES
 AND HEADS.
  
 2) SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A
 DETAIL IN SCHEMATIC OF TEMPERATURE LIMITING DEVICE
 SHOWING HOT AND COLD WATER PIPING FROM WALL TO AND FROM
 DEVICE, VALVING AND CONNECTIONS TO TUB VALVE.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By jesmith Date 2021-04-15 Time 14:54 Rev Time 0.00
Received By jesmith Date 2021-04-13 Time 16:39 Sent To  
Notes
2021-04-15 14:21:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030338 529 S FLAGLER DR # 31E
  
 1ST REVIEW
 PLUMBING COMMENTS:
  
 I. PER WPB FBC 105.1,A PLUMBING SUB PERMIT IS REQUIRED
 AND SHALL BE APPLIED FOR BY A LICENSED PLUMBING
 CONTRACTOR.
  
 II. PER WPB FBC 107.2.1 AND 107.3.5.1.3, A PLUMBING
 PLAN IS REQUIRED SHOWING EXISTING SIZED SANITARY SOIL,
 WASTE AND VENT RISERS AND HORIZONTAL BRANCHES. CHASES
 AND PARTITIONS SHALL NOT BE BLOCKED IN SOLID SO THAT
 THE RISERS CAN BE EASILY SEEN ON THE PLAN.
  
 III. ITEMIZED COMMENTS
  
 1.MASTER BATH
 . A.SHOWER
 . 1) DRAIN LOCATION APPEARS TO BE RELOCATED; PER WPB
 FBC 107.2.1, CLARIFY. IF NOT TO BE RELOCATED, STATE AS
 MUCH ON THE PLANS AND IF RELOCATED PROVIDE DETAIL OF
 NEW FLOOR PENETRATION AND PROVIDE UL RATED FIRE
 ASSEMBLY COMPLYING WITH FBC CHAPTER 7. IF DRAIN IS
 RELOCATED FROM EXISTING CONDITION INDICATE TYPE OF
 MATERIAL (I.E. CAST IRON, PVC) OF SHOWER DRAIN PIPE
 PENETRATING THROUGH THE FLOOR AND THE TRAP AND
 HORIZONTAL FIXTURE DRAIN BELOW. PROVIDE ASSEMBLY HAVING
 A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE
 USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS
 REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC
 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE
 REMEDIATED.
 . 2) SHOWER CURB DETAIL ON SHEET 01; PROPOSED
 CONDITIONS. THE DETAIL SHOWER PAN AND CURB DETAIL SHALL
 PER WPB FBC 107.2.1, SHOW COMPLIANCE WITH FBC PL
 SECTION 421 INCLUDING THE REQUIRED 2% PITCH REQUIRED
 FOR THE MEMBRANE, TYPE OF LINER MATERIAL, WALL SECTION
 SHOWING BACKER FOR MEMBRANE AND HEIGHT OF LINER AT WALL
 ABOVE TOP OF FINISHED CURB, DRAIN BODY WITH STRAINER
 AND CLAMPING RING.
 . 3) IF SHOWER DRAIN IS RELOCATED FROM EXISTING
 CONDITIONS PROVIDE NOTE "MODIFY EXISTING FIXTURE DRAIN
 TO ACCOMMODATE NEW DRAIN LOCATION, COMPLY WITH FBC PL
 SECTION 909.1 AND TABLE 909.1." THIS IS IN LIEU OF
 REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION.
 . 4) PROVIDE NOTE "PROVIDE NEW SHOWER CONTROL VALVE TO
 COMPLY WITH FBC PL 412.3, WHICH SHALL BE PRESSURE
 BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP
 THAT CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND
 TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION
 SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120F, WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION."
 . 5) PER WPB FBC 107.2.1, INDICATE ON THE PLANS THE
 NUMBER OF SHOWER CONTROL VALVES AND HEADS ON EXISTING
 CONDITIONS AND ON PROPOSED CONDITIONS.
 . 5A) PROVIDE TOTAL FLOW RATE (GPM) FOR NEW SHOWER
 CONTROL VALVE(S) AND HEADS. PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS FOR SHOWER CONTROL VALVES AND
 HEADS. IF GREATER THAN 5.7 GPM, THEN REFER TO FBC PL
 TABLE 709.1 REGARDING INCREASED SIZING FOR FIXTURE
 DRAIN. A SANITARY RISER DIAGRAM WILL BE REQUIRED
 SHOWING HOW THIS WILL BE ACCOMPLISHED IN A MANNER THAT
 COMPLIES WITH THE REQUIREMENTS OF FBC PL CHAPTERS 7 AND
 9.
 . 5B) IF QUANTITY OF SHOWER VALVES INCREASED FROM
 EXISTING CONDITIONS, PROVIDE WATER RISER DIAGRAM OF
 IN-WALL PIPING AND SOURCE AND PROVIDE NOTE "WATER
 PIPING SHALL COMPLY WITH REQUIREMENTS OF FBC PL CHAPTER
 6 INCLUDING BUT NOT LIMITED TO SECTIONS 604 (SIZING)
 AND 605.2.1 (LEAD CONTENT)."
 . 5C) IF QUANTITY OF SHOWER VALVES REMAIN THE SAME AS
 EXISTING CONDITIONS, PROVIDE NOTE "MODIFY EXISTING
 IN-WALL WATER PIPING TO ACCOMMODATE NEW SHOWER CONTROL
 VALVE(S). WATER PIPING SHALL COMPLY WITH REQUIREMENTS
 OF FBC PL CHAPTER 6 INCLUDING BUT NOT LIMITED TO
 SECTIONS 604 (SIZING) AND 605.2.1 (LEAD CONTENT)."
  
 . B.BATHTUB
 . 1) NEW BATHTUB APPEARS TO BE SIMILAR IN CONFIGURATION
 TO THE EXISTING TUB THAT IS TO BE REPLACED. PER WPB FBC
 107.2.1, CLARIFY/CONFIRM THAT EXISTING FLOOR
 PENETRATION WILL BE INCORPORATED FOR THIS APPLICATION.
 IF RELOCATED PROVIDE DETAIL OF NEW FLOOR PENETRATION
 AND PROVIDE UL RATED FIRE ASSEMBLY COMPLYING WITH FBC
 CHAPTER 7. IF DRAIN IS RELOCATED FROM EXISTING
 CONDITION INDICATE TYPE OF MATERIAL (I.E. CAST IRON,
 PVC, COPPER) OF TUB DRAIN PIPE PENETRATING THROUGH THE
 FLOOR AND THE TRAP AND HORIZONTAL FIXTURE DRAIN BELOW.
 PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE SHOWER
 FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1 THROUGH
 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW ABANDONED
 PENETRATION WILL BE REMEDIATED.
 . 2) IF TUB DRAIN PENETRATION IS RELOCATED FROM
 EXISTING CONDITIONS PROVIDE NOTE "MODIFY EXISTING
 FIXTURE DRAIN TO ACCOMMODATE NEW DRAIN LOCATION, COMPLY
 WITH FBC PL SECTION 909.1 AND TABLE 909.1." THIS IS IN
 LIEU OF REQUIRING A SANITARY RISER DIAGRAM FOR THIS
 CONDITION.
 . 3) PROVIDE NOTE "PROVIDE ACCESSIBLE TEMPERATURE
 LIMITING DEVICE ON HOT WATER TO MASTER BATH BATHTUB;
 COMPLY WITH FBC PL 412.5. MODIFY EXISTING WATER PIPING
 TO ACCOMMODATE NEW TUB FAUCET AND DEVICE. COMPLY WITH
 REQUIREMENTS OF FBC PL CHAPTER 6 INCLUDING BUT NOT
 LIMITED TO SECTIONS 604 (SIZING), 605.2.1 (LEAD
 CONTENT) AND 607.4 (HOT WATER ON THE LEFT)."
 . 4) PER WPB FBC 107.2.1, PROVIDE DETAIL IN SCHEMATIC
 OF TEMPERATURE LIMITING DEVICE SHOWING HOT AND COLD
 WATER PIPING FROM WALL TO AND FROM DEVICE, VALVING AND
 CONNECTIONS TO TUB VALVE.
  
 . C.LAVATORIES
 . 1) IT WOULD APPEAR THAT THE LAVATORY IN EXISTING
 CONDITIONS IS AN INDIVIDUALLY VENTED FIXTURE DRAIN AND
 THE FLOOR PENETRATION WILL NOT BE RELOCATED. PER WPB
 FBC 107.2.1, CLARIFY/CONFIRM ON THE PLANS. IF THIS IS
 THE CASE PROVIDE NOTE "MODIFY EXISTING IN-WALL SANITARY
 WASTE AND VENT PIPING BY PROVIDING COMMON VENTING OF
 TWO (2) LAVATORIES; COMPLY WITH FBC PL SECTION 909.1,
 TABLE 909.1 AND SECTION 911." THIS IS IN LIEU OF
 REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION.
 IF THIS NOT THE CONDITION, A SANITARY RISER DIAGRAM
 WILL BE REQUIRED SHOWING HOW THIS PIPING WILL BE
 ACCOMPLISHED IN A MANNER THAT COMPLIES WITH THE
 REQUIREMENTS OF FBC PL CHAPTERS 7 AND 9. ADDITIONALLY
 INDICATE TYPE OF MATERIAL (I.E. CAST IRON, PVC) OF
 DRAIN PIPE PENETRATING THROUGH THE FLOOR AND THE
 HORIZONTAL BRANCH BELOW. PROVIDE ASSEMBLY HAVING A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE
 USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS
 REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC
 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE
 REMEDIATED.
 . 2) PER WPB FBC 107.2.1, PROVIDE NOTE "MODIFY EXISTING
 IN-WALL WATER PIPING TO ACCOMMODATE TWO (2) NEW
 LAVATORIES WHICH ARE REPLACING ORIGINAL SINGLE
 LAVATORY; COMPLY WITH REQUIREMENTS OF FBC PL CHAPTER 6
 INCLUDING BUT NOT LIMITED TO SECTIONS 604 (SIZING),
 605.2.1 (LEAD CONTENT) AND 607.4 (HOT WATER ON THE
 LEFT)"
  
 . D.LAUNDRY
 . 1) PROVIDE NOTE "THE VALVES FOR THE STACKABLE WASHING
 MACHINE(S) SHALL BE ACCESSIBLE TO COMPLY WITH FBC PL
 606.3".
 . 2)PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING
 WASHER PLUMBING RECEPTACLE AND THEN ON PROPOSED
 CONDITIONS SHOW PROPOSED LOCATION TO COMPLY WITH FBC PL
 606.3. CLARIFY ON THE PLANS IF THERE WILL BE A CHANGE
 IN THE WATER OUTLETS AND DRAIN INLET LOCATION.
 . 3) IF THERE IS A RELOCATION OF THE PLUMBING WASHER
 RECEPTACLE PROVIDE A SANITARY RISER DIAGRAM DETAILING
 EXISTING CONDITIONS AND A SANITARY RISER DIAGRAM
 DETAILING PROPOSED CONDITIONS HOW THE CHANGES IN PIPING
 WILL BE MADE IN A MANNER THAT COMPLIES WITH THE
 REQUIREMENTS OF FBC PL CHAPTERS 7 AND 9.
 . 3A) IF RELOCATION OF THE PLUMBING WASHER RECEPTACLE
 INCLUDES RELOCATION OF FLOOR PENETRATION INDICATE TYPE
 OF MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE
 PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL THEN
 BRANCH BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING
 WITH THE SHOWER FLOOR PENETRATION AS REQUIRED BY FBC
 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW
 HOW ABANDONED PENETRATION WILL BE REMEDIATED.
 . 4) IF THERE IS A RELOCATION OF THE PLUMBING WASHER
 RECEPTACLE, PROVIDE NOTE "WATER HAMMER ARRESTORS ARE
 REQUIRED AT CLOTHES WASHER PER FPC PL 604.9."
  
 . E. KITCHEN
 . 1) PER WPB FBC 107.2.1, INDICATE ON THE PLANS HOW THE
 WATER AND DRAIN PIPING TO THE SMALL SINK IN THE
 EXISTING KITCHEN WILL BE REMOVED, TO WHAT POINT AND HOW
 THEY WILL BE CAPPED. IF FLOOR PENETRATIONS ARE
 IMPACTED, SHOW HOW THEY WILL BE REMEDIATED.
 . 2)WILL EXISTING WASTE TO KITCHEN SINK WASTE REQUIRE
 NEW FLOOR PENETRATION OR IS IT IN A POSITION TO SERVE
 THE NEW KITCHEN SINK AS IS OR WITH SIMPLE REDIRECTION
 OF HORIZONTAL FIXTURE DRAIN? PER WPB FBC 107.2.1,
 CLARIFY/CONFIRM ON THE PLANS.
 . 2A) IF RELOCATION OF THE KITCHEN SINK INCLUDES
 RELOCATION OF FLOOR PENETRATION INDICATE TYPE OF
 MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE
 PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL BRANCH
 BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING
 OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE
 SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1
 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW
 ABANDONED PENETRATION WILL BE REMEDIATED.
 . 3A) IT APPEARS THAT THE EXISTING KITCHEN SINK DRAIN
 IS VENTED BY EITHER AN ISLAND VENT (FBC PL 916) OR AN
 AIR ADMITTANCE VALVE (FBC PL 918). PER WPB FBC 107.2.1,
 CLARIFY/CONFIRM AND IF SO, CLARIFY WHICH TYPE IT IS.
 . 3A)1. IF IT IS WITH AN AIR ADMITTANCE VALVE PROVIDE
 NOTE "MODIFY EXISTING SANITARY WASTE AND VENT PIPING
 FOR KITCHEN SINK BY PROVIDING DIRECTIONAL CHANGE OF
 HORIZONTAL FIXTURE DRAIN TO ACCOMMODATE NEW LOCATION OF
 SINK; COMPLY WITH FBC PL FBC PL SECTION 909.1, TABLE
 909.1 AND SECTION 918." THIS IS IN LIEU OF REQUIRING A
 SANITARY RISER DIAGRAM FOR THIS CONDITION.
 . 3A)2. IF IT IS WITH AN ISLAND VENT PROVIDE NOTE
 "MODIFY EXISTING SANITARY WASTE AND VENT PIPING FOR
 KITCHEN SINK BY PROVIDING DIRECTIONAL CHANGE OF
 HORIZONTAL FIXTURE DRAIN AND VENT PIPING TO ACCOMMODATE
 NEW LOCATION OF SINK; COMPLY WITH FBC PL FBC PL SECTION
 909.1, TABLE 909.1 AND SECTION 916." THIS IS IN LIEU OF
 REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION.
 PLEASE NOTE THAT YOU CAN ELIMINATE THE ISLAND VENT
 PIPING BY REMOVING THE LOOP PORTION OF THE ISLAND CENT,
 CAPPING THE CONNECTION BACK TO WASTE AND PROVIDING AN
 AIR ADMITTANCE VALVE ABOVE THE TRAP ARM INLET. IF THIS
 WOULD BE THE CONDITION THEN PROVIDE NOTE "MODIFY
 EXISTING SANITARY WASTE AND VENT PIPING FOR KITCHEN
 SINK BY PROVIDING DIRECTIONAL CHANGE OF HORIZONTAL
 FIXTURE DRAIN, ELIMINATING LOOP PORTION OF EXISTING
 ISLAND VENT, CAPPING THE CONNECTION BACK TO WASTE AND
 PROVIDE AN AIR ADMITTANCE VALVE ABOVE THE TRAP ARM
 INLET TO ACCOMMODATE NEW LOCATION OF SINK; COMPLY WITH
 FBC PL FBC PL SECTION 909.1, TABLE 909.1 AND SECTION
 918." THIS IS IN LIEU OF REQUIRING A SANITARY RISER
 DIAGRAM FOR THIS CONDITION.
 . 3A)3. IF NONE OF THESE CONDITIONS ARE THE CASE A
 SANITARY RISER DIAGRAM WILL BE REQUIRED SHOWING HOW
 THIS PIPING WILL BE ACCOMPLISHED IN A MANNER THAT
 COMPLIES WITH THE REQUIREMENTS OF FBC PL CHAPTERS 7 AND
 9.
 . 3) PER WPB FBC 107.2.1, PROVIDE NOTE "WATER HAMMER
 ARRESTORS ARE REQUIRED AT WATER SUPPLIES TO DISHWASHER
 AND ICE LINE PER FPC PL 604.9."
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030338 529 S FLAGLER DR # 31E
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By medwards Date 2021-04-27 Time 13:40 Rev Time 0.00
Received By medwards Date 2021-04-27 Time 13:40 Sent To  
Notes
2021-04-27 13:40:46ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-12 Cont ID  
Sent By medwards Date 2021-03-12 Time 13:21 Rev Time 0.00
Received By medwards Date 2021-03-12 Time 13:20 Sent To  
Notes
2021-03-12 13:21:54ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 1 Status N Date 2021-03-30 Cont ID  
Sent By eleveque Date 2021-03-30 Time 10:46 Rev Time 0.00
Received By elevesqu Date 2021-03-30 Time 10:46 Sent To  
Notes
***NONE***