| 2021-04-15 14:21:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21030338 529 S FLAGLER DR # 31E |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: |
| | |
| | I. PER WPB FBC 105.1,A PLUMBING SUB PERMIT IS REQUIRED |
| | AND SHALL BE APPLIED FOR BY A LICENSED PLUMBING |
| | CONTRACTOR. |
| | |
| | II. PER WPB FBC 107.2.1 AND 107.3.5.1.3, A PLUMBING |
| | PLAN IS REQUIRED SHOWING EXISTING SIZED SANITARY SOIL, |
| | WASTE AND VENT RISERS AND HORIZONTAL BRANCHES. CHASES |
| | AND PARTITIONS SHALL NOT BE BLOCKED IN SOLID SO THAT |
| | THE RISERS CAN BE EASILY SEEN ON THE PLAN. |
| | |
| | III. ITEMIZED COMMENTS |
| | |
| | 1.MASTER BATH |
| | . A.SHOWER |
| | . 1) DRAIN LOCATION APPEARS TO BE RELOCATED; PER WPB |
| | FBC 107.2.1, CLARIFY. IF NOT TO BE RELOCATED, STATE AS |
| | MUCH ON THE PLANS AND IF RELOCATED PROVIDE DETAIL OF |
| | NEW FLOOR PENETRATION AND PROVIDE UL RATED FIRE |
| | ASSEMBLY COMPLYING WITH FBC CHAPTER 7. IF DRAIN IS |
| | RELOCATED FROM EXISTING CONDITION INDICATE TYPE OF |
| | MATERIAL (I.E. CAST IRON, PVC) OF SHOWER DRAIN PIPE |
| | PENETRATING THROUGH THE FLOOR AND THE TRAP AND |
| | HORIZONTAL FIXTURE DRAIN BELOW. PROVIDE ASSEMBLY HAVING |
| | A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE |
| | USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS |
| | REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC |
| | 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE |
| | REMEDIATED. |
| | . 2) SHOWER CURB DETAIL ON SHEET 01; PROPOSED |
| | CONDITIONS. THE DETAIL SHOWER PAN AND CURB DETAIL SHALL |
| | PER WPB FBC 107.2.1, SHOW COMPLIANCE WITH FBC PL |
| | SECTION 421 INCLUDING THE REQUIRED 2% PITCH REQUIRED |
| | FOR THE MEMBRANE, TYPE OF LINER MATERIAL, WALL SECTION |
| | SHOWING BACKER FOR MEMBRANE AND HEIGHT OF LINER AT WALL |
| | ABOVE TOP OF FINISHED CURB, DRAIN BODY WITH STRAINER |
| | AND CLAMPING RING. |
| | . 3) IF SHOWER DRAIN IS RELOCATED FROM EXISTING |
| | CONDITIONS PROVIDE NOTE "MODIFY EXISTING FIXTURE DRAIN |
| | TO ACCOMMODATE NEW DRAIN LOCATION, COMPLY WITH FBC PL |
| | SECTION 909.1 AND TABLE 909.1." THIS IS IN LIEU OF |
| | REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION. |
| | . 4) PROVIDE NOTE "PROVIDE NEW SHOWER CONTROL VALVE TO |
| | COMPLY WITH FBC PL 412.3, WHICH SHALL BE PRESSURE |
| | BALANCED PB, THERMOSTATIC MIXING (TM) OR COMBINATION |
| | PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP |
| | THAT CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND |
| | TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION |
| | SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM |
| | SETTING OF THE VALVE TO 120F, WHICH SHALL BE FIELD |
| | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | UTILIZED FOR COMPLIANCE WITH THIS SECTION." |
| | . 5) PER WPB FBC 107.2.1, INDICATE ON THE PLANS THE |
| | NUMBER OF SHOWER CONTROL VALVES AND HEADS ON EXISTING |
| | CONDITIONS AND ON PROPOSED CONDITIONS. |
| | . 5A) PROVIDE TOTAL FLOW RATE (GPM) FOR NEW SHOWER |
| | CONTROL VALVE(S) AND HEADS. PROVIDE MANUFACTURER'S |
| | SPECIFICATION SHEETS FOR SHOWER CONTROL VALVES AND |
| | HEADS. IF GREATER THAN 5.7 GPM, THEN REFER TO FBC PL |
| | TABLE 709.1 REGARDING INCREASED SIZING FOR FIXTURE |
| | DRAIN. A SANITARY RISER DIAGRAM WILL BE REQUIRED |
| | SHOWING HOW THIS WILL BE ACCOMPLISHED IN A MANNER THAT |
| | COMPLIES WITH THE REQUIREMENTS OF FBC PL CHAPTERS 7 AND |
| | 9. |
| | . 5B) IF QUANTITY OF SHOWER VALVES INCREASED FROM |
| | EXISTING CONDITIONS, PROVIDE WATER RISER DIAGRAM OF |
| | IN-WALL PIPING AND SOURCE AND PROVIDE NOTE "WATER |
| | PIPING SHALL COMPLY WITH REQUIREMENTS OF FBC PL CHAPTER |
| | 6 INCLUDING BUT NOT LIMITED TO SECTIONS 604 (SIZING) |
| | AND 605.2.1 (LEAD CONTENT)." |
| | . 5C) IF QUANTITY OF SHOWER VALVES REMAIN THE SAME AS |
| | EXISTING CONDITIONS, PROVIDE NOTE "MODIFY EXISTING |
| | IN-WALL WATER PIPING TO ACCOMMODATE NEW SHOWER CONTROL |
| | VALVE(S). WATER PIPING SHALL COMPLY WITH REQUIREMENTS |
| | OF FBC PL CHAPTER 6 INCLUDING BUT NOT LIMITED TO |
| | SECTIONS 604 (SIZING) AND 605.2.1 (LEAD CONTENT)." |
| | |
| | . B.BATHTUB |
| | . 1) NEW BATHTUB APPEARS TO BE SIMILAR IN CONFIGURATION |
| | TO THE EXISTING TUB THAT IS TO BE REPLACED. PER WPB FBC |
| | 107.2.1, CLARIFY/CONFIRM THAT EXISTING FLOOR |
| | PENETRATION WILL BE INCORPORATED FOR THIS APPLICATION. |
| | IF RELOCATED PROVIDE DETAIL OF NEW FLOOR PENETRATION |
| | AND PROVIDE UL RATED FIRE ASSEMBLY COMPLYING WITH FBC |
| | CHAPTER 7. IF DRAIN IS RELOCATED FROM EXISTING |
| | CONDITION INDICATE TYPE OF MATERIAL (I.E. CAST IRON, |
| | PVC, COPPER) OF TUB DRAIN PIPE PENETRATING THROUGH THE |
| | FLOOR AND THE TRAP AND HORIZONTAL FIXTURE DRAIN BELOW. |
| | PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING OF NOT |
| | LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE SHOWER |
| | FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1 THROUGH |
| | 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW ABANDONED |
| | PENETRATION WILL BE REMEDIATED. |
| | . 2) IF TUB DRAIN PENETRATION IS RELOCATED FROM |
| | EXISTING CONDITIONS PROVIDE NOTE "MODIFY EXISTING |
| | FIXTURE DRAIN TO ACCOMMODATE NEW DRAIN LOCATION, COMPLY |
| | WITH FBC PL SECTION 909.1 AND TABLE 909.1." THIS IS IN |
| | LIEU OF REQUIRING A SANITARY RISER DIAGRAM FOR THIS |
| | CONDITION. |
| | . 3) PROVIDE NOTE "PROVIDE ACCESSIBLE TEMPERATURE |
| | LIMITING DEVICE ON HOT WATER TO MASTER BATH BATHTUB; |
| | COMPLY WITH FBC PL 412.5. MODIFY EXISTING WATER PIPING |
| | TO ACCOMMODATE NEW TUB FAUCET AND DEVICE. COMPLY WITH |
| | REQUIREMENTS OF FBC PL CHAPTER 6 INCLUDING BUT NOT |
| | LIMITED TO SECTIONS 604 (SIZING), 605.2.1 (LEAD |
| | CONTENT) AND 607.4 (HOT WATER ON THE LEFT)." |
| | . 4) PER WPB FBC 107.2.1, PROVIDE DETAIL IN SCHEMATIC |
| | OF TEMPERATURE LIMITING DEVICE SHOWING HOT AND COLD |
| | WATER PIPING FROM WALL TO AND FROM DEVICE, VALVING AND |
| | CONNECTIONS TO TUB VALVE. |
| | |
| | . C.LAVATORIES |
| | . 1) IT WOULD APPEAR THAT THE LAVATORY IN EXISTING |
| | CONDITIONS IS AN INDIVIDUALLY VENTED FIXTURE DRAIN AND |
| | THE FLOOR PENETRATION WILL NOT BE RELOCATED. PER WPB |
| | FBC 107.2.1, CLARIFY/CONFIRM ON THE PLANS. IF THIS IS |
| | THE CASE PROVIDE NOTE "MODIFY EXISTING IN-WALL SANITARY |
| | WASTE AND VENT PIPING BY PROVIDING COMMON VENTING OF |
| | TWO (2) LAVATORIES; COMPLY WITH FBC PL SECTION 909.1, |
| | TABLE 909.1 AND SECTION 911." THIS IS IN LIEU OF |
| | REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION. |
| | IF THIS NOT THE CONDITION, A SANITARY RISER DIAGRAM |
| | WILL BE REQUIRED SHOWING HOW THIS PIPING WILL BE |
| | ACCOMPLISHED IN A MANNER THAT COMPLIES WITH THE |
| | REQUIREMENTS OF FBC PL CHAPTERS 7 AND 9. ADDITIONALLY |
| | INDICATE TYPE OF MATERIAL (I.E. CAST IRON, PVC) OF |
| | DRAIN PIPE PENETRATING THROUGH THE FLOOR AND THE |
| | HORIZONTAL BRANCH BELOW. PROVIDE ASSEMBLY HAVING A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE |
| | USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS |
| | REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC |
| | 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE |
| | REMEDIATED. |
| | . 2) PER WPB FBC 107.2.1, PROVIDE NOTE "MODIFY EXISTING |
| | IN-WALL WATER PIPING TO ACCOMMODATE TWO (2) NEW |
| | LAVATORIES WHICH ARE REPLACING ORIGINAL SINGLE |
| | LAVATORY; COMPLY WITH REQUIREMENTS OF FBC PL CHAPTER 6 |
| | INCLUDING BUT NOT LIMITED TO SECTIONS 604 (SIZING), |
| | 605.2.1 (LEAD CONTENT) AND 607.4 (HOT WATER ON THE |
| | LEFT)" |
| | |
| | . D.LAUNDRY |
| | . 1) PROVIDE NOTE "THE VALVES FOR THE STACKABLE WASHING |
| | MACHINE(S) SHALL BE ACCESSIBLE TO COMPLY WITH FBC PL |
| | 606.3". |
| | . 2)PER WPB FBC 107.2.1, SHOW LOCATION OF EXISTING |
| | WASHER PLUMBING RECEPTACLE AND THEN ON PROPOSED |
| | CONDITIONS SHOW PROPOSED LOCATION TO COMPLY WITH FBC PL |
| | 606.3. CLARIFY ON THE PLANS IF THERE WILL BE A CHANGE |
| | IN THE WATER OUTLETS AND DRAIN INLET LOCATION. |
| | . 3) IF THERE IS A RELOCATION OF THE PLUMBING WASHER |
| | RECEPTACLE PROVIDE A SANITARY RISER DIAGRAM DETAILING |
| | EXISTING CONDITIONS AND A SANITARY RISER DIAGRAM |
| | DETAILING PROPOSED CONDITIONS HOW THE CHANGES IN PIPING |
| | WILL BE MADE IN A MANNER THAT COMPLIES WITH THE |
| | REQUIREMENTS OF FBC PL CHAPTERS 7 AND 9. |
| | . 3A) IF RELOCATION OF THE PLUMBING WASHER RECEPTACLE |
| | INCLUDES RELOCATION OF FLOOR PENETRATION INDICATE TYPE |
| | OF MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE |
| | PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL THEN |
| | BRANCH BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE |
| | RATING OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING |
| | WITH THE SHOWER FLOOR PENETRATION AS REQUIRED BY FBC |
| | 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW |
| | HOW ABANDONED PENETRATION WILL BE REMEDIATED. |
| | . 4) IF THERE IS A RELOCATION OF THE PLUMBING WASHER |
| | RECEPTACLE, PROVIDE NOTE "WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT CLOTHES WASHER PER FPC PL 604.9." |
| | |
| | . E. KITCHEN |
| | . 1) PER WPB FBC 107.2.1, INDICATE ON THE PLANS HOW THE |
| | WATER AND DRAIN PIPING TO THE SMALL SINK IN THE |
| | EXISTING KITCHEN WILL BE REMOVED, TO WHAT POINT AND HOW |
| | THEY WILL BE CAPPED. IF FLOOR PENETRATIONS ARE |
| | IMPACTED, SHOW HOW THEY WILL BE REMEDIATED. |
| | . 2)WILL EXISTING WASTE TO KITCHEN SINK WASTE REQUIRE |
| | NEW FLOOR PENETRATION OR IS IT IN A POSITION TO SERVE |
| | THE NEW KITCHEN SINK AS IS OR WITH SIMPLE REDIRECTION |
| | OF HORIZONTAL FIXTURE DRAIN? PER WPB FBC 107.2.1, |
| | CLARIFY/CONFIRM ON THE PLANS. |
| | . 2A) IF RELOCATION OF THE KITCHEN SINK INCLUDES |
| | RELOCATION OF FLOOR PENETRATION INDICATE TYPE OF |
| | MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE |
| | PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL BRANCH |
| | BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING |
| | OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE |
| | SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1 |
| | THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW |
| | ABANDONED PENETRATION WILL BE REMEDIATED. |
| | . 3A) IT APPEARS THAT THE EXISTING KITCHEN SINK DRAIN |
| | IS VENTED BY EITHER AN ISLAND VENT (FBC PL 916) OR AN |
| | AIR ADMITTANCE VALVE (FBC PL 918). PER WPB FBC 107.2.1, |
| | CLARIFY/CONFIRM AND IF SO, CLARIFY WHICH TYPE IT IS. |
| | . 3A)1. IF IT IS WITH AN AIR ADMITTANCE VALVE PROVIDE |
| | NOTE "MODIFY EXISTING SANITARY WASTE AND VENT PIPING |
| | FOR KITCHEN SINK BY PROVIDING DIRECTIONAL CHANGE OF |
| | HORIZONTAL FIXTURE DRAIN TO ACCOMMODATE NEW LOCATION OF |
| | SINK; COMPLY WITH FBC PL FBC PL SECTION 909.1, TABLE |
| | 909.1 AND SECTION 918." THIS IS IN LIEU OF REQUIRING A |
| | SANITARY RISER DIAGRAM FOR THIS CONDITION. |
| | . 3A)2. IF IT IS WITH AN ISLAND VENT PROVIDE NOTE |
| | "MODIFY EXISTING SANITARY WASTE AND VENT PIPING FOR |
| | KITCHEN SINK BY PROVIDING DIRECTIONAL CHANGE OF |
| | HORIZONTAL FIXTURE DRAIN AND VENT PIPING TO ACCOMMODATE |
| | NEW LOCATION OF SINK; COMPLY WITH FBC PL FBC PL SECTION |
| | 909.1, TABLE 909.1 AND SECTION 916." THIS IS IN LIEU OF |
| | REQUIRING A SANITARY RISER DIAGRAM FOR THIS CONDITION. |
| | PLEASE NOTE THAT YOU CAN ELIMINATE THE ISLAND VENT |
| | PIPING BY REMOVING THE LOOP PORTION OF THE ISLAND CENT, |
| | CAPPING THE CONNECTION BACK TO WASTE AND PROVIDING AN |
| | AIR ADMITTANCE VALVE ABOVE THE TRAP ARM INLET. IF THIS |
| | WOULD BE THE CONDITION THEN PROVIDE NOTE "MODIFY |
| | EXISTING SANITARY WASTE AND VENT PIPING FOR KITCHEN |
| | SINK BY PROVIDING DIRECTIONAL CHANGE OF HORIZONTAL |
| | FIXTURE DRAIN, ELIMINATING LOOP PORTION OF EXISTING |
| | ISLAND VENT, CAPPING THE CONNECTION BACK TO WASTE AND |
| | PROVIDE AN AIR ADMITTANCE VALVE ABOVE THE TRAP ARM |
| | INLET TO ACCOMMODATE NEW LOCATION OF SINK; COMPLY WITH |
| | FBC PL FBC PL SECTION 909.1, TABLE 909.1 AND SECTION |
| | 918." THIS IS IN LIEU OF REQUIRING A SANITARY RISER |
| | DIAGRAM FOR THIS CONDITION. |
| | . 3A)3. IF NONE OF THESE CONDITIONS ARE THE CASE A |
| | SANITARY RISER DIAGRAM WILL BE REQUIRED SHOWING HOW |
| | THIS PIPING WILL BE ACCOMPLISHED IN A MANNER THAT |
| | COMPLIES WITH THE REQUIREMENTS OF FBC PL CHAPTERS 7 AND |
| | 9. |
| | . 3) PER WPB FBC 107.2.1, PROVIDE NOTE "WATER HAMMER |
| | ARRESTORS ARE REQUIRED AT WATER SUPPLIES TO DISHWASHER |
| | AND ICE LINE PER FPC PL 604.9." |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |