| 2021-03-30 17:00:00 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21030333 |
| | ADD: 1700 45TH ST. UNIT: 1801 |
| | CONT: STANISLAUS ENTERPRISE INC. |
| | TEL: 561-676-6107 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 30TH/ 2021 |
| | ACTION: DENIED |
| | |
| | SHEET A-00 THE COVERSHEET STATES THE SCOPE OF WORK TO |
| | PROVIDE A TAKEOUT/ DINING RESTAURANT: |
| | |
| | 1A) THE CODE RESEARCH STATES THE PLANS WERE DEVELOPED |
| | UNDER THE 2017 FBC-B. PLEASE BE AWARE ON DEC. 31ST/ |
| | 2020 THE 7TH EDITION, 2020 FLORIDA BUILDING CODE WAS |
| | ADOPTED STATEWIDE. PLEASE CORRECT ALL REFERENCES TO THE |
| | 2017 FBC-BUILDING. |
| | |
| | 1B) (1)THE OCCUPANCY TYPE IS DECLARED A A-2 ASSEMBLY. |
| | PLEASE REVIEW THE 2020 FBC-BUILDING SECTION 301.2. |
| | SMALL ASSEMBLY SPACES WHERE (1) THE OCCUPANT LOAD FOR |
| | ROOMS OR SPACES USED FOR ASSEMBLY PURPOSES HAS A |
| | OCCUPANT LOAD OF LESS THAN 50 OCCUPANTS AND ASSEMBLY |
| | USE ROOM WHERE THE ASSEMBLY ROOM IS LES THAN 750 SQ. |
| | FT. THEN THE OCCUPANCY TYPE IS DECLARED A BUSINESS |
| | OCCUPANCY. |
| | |
| | 1B)(2) THE OCCUPANT LOAD IS DECLARED IN THE DINING AREA |
| | 297/15= 20 OCCUPANTS, BUT ON THE S-1 LIFE SAFETY SHEET |
| | THE SEATING IS SHOWN WITH 24 SEATS. AS THE DESIGNER YOU |
| | CAN DECLARE AN INCREASED OCCUPANT LOAD SEE SECTION |
| | 1004.2 OF THE 2020 FBC-B PLEASE UPDATE THE PLAN ( SHEET |
| | A-00 OCCUPANT LOADS) WITH THE INCREASED SEATING LOAD. |
| | |
| | 1C) THE CODE RESEARCH LIST THIS AS A LEVEL II |
| | ALTERATION. IN RESEARCHING THE LAST KNOWN USE FOR THIS |
| | TENANT SPACE (BUSINESS TAX RECORDS) THIS WAS AN |
| | MERCANTILE OCCUPANCY SELLING CELL PHONES & ACCESSORIES. |
| | THIS PERMIT THEN IS THEN DECLARED A |
| | CHANGE OF OCCUPANCY AND SECTION 1001.2.2.1 PARTIAL |
| | CHANGE OF OCCUPANCY OF THE 2020 FBC-EXISTING BUILDING |
| | CODE. SECTION 1012 SHALL APPLY IN THE EXISTING BUILDING |
| | CODE. |
| | |
| | 1D) PLEASE PROVIDE A SITE PLAN WHERE THIS TENANT SPACE |
| | IS LOCATED SINCE IN THIS SHOPPING CENTER PART OF IT |
| | LIES IN THE TOWN OF MANGONIA PARK. THIS MAY NOT BE IN |
| | THE CITY LIMITS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. GOGGLE MAPS. |
| | |
| | 2) WIND ANALYSIS CAN NOT BE DETERMINED UNTIL A SITE |
| | PLAN IS PROVIDED SHOWING THE LOCATION OF THIS TENANT |
| | SPACE. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | GOOGLE MAPS. |
| | |
| | 3) SHEET S-1 THE LIFE SAFETY SHEET SHOWING 24 SEATS AND |
| | ONLY ONE ACCESSIBLE SEAT. 24 X0.05= 1.2 ALWAYS ROUND UP |
| | OR 2 ACCESSIBLE SEATS REQUIRED. 2020FBC-ACCESSIBILITY |
| | CODE SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED |
| | FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 |
| | PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | |
| | 4) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS. |
| | CODE SECTION 902.2 CLEAR FLOOR OR GROUND SPACE FOR |
| | ACCESSIBLE SEATING. A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305 POSITIONED FOR A FORWARD APPROACH SHALL BE |
| | PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306 |
| | SHALL BE PROVIDED. |
| | |
| | 5) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS. |
| | CODE SECTION 902.3 HEIGHT. THE TOPS OF DINING SURFACES |
| | AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6) SHEET S-1 THE LIFE SAFETY SHEET. THE FLOOR PLAN |
| | SHOWS ANEW DRIVE UP WINDOW FOR PICK UP & PAY. THE PLAN |
| | SHOW A DETAIL 5/ A-04. PLEASE NOTE THERE IS NO A-04 |
| | SHEET WITH DETAILS. 107.2.1.2. ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 6A) SUBMIT PRODUCT APPROVALS FOR COMPLIANCE WITH |
| | COMPONENTS AND CLADDING. 2020 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS & MULLIONS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOFTOP CURBS FOR |
| | RTU UNITS AND INTAKE OR EXHAUST FANS (HOODS) |
| | (G) ROOFTOP PRE-ENGINEERED A/C STANDS |
| | |
| | 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 7) MISSING WIND DESIGN DATA. PRESSURES ARE NEEDED TO BE |
| | IN VASD FOR ZONES 1.2.3.4 & 5. |
| | 2020 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 7.2. RISK CATEGORY. |
| | |
| | 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | |
| | 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 7.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 8) MECHANICAL SHEET M-2 MOUNTING , REFERS TO |
| | MANUFACTURER MOUNTING DRAWINGS WIND LOAD CALCULATIONS, |
| | AND PLACEMENT OF BRACKETS AND FASTENERS FOR THE RTU TO |
| | ROOF TOP CURB. |
| | 2020 FBC-M- 301.15 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | |
| | LATERAL FORCE-RESISTING SYSTEM |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, |
| | AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING & |
| | DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE |
| | EQUIPMENT ABOVE. |
| | |
| | 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 9) SHEET S-1 THE LIFE SAFETY SHEET. AT THE FOOD PICK UP |
| | WINDOW THERE IS ALSO A NOTE FOR A PREFABRICATED |
| | OVERHEAD AWNING BY OTHERS SEE ATTACHED SPECS. |
| | |
| | 10) THE M-2 SHEET SHOWS CURB TO ROOF JOIST ATTACHMENT |
| | DETAIL PLEASE SHOW COMPLIANCE WITH WELDED OR BOLTED |
| | CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 11) 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION |
| | OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | |
| | |
| | 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |