Plan Review Details - Permit 21030333
Plan Review Stops For Permit 21030333
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-13 Cont ID  
Sent By jwitmer Date 2021-06-13 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2021-06-13 Time 15:46 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By jwitmer Date 2021-03-30 Time 17:03 Rev Time 0.00
Received By jwitmer Date 2021-03-30 Time 15:22 Sent To  
Notes
2021-03-30 17:00:55COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-13 Cont ID  
Sent By jwitmer Date 2021-06-13 Time 16:46 Rev Time 0.00
Received By jwitmer Date 2021-06-13 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By jwitmer Date 2021-03-30 Time 17:04 Rev Time 0.00
Received By jwitmer Date 2021-03-30 Time 15:22 Sent To  
Notes
2021-03-30 17:00:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030333
 ADD: 1700 45TH ST. UNIT: 1801
 CONT: STANISLAUS ENTERPRISE INC.
 TEL: 561-676-6107
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 30TH/ 2021
 ACTION: DENIED
  
 SHEET A-00 THE COVERSHEET STATES THE SCOPE OF WORK TO
 PROVIDE A TAKEOUT/ DINING RESTAURANT:
  
 1A) THE CODE RESEARCH STATES THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-B. PLEASE BE AWARE ON DEC. 31ST/
 2020 THE 7TH EDITION, 2020 FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE. PLEASE CORRECT ALL REFERENCES TO THE
 2017 FBC-BUILDING.
  
 1B) (1)THE OCCUPANCY TYPE IS DECLARED A A-2 ASSEMBLY.
 PLEASE REVIEW THE 2020 FBC-BUILDING SECTION 301.2.
 SMALL ASSEMBLY SPACES WHERE (1) THE OCCUPANT LOAD FOR
 ROOMS OR SPACES USED FOR ASSEMBLY PURPOSES HAS A
 OCCUPANT LOAD OF LESS THAN 50 OCCUPANTS AND ASSEMBLY
 USE ROOM WHERE THE ASSEMBLY ROOM IS LES THAN 750 SQ.
 FT. THEN THE OCCUPANCY TYPE IS DECLARED A BUSINESS
 OCCUPANCY.
  
 1B)(2) THE OCCUPANT LOAD IS DECLARED IN THE DINING AREA
 297/15= 20 OCCUPANTS, BUT ON THE S-1 LIFE SAFETY SHEET
 THE SEATING IS SHOWN WITH 24 SEATS. AS THE DESIGNER YOU
 CAN DECLARE AN INCREASED OCCUPANT LOAD SEE SECTION
 1004.2 OF THE 2020 FBC-B PLEASE UPDATE THE PLAN ( SHEET
 A-00 OCCUPANT LOADS) WITH THE INCREASED SEATING LOAD.
  
 1C) THE CODE RESEARCH LIST THIS AS A LEVEL II
 ALTERATION. IN RESEARCHING THE LAST KNOWN USE FOR THIS
 TENANT SPACE (BUSINESS TAX RECORDS) THIS WAS AN
 MERCANTILE OCCUPANCY SELLING CELL PHONES & ACCESSORIES.
 THIS PERMIT THEN IS THEN DECLARED A
 CHANGE OF OCCUPANCY AND SECTION 1001.2.2.1 PARTIAL
 CHANGE OF OCCUPANCY OF THE 2020 FBC-EXISTING BUILDING
 CODE. SECTION 1012 SHALL APPLY IN THE EXISTING BUILDING
 CODE.
  
 1D) PLEASE PROVIDE A SITE PLAN WHERE THIS TENANT SPACE
 IS LOCATED SINCE IN THIS SHOPPING CENTER PART OF IT
 LIES IN THE TOWN OF MANGONIA PARK. THIS MAY NOT BE IN
 THE CITY LIMITS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. GOGGLE MAPS.
  
 2) WIND ANALYSIS CAN NOT BE DETERMINED UNTIL A SITE
 PLAN IS PROVIDED SHOWING THE LOCATION OF THIS TENANT
 SPACE. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 GOOGLE MAPS.
  
 3) SHEET S-1 THE LIFE SAFETY SHEET SHOWING 24 SEATS AND
 ONLY ONE ACCESSIBLE SEAT. 24 X0.05= 1.2 ALWAYS ROUND UP
 OR 2 ACCESSIBLE SEATS REQUIRED. 2020FBC-ACCESSIBILITY
 CODE SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 4) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS.
 CODE SECTION 902.2 CLEAR FLOOR OR GROUND SPACE FOR
 ACCESSIBLE SEATING. A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR A FORWARD APPROACH SHALL BE
 PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
  
 5) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS.
 CODE SECTION 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET S-1 THE LIFE SAFETY SHEET. THE FLOOR PLAN
 SHOWS ANEW DRIVE UP WINDOW FOR PICK UP & PAY. THE PLAN
 SHOW A DETAIL 5/ A-04. PLEASE NOTE THERE IS NO A-04
 SHEET WITH DETAILS. 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 6A) SUBMIT PRODUCT APPROVALS FOR COMPLIANCE WITH
 COMPONENTS AND CLADDING. 2020 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOFTOP CURBS FOR
 RTU UNITS AND INTAKE OR EXHAUST FANS (HOODS)
 (G) ROOFTOP PRE-ENGINEERED A/C STANDS
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) MISSING WIND DESIGN DATA. PRESSURES ARE NEEDED TO BE
 IN VASD FOR ZONES 1.2.3.4 & 5.
 2020 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 7.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 8) MECHANICAL SHEET M-2 MOUNTING , REFERS TO
 MANUFACTURER MOUNTING DRAWINGS WIND LOAD CALCULATIONS,
 AND PLACEMENT OF BRACKETS AND FASTENERS FOR THE RTU TO
 ROOF TOP CURB.
 2020 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 9) SHEET S-1 THE LIFE SAFETY SHEET. AT THE FOOD PICK UP
 WINDOW THERE IS ALSO A NOTE FOR A PREFABRICATED
 OVERHEAD AWNING BY OTHERS SEE ATTACHED SPECS.
  
 10) THE M-2 SHEET SHOWS CURB TO ROOF JOIST ATTACHMENT
 DETAIL PLEASE SHOW COMPLIANCE WITH WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 11) 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION
 OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
  
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-06 Cont ID  
Sent By jleahy Date 2021-04-06 Time 08:10 Rev Time 0.00
Received By jleahy Date 2021-04-06 Time 07:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-11 Cont ID  
Sent By pleduc Date 2021-06-11 Time   Rev Time 0.00
Received By pleduc Date 2021-06-08 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By pleduc Date 2021-03-12 Time   Rev Time 0.00
Received By pleduc Date 2021-03-12 Time 16:14 Sent To  
Notes
2021-03-12 16:20:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEETS E 1 INDICATES 2 DOORS OPENING OUT FROM THE
 KITCHEN BOTH INTO A CORRIDOR RESTRICTING THE MEANS OF
 EGRESS.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET M 1 INDICATES HOOD PLAN BY OTHERS.
  
 THE HOOD AND SUPPRESSION SYSTEMS SHALL BE SUBMITTED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 14:24 Rev Time 0.00
Received By ccole Date 2021-06-25 Time 10:36 Sent To  
Notes
2021-06-28 14:25:55A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE LP
 TANK INSTALLTIONS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By ccole Date 2021-04-15 Time 08:46 Rev Time 0.00
Received By ccole Date 2021-04-14 Time 18:09 Sent To  
Notes
2021-04-15 08:46:341ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030333
 4/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA 58- 2017
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: CLARIFY THE NUMBER OF LP TANKS TO
 BE INSTALLED. P-1 SHOWS 3 TANKS WITH 2 MANIFOLDED
 TOGETHER, P-2 SHOWS 2 TANKS- SECTION 107.2.1 WPB.
  
 2) P-1 & P-2: INDICATE THE GALLON SIZES OF THE TANKS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 5.2.1.1 NFPA 58.
  
 3) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE
 REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH
 THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW
 HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND
 WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58.
  
 4) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE
 CLEARANCE DISTANCES FOR THE TANKS TO THE BUILDING- SEE
 SECTIONS 6.4.3.2 (A) & (B) AND TABLE 6.4.1.1 NFPA 58.
  
 5) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE
 CLEARANCE DISTANCES FOR THE TANK RELIEF VALVES TO THE
 REAR DOOR OPENING, MECHANICAL AIR INTAKES, AND EXTERIOR
 SOURCES OF IGNITION- SECTIONS 6.4.4.3 & 6.4.4.4 AND
 TABLE 6.4.4.3 NFPA 58.
  
 6) P-1 & P-2: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1
 NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE
 REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A
 2 PSI REGULATOR IS REQUIRED FOR THE 11 IN.WC SYSTEM.
 PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATOR.
 7) P-1: REFER TO SECTION 6.10.1.7 NFPA 58 AND INDICATE
 THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE RELIEF
 VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL AIR
 INTAKES, AND ANY SOURCE OF IGNITION.
  
 8) P-1 & P-2: SUBMIT MANUFACTURER'S DATA SHEETS FOR THE
 COOKING APPLIANCES SHOWING APPLIANCE LISTINGS, BTU
 CAPACITIES, AND INPUT PRESSURES- SECTION 623.1 FBC FG.
  
 9) P-1 & P-2: INDICATE HOW COMBUSTION AIR WILL BE
 PROVIDED TO THE COOKING APPLIANCES AND PROVIDED
 CALCULATIONS- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 08:29 Rev Time 0.00
Received By medwards Date 2021-07-22 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 15:36 Rev Time 0.00
Received By medwards Date 2021-07-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-28 Time   Rev Time 0.00
Received By aoliver Date 2021-06-07 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By rmcdouga Date 2021-05-17 Time 12:40 Rev Time 0.00
Received By rmcdouga Date 2021-03-11 Time 10:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-08-16 Cont ID  
Sent By lmarchan Date 2021-08-16 Time 15:10 Rev Time 0.00
Received By lmarchan Date 2021-08-09 Time 11:52 Sent To  
Notes
2021-08-16 14:25:11RECEIPT MU-2021-39268 - $27,537.38 PAID
2021-08-09 11:52:538-9-21 UPLOADED IMPACT FEES QUESTIONNAIRE - EMAILED PBC
 IMPACT OFFICE TO REVIEW. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-30 Cont ID  
Sent By jwitmer Date 2021-03-30 Time 17:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-03-30 17:03:35IMPACT FEE REVIEW, CHANGE IN OCCUPANCY AND NEW POINT OF
 SALE DRIVE UP WINDOW.
 IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 08:27 Rev Time 0.00
Received By medwards Date 2021-07-28 Time 08:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 15:29 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 15:29 Sent To  
Notes
2021-07-21 15:30:53PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BAESED ON TABLE
 403.3.1.1 FOR EACH USE OF SPACE IN THIS RESTAURANT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By medwards Date 2021-06-24 Time 10:17 Rev Time 0.00
Received By medwards Date 2021-06-24 Time 10:17 Sent To  
Notes
2021-06-24 10:18:012ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21030333
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH
 USE OF SPACE IN THIS TENANT SPACE BASED ON FBC M
 403.3.1.1 AND TABLE 403.3.1.1 NOT THE ARCHITECTURAL
 OCCUPANT COUNT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 12:27 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 11:05 Sent To  
Notes
2021-04-08 12:29:241ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030333
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ATTACH A STATEMENT ON THE MECHANICAL PLANS
 THAT THE KITCHEN HOOD, GREASE DUCT AND MAKEUP AIR WILL
 BE SUBMITTED UNDER A SEPARATE PERMIT AND MECHANICAL
 REVIEW.
  
 2) PLEASE ATTACH A STATEMENT ON THE MECHANICAL PLANS
 THAT THE REFRIGERATION WILL BE SUBMITTED UNDER A
 SEPARATE PERMIT AND PLAN REVIEW.
  
 3) AS THIS IS A CHANGE OF USE FROM MERCANTILE TO AN A-2
 PLEASE PROVIDE A COMPLETE MECHANICAL SIZING
 CALCULATION. FBC EC C403.2.1
  
 4) SHEET M-1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE 2020 FBC M 403.3.1.1 AND
 TABLE 403.3.1.1
  
 5) SHEET M-1: RTU-2 INDICATES A MAXIMUM 2000 CFM OF
 SUPPLY AIR, CALCULATING THE TOTAL OF EACH SUPPLY GRILLE
 IS 3475 CFM. PLEASE MAKE SURE THE TWO MATCH. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 14:26 Rev Time 0.00
Received By ccole Date 2021-06-25 Time 10:36 Sent To  
Notes
2021-06-28 14:26:56SEPARATE PERMIT REQUIRED FOR THE GREASE INTERCEPTOR.

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-14 Cont ID  
Sent By ccole Date 2021-04-14 Time 17:45 Rev Time 0.00
Received By ccole Date 2021-04-14 Time 13:07 Sent To  
Notes
2021-04-14 17:46:121ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21030333
 4/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-00: THE DRAWING INDEX SHOWS MANY
 ARCHITECTURAL PLANS THAT HAVE NOT BEEN UPLOADED FOR
 REVIEW. PLEASE PROVIDE THE PLANS AND ALSO REVISE THE
 INDEX TO INCLUDE THE MEP PLANS- SECTION 107.2.1 WPB.
  
 2) A-00 & P-PLANS: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC P.
 PROVIDE A SCHEDULE THAT LISTS THE NUMBER OF REQUIRED
 AND THE NUMBER OF PROVIDED FIXTURES FOR THE A2
 OCCUPANCY. PLEASE REFER TO SECTION 410.4 FBC P AND NOTE
 THAT A DRINKING FOUNTAIN IS REQUIRED UNLESS IT IS NOTED
 ON THE PLAN THAT DRINKING WATER WILL BE PROVIDED FREE
 OF CHARGE.
  
 3) ACCESSIBLE PLUMBING FIXTURE DETAILS REQUIRED PER FBC
 ACC:
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 4) P-1: BASED ON SECTION 1003.3.1 FBC P. THE HAND SINKS
 AND FLOOR SINK UNDER THE ICE MACHINE SHALL NOT DRAIN
 INTO THE GREASE WASTE LINE- PLEASE CORRECT THE PLAN.
  
 5) P-1: HYDROMECHANICAL GREASE INTERCEPTORS SHALL BE
 SIZED IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.5 FBC P. PLEASE INDICATE THE SIZING
 METHOD USED AND HOW THE NUMBER OF MEALS AND LBS. PER
 MEAL WERE DETERMINED.
  
 6) P-1: THE SAMPLING PORT DETAIL SHOWING A SANITARY
 CROSS WITH SUMP WHICH IS NOT ACCEPTABLE. PLEASE PROVIDE
 A SAMPLING PORT DETAIL IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.3.5 FBC P.
  
 7) P-1 & P-3: PLEASE PROVIDE A PLUMBING FIXTURE
 SCHEDULE LISTING THE MAKES AND MODELS OF THE ACCESSIBLE
 TOILET ROOM FIXTURES- SECTIONS 412, 419, & 425 FBC P.
  
 8) P-1 & P-3: PROVIDE A KITCHEN EQUIPMENT PLAN AND
 CORRELATING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
  
 9) P-2: THE BRANCH DRAIN CONNECTIONS FROM THE FLOOR
 SINKS BELOW THE 3-COMPARTMENT SINK AND ICE MAKER ARE
 NOT SHOWN IN THE SANITARY ISOMETRIC- SECTION 704 FBC P.
  
 10) P-1 & P2: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES IN COMPLIANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. IF MIXING VALVES ARE USED UNDER
 THE SINKS PLEASE PROVIDE AN INSTALLATION DETAIL.
  
 11) P-3: PROVIDE THE MAKE AND MODEL AND EFFICIENCY
 RATING OF THE NEW WATER HEATER- TABLE C404.2 FBC EC.
  
 12) P-3: PROVIDE AN INDIRECT WASTE DETAIL FOR THE FLOOR
 SINKS- SECTIONS 802.1.1 & 802.3.
  
 13) P-1: PROVIDE THE TYPES OF FLOOR AND WALL, SURROUND
 MATERIAL TO BE USED AT THE MOP SINK. PLEASE NOTE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT
 LESS THAN 4 FEET SHALL BE PROVIDED- SECTION 1210.2.2
 FBC B.
  
 14) P-1: THE PLAN SHOWS AN LP TANK BLOCKING ACCESS TO
 THE SANITARY DRAIN/SEWER JUNCTION CLEANOUT- SECTION
 708.1.10 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By ccole Date 2021-06-28 Time 14:28 Rev Time 0.00
Received By ccole Date 2021-06-28 Time 14:28 Sent To  
Notes
2021-06-28 14:29:19SEPARATE PERMIT REQUIRED FOR THE GREASE INTERCEPTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-28 Cont ID  
Sent By medwards Date 2021-07-28 Time 08:28 Rev Time 0.00
Received By medwards Date 2021-07-28 Time 08:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 15:35 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 15:31 Sent To  
Notes
2021-07-21 15:36:32PLEASE PROVIDE DIGITAL SIGNATURES FOR THE FOLLOWING
 SHEETS: P-1, P-2, P-3.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By medwards Date 2021-06-24 Time 10:19 Rev Time 0.00
Received By medwards Date 2021-06-24 Time 10:19 Sent To  
Notes
2021-06-24 10:29:46PLEASE PROVIDE THE DIGITAL SIGNATURE FOR M-1, P-3, P-2,
 P-1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 12:35 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 12:35 Sent To  
Notes
2021-04-08 12:38:37MR. NELSON FEDERICO WALTERS MUST USE A THIRD PARTY
 VERIFICATION FOR HIS SIGNATURES.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By rthermid Date 2021-06-22 Time   Rev Time 0.00
Received By rthermid Date 2021-06-22 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-14 Cont ID  
Sent By rthermid Date 2021-05-14 Time   Rev Time  
Received By rthermid Date 2021-05-14 Time   Sent To I
Notes
2021-05-14 10:15:52ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 5/14/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING THE
 LOCATION OF THE NEW BUILDOUT AND THE SETBACKS TO ALL
 PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  