Plan Review Details - Permit 21030277
Plan Review Stops For Permit 21030277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 15:12 Rev Time 0.00
Received By rmcphers Date 2021-03-18 Time 15:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-12 Cont ID  
Sent By rmcphers Date 2021-03-12 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2021-03-12 Time 15:23 Sent To  
Notes
2021-03-12 15:37:05ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL ROOFING SYSTEM CHOSEN HAS A MAXIMUM
 DESIGN PRESSURE OF (-97.5) - WIND ZONE 3 FOR EXPOSURE
 "C" REQUIRES A PRESSURE OF (-108.17) 2020 FBC TABLE
 R301.2(2) - PLEASE PROVIDE ADDITIONAL ATTACHMENT
 DETAILS FROM A QUALIFIED DESIGN PROFESSIONAL PER NOTE
 NUMBER 9 ON THE PRODUCT APPROVAL.
  