| Plan Review Stops For Permit 21030263 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-04-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-04-05 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-04-05 |
Time |
17:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-03-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-03-10 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-03-10 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2021-03-10 12:00:20 | SUITE 1400 IS NOT IN OUR GIS SYSTEM, PLEASE PROVIDE A | | | SITE PLAN SHOWING THE LOCATION OF THE SUITE AS WELL AS | | | A WHOLE FLOOR PLAN SHOWING ALL THE SUITES NUMBERS ON | | | THE FLOOR. THE DRAWINGS INDICATE THAT THE SUITE IS ON | | | THE 12TH FLOOR, IS THIS CORRECT? PLEASE EMAIL | | | [email protected] WITH RESPONSES. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
N |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-07 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2021-05-07 09:34:00 | NO DEMO - NEW BUILDING BUILDOUT |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-13 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-13 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2021-04-13 10:37:12 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-30 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-30 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2021-03-30 09:36:38 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-07 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-13 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-13 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-30 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-30 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2021-03-30 09:35:37 | INTERIOR OFFICE BUILDOUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | CORRECTIONS NEEDED- FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE COFFEE ROOM SINK TO COMPLY WITH FBC | | | 606.2 CLEAR FLOOR SPACE. | | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND | | | DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE | | | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST | | | CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES | | | UNDER LAVATORIES AND SINKS. ALSO SHOW THE TURNING SPACE | | | IN THE COFFEE ROOM THAT ALLOWS THE SINK UNDER COUNTER | | | FLOOR SPACE TO WORK. FBC 304 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-04-30 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-30 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-30 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-04-15 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-15 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-15 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-03-25 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-03-25 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-03-24 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2021-03-25 10:08:52 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | | 7TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | | | 1) PLEASE PROVIDE PANEL SCHEDULE FOR PANEL H14 FBC 107 | | | | | | END OF COMMENTS | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR | | | MS | | | | | | ENRIQUE QUINONEZ P.E. | | | ELECTRICAL PLANS EXAMINER | | | DEVELOPMENT SERVICES | | | CITY OF WEST PAM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | | 561-805-6746. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-03-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-03-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-03-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2021-03-12 11:10:13 | FIRE PROVISO: | | | * CARD READER INSTALLATION SHALL BE SUBMITTED UNDER | | | SEPARATE PERMIT | | | AND SHOP DRAWINGS AND COMPLY WITH THE REQUIRMENTS OF | | | NFPA101, | | | CH 7 MEANS OF EGRESS WHERE APPLICABLE. | | | | | | * THERE ARE INDICATIONS OF FIRE ALARM DEVICES. | | | ANY WORK ON THE FIRE ALARM SHALL BE DONE UNDER SEPARATE | | | PERMIT AND SHOP DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-23 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-21 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-07 |
Time |
15:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-30 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-10 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-30 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-30 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-04-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-16 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-16 |
Time |
05:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-26 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-26 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2021-03-26 11:12:25 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030263 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.01: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS | | | BASED ON TABLE 403.3.1.1 NOT THE ARCHITECTS | | | CALCULATIONS OF NUMBER OF PEOPLE IN THE SPACE. FBC M | | | SECTION 403.3.1.1 | | | | | | 2) PLEASE SHOW THE CONDENSATE DRAIN PIPING ON THE | | | MECHANICAL DRAWING. PLEASE INCLUDE THE TYPE OF MATERIAL | | | USED, THE LOCATION OF THE APPROVED DRAIN, THE SLOPE OF | | | THE PIPING, SUPPORTING OF THE PIPING, AND THE SIZE OF | | | THE PIPING. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-04-20 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-04-20 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-04-20 |
Time |
18:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-03-23 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2021-03-23 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2021-03-23 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2021-03-23 16:18:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1 | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 21030263 360 S ROSEMARY AVE # 1400 | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS | | | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW | | | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL | | | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST | | | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW | | | APPROVAL. | | | | | | 1.DRAWING A0.01 LIFE SAFETY IS MISSING FROM PROJECT | | | DOCS. PER WPB FBC 107.2.1, PROVIDE. | | | 2.PER WPB FBC 107.2.1, SHOW CLEAR FLOOR SPACES FOR | | | ACCESSIBLE SINKS SHOWING COMPLIANCE WITH FBC ACC | | | SECTION 305. | | | 3.PER WPB FBC 107.2.1, PROVIDE A WATER RISER DIAGRAM. | | | SHOW ALL VALVES, REQUIRED WATER HAMMER ARRESTORS, | | | FILTERS AND REQUIRED BACKFLOW PREVENTORS. PROVIDE A | | | SCHEDULE FOR WATER HAMMER ARRESTORS, FILTERS AND | | | BACKFLOW PREVENTORS. NOTE BACKFLOW PREVENTORS SHALL BE | | | SPECIFIED AND MODEL NUMBERS SHALL REFLECT LEAD | | | CONSTRUCTION. PROVIDE VALVED OUTLET WITH BACKFLOW | | | PREVENTOR FOR COFFEE MAKER. PROVIDE BACKFLOW PREVENTOR | | | FOR ICE MACHINE. REGARDING BACKFLOW PREVENTORS, REFER | | | TO FBC PL 608. | | | 4.REFERENCE PLAN SHEET P1.01: NON PRESSURE PIPING PLAN | | | (SANITARY); PER FBC PL 802.4, READY ACCESS SHALL BE | | | PROVIDED TO WASTE RECEPTORS (FLOOR SINK). SEE FBC PL | | | CHAPTER 2, DEFINITIONS; READY ACCESS. THAT WHICH | | | ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO BE | | | DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR | | | MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND | | | WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR | | | SIMILAR DEVICE. PER WPB FBC 107.2.1, CONFIRM THAT FLOOR | | | SINK IS READILY ACCESSIBLE. | | | 5.REFERENCE PLAN SHEET P2.01: APPLICABLE CODES AND | | | STANDARDS. PER WPB FBC 107.2.1 REPLACE 2017 WITH 2020 | | | TO REFLECT THE CURRENT EDITION OF THE FLORIDA BUILDING, | | | PLUMBING AND MECHANICAL CODES. | | | | | | PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, | | | PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S | | | SPECIFICATION AND INSTALLATION GUIDE FOR THE NEW ICE | | | MACHINE FURNISHED BY OTHERS. DOCUMENT SHALL BE | | | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL | | | INSPECTION. MACHINE SHALL BE INSTALLED IN COMPLIANCE | | | WITH ALL REQUIREMENTS OF FBC PL PRIOR TO FINAL | | | INSPECTION (SEE WPB FBC 111.1). PROCEED AT YOUR OWN | | | RISK. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | MOBILE 561-243-0882 | | | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND | | | THURSDAYS |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-07 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-07 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-04-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-04-13 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-04-13 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2021-04-13 10:29:16 | ARCHITECTURAL DRAWINGS ADDED ON 4/6/2021 = SIGNED AND | | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-26 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-26 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|