| 2021-04-01 14:32:29 | 04/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-0, UNDER CODES, YOU ONLY REFERENCE |
| | BUILDING CODE 202, WHICH IS ONLY ONE VOLUME. PLEASE |
| | INCLUDE THE PLUMBING COMMERCIAL AND ACCESIBILTIES CODES |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3 |
| | APPLICATION OF REFERENCES. |
| | |
| | 2. ON SHEET A-1; |
| | A. IT SHOWS A SINK IN AN OPEN AREA THAT SHALL COMPLY |
| | WITH THE ACCESSIBILITY CODE. PLEASE SHOW THE CLEAR |
| | FLOOR SPACE AND DIMENSION PLUS PROVIDE CABINET DETAIL |
| | SHOWING THE SINK AND OR LAVS HEIGHT OF 34" INCHES |
| | MAXIMUM PER THE 2017 FBC ACC SEC. 606.3. |
| | |
| | B. THE TOILET IS OF THE WALL SAYS 1"- 4", AND THERE IS |
| | A RANGE TO 1'- 6" PLEASE ADD IT PER THE 2020 FBC ACC. |
| | SEC. 604.2 LOCATION. |
| | |
| | C. ON THE DIMENSION OF THE HORIZONTAL GRAB BARS, PLEASE |
| | SHOW THE CENTERLINE PER THE 2020 FBC ACC. 604.5.1 SIDE |
| | WALL AND 604.5.2 REAR. |
| | |
| | D. ON THE REAR WALL, PLEASE SHOW THE REAR GRAB BAR 12" |
| | FROM THE CENTER OF THE TOILET PER THE 2020 FBC ACC. |
| | SEC. 604.5.2. |
| | |
| | E. PLEASE REMOVE OR STRIKE THROUGH THE WATER COOLER |
| | DETAIL THAT DOES NOT PERTAIN TO THIS SET OF PLANS FOR |
| | THIS STRUCTURE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION |
| | ON THE OPEN SIDE ON THE FIRST DETAIL IN THE TYPE TOILER |
| | ROOM ELEVATION PER THE 2017 FBC SEC. 604.6 FLUSH |
| | CONTROLS. |
| | |
| | G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5. |
| | |
| | 3. ON SHEET A-3; |
| | |
| | A. IT SHOWS ON SIDE ELEVATION THE TOILET PAPER |
| | DISPENSER AT 36? FROM THE REAR WALL. PLEASE SHOW TOILET |
| | PAPER DISPENSERS 7" INCHES MINIMUM AND 9" INCHES |
| | MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| | CENTERLINE DISPENSER PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | 4. ON SHEET P-2; |
| | |
| | A. IN GENERAL, PLUMBING NOTES NUMBER 18 REFERS TO 2014. |
| | PLEASE CORRECT TO CURRENT CODE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | B. THE KITCHEN AND THE MOP SINK CANNOT DISCHARGE INTO |
| | THE BATHROOM GROUP'S WET VET; IT MUST BE DOWNSTREAM PER |
| | THE 2017 FBC SECTION R3108.1 HORIZONTAL WET VENT |
| | PERMITTED. |
| | |
| | C. IN YOUR FLOW RATE CONSUMPTION, IT REFERS TO P |
| | 2903.2A. THIS IS NOT A REFERENCE CODE. PLEASE CLARIFY |
| | AND REMOIVE DISHWASHER AHD WASHING MACHINE THAT IS NOT |
| | ON THIS STRUCTURE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P |
| | 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 5. ON SHEET, LS-1 SHOWS THE MOP SINK IN A DIFFERENT |
| | LOCATION. PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |