Plan Review Details - Permit 21030182
Plan Review Stops For Permit 21030182
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-14 Cont ID  
Sent By jwitmer Date 2021-04-14 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2021-04-14 Time 09:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-03-18 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2021-03-18 Time 11:14 Sent To  
Notes
2021-03-18 11:34:04TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-04-14 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2021-04-14 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By jwitmer Date 2021-03-18 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2021-03-18 Time 11:14 Sent To  
Notes
2021-03-18 11:32:54WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21031082
 ADD: 525 S. FLAGLER DR. SUITE # 19A
 CONT: ALBRIGHT CONSTRUCTION
 TEL: 561-547-7433
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDI2) NG CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 18TH/ 2021
 ACTION: DENIED
  
 1) THE SPEC SHEET FOR SUPER SAM 125 UNDERLAYMENT SOUND
 PROOFING IS NOTHING MORE THAN A SALES BROCHURE. TO DATE
 WE DO NOT HAVE SUPER SAM 125 IN OUR FOLDER OF APPROVED
 FLOOR UNDERLAYMENT SYSTEMS.
 THE CITY OF WEST PALM BEACH REQUIRES THE ACTUAL TEST
 REPORTS LISTED BELOW.
  
 FLOOR INSULATION (FBC-B 2020). FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2)FLOOR PLAN-PROPOSED CONDITIONS. THE FLOOR PLAN IS
 SILENT AS TO THE TYPE OF BACKER BOARD FOR THE SHOWER
 AND TUB FOR ALL BATHROOMS.
 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURERS RECOMMENDATIONS.
  
 3) FOR FUTURE REFERENCE. THE DETAIL DRYWALL TO CEILING
 IS DRAWN BACKWARDS. THE TWO FLANGES SHOULD BE DRAWN
 NEXT TO THE CONCRETE CEILING SO THEY CAN BE SHOT INTO
 THE CONCRETE AND THE RAISED WIDE CENTER SECTION GIVE
 THE DRYWALL HANGER SOMETHING TO SECURE THE DRYWALL TOO.
  
 4) IF ALBRIGHT CONSTRUCTION IS TRYING TO GET NO FEE
 SUB-CONTRACTOR PERMITS THEY MUST BE SUBMITTED AT TIME
 OF THE MAIN BUILDING PERMIT, A LIST DOES NOT SUFFICE.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-09 Cont ID  
Sent By equinone Date 2021-04-09 Time 09:00 Rev Time 0.00
Received By equinone Date 2021-04-09 Time 08:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-10 Cont ID  
Sent By equinone Date 2021-03-10 Time 09:46 Rev Time 0.00
Received By equinone Date 2021-03-10 Time 09:30 Sent To  
Notes
2021-03-10 09:46:17CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL
 SUFFICE)
  
 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN
 EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1
  
 3) ALL COUNTERTOP KITCHEN RECEPTACLES MUST BE GFCI.
 PLEASE INDICATE THIS REQUIREMENTS ON DRAWING. NEC 210
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By pleduc Date 2021-04-08 Time   Rev Time 0.00
Received By pleduc Date 2021-04-08 Time 16:05 Sent To  
Notes
2021-04-08 16:06:01FIRE PROVISO:
  
 * FIRE SPRINKLER PROTECTION REQUIRES MODIFICATION.
  
 * PROTECT FIRE SPRINKLER HEADS AND FIRE ALARM DEVICES
 THROUGHOUT . DO NOT PAINT OVER FS HEADS OR FA DEVICES
  
 *ANY WORK ON THE FS OR FA SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-08 Cont ID  
Sent By pleduc Date 2021-03-08 Time   Rev Time 0.00
Received By pleduc Date 2021-03-08 Time 10:38 Sent To  
Notes
2021-03-08 10:40:26FIRE PROVISO:
  
 * FIRE SPRINKLER PROTECTION REQUIRES MODIFICATION.
  
 * PROTECT FIRE SPRINKLER HEADS AND FIRE ALARM DEVICES
 THROUGHOUT . DO NOT PAINT OVER FS HEADS OR FA DEVICES
  
 *ANY WORK ON THE FS OR FA SYSTEM SHALL BE DONE UNDER
 SEPARATE PEMRIS AND SHPR DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By lmarchan Date 2021-04-23 Time 08:17 Rev Time 0.00
Received By lmarchan Date 2021-04-06 Time 12:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-19 Cont ID  
Sent By pvalenti Date 2021-03-19 Time 08:54 Rev Time 0.00
Received By pvalenti Date 2021-03-04 Time 17:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-03-19 Cont ID  
Sent By pvalenti Date 2021-03-19 Time 08:54 Rev Time 0.00
Received By pvalenti Date 2021-03-19 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By medwards Date 2021-04-15 Time 13:42 Rev Time 0.00
Received By medwards Date 2021-04-15 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-03-16 Cont ID  
Sent By medwards Date 2021-03-16 Time 16:04 Rev Time 0.00
Received By medwards Date 2021-03-16 Time 15:51 Sent To  
Notes
2021-03-16 16:05:38THIS WILL REQUIRE A MECHANICAL SUB PERMIT FOR THE
 MASTER BATH EXHAUST FAN CHANGE OUT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-22 Cont ID  
Sent By jesmith Date 2021-04-22 Time 08:36 Rev Time 0.00
Received By jesmith Date 2021-04-20 Time 16:48 Sent To  
Notes
2021-04-22 08:35:5521030182 525 S FLAGLER DR # 19A
  
 PLUMBING COMMENTS: APPROVED
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A SUB PERMIT SHALL BE APPLIED FOR BY A LICENSED
 PLUMBING CONTRACTOR AND SHALL BE IN PLACE PRIOR TO ANY
 PLUMBING WORK TO PROCEED.
  
 ALL THROUGH THE SLAB DRAINS TO REMAIN IN ORIGINAL
 LOCATIONS.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-03-18 Cont ID  
Sent By jesmith Date 2021-03-18 Time 15:30 Rev Time 0.00
Received By jesmith Date 2021-03-18 Time 12:35 Sent To  
Notes
2021-03-18 15:30:3621030182 525 S FLAGLER DR # 19A
  
 PLUMBING COMMENTS: APPROVED
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A SUB PERMIT SHALL BE APPLIED FOR BY A LICENSED
 PLUMBING CONTRACTOR AND SHALL BE IN PLACE PRIOR TO ANY
 PLUMBING WORK TO PROCEED.
  
 ALL THROUGH THE SLAB DRAINS TO REMAIN IN ORIGINAL
 LOCATIONS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By medwards Date 2021-04-06 Time 16:52 Rev Time 0.00
Received By medwards Date 2021-04-06 Time 16:51 Sent To  
Notes
2021-04-06 16:53:18ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By medwards Date 2021-03-05 Time 10:11 Rev Time 0.00
Received By medwards Date 2021-03-05 Time 10:06 Sent To  
Notes
2021-03-05 10:12:41ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 2 Status N Date 2021-04-22 Cont ID  
Sent By aaponte Date 2021-04-22 Time 17:56 Rev Time 0.00
Received By aaponte Date 2021-04-22 Time 17:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By elevesqu Date 2021-03-18 Time 09:44 Rev Time  
Received By elevesqu Date   Time   Sent To  
Notes
***NONE***