| Plan Review Stops For Permit 21030180 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-09-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-22 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-22 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2021-09-22 15:07:35 | ALL WINDOWS TO BE REPLACED ON THE FRONT STRUCTURE, 5107 | | | N FLAGLER DR ADDRESS IS OK. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-04-14 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-04-14 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-04-14 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2021-04-14 11:28:39 | WHICH UNIT ARE THE WINDOWS FOR UNTI 1,2,3 & 4 OR IS IT | | | FOR THE WHOLE BUILDING? PLEASE RESPOND TO | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-09-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-28 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-28 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2021-09-28 14:07:40 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | SLIDING GLASS DOOR IS FOR AN NON-IMPACT RATED DOOR. THE | | | DOOR SCHEDULE ON THE PLANS INDICATES AN IMPACT RATED | | | DOOR. PLEASE CLARIFY. FBC AMENDMENTS 107.2.1 (NOTE: IF | | | THIS IS A NON-IMPACT RATED DOOR, SUBMIT PRODUCT | | | APPROVALS AND AN INSTALLATION SCHEDULE FOR FOR THE | | | REQUIRED IMPACT PROTECTION DEVICES THAT WILL BE | | | INSTALLED.) | | | | | | 2) (PREVIOUS COMMENT NOT ADDRESSED. SPECIFY THE TOTAL | | | VALUE OF THE WORK. PROVIDE A COST BREAKDOWN.) THE VALUE | | | FOR THIS PROJECT OF $12,500 IS LOW FOR REPLACING (23) | | | SH WINDOWS, (9) SWING DOORS AND (1) SLIDING GLASS DOOR | | | WITH IMPACT RATED ONES. SUBMIT A COPY OF THE SIGNED | | | CONTRACT TO VERIFY. FBC 109.3 BUILDING PERMIT | | | VALUATION. FOR PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE | | | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, | | | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND | | | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; | | | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE | | | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET | | | BY THE BUILDING OFFICIAL. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-18 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-18 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2021-03-18 16:14:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS | | | AND THE MULLIONS ARE MISSING THE FLORIDA PRODUCT | | | APPROVAL COVERSHEETS. FBC 107.2.1 | | | | | | 2) THE PRODUCT APPROVALS FOR THE WINDOWS AND MULLIONS | | | ARE LABELED AS LOAD CALCULATIONS1 AND 2 IN PROJECTDOX. | | | PLEASE LABEL CORRECTLY. FBC 107.2.1 | | | | | | 3) CIRCLE THE ITEMS SUCH AS SIZE AND DESIGN PRESSURES | | | THAT APPLY TO THIS PROJECT IN THE PRODUCT APPROVALS. | | | FBC 107.2.1 | | | | | | 4) THIS IS A 4 UNIT CONDOMINIUM AND THE 2020 FBC AND | | | ASCE 7-16 APPLIES. SUBMIT REQUIRED COMPONENT AND | | | CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE | | | BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE | | | DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE | | | ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE | | | SUBMITTED. FS 471 & FAC 61G15 SUBMIT SIGNED AND SEALED | | | WINDLOAD DATA AND OPENING DESIGN PRESSURES FOR THIS | | | PROJECT. IT APPEARS THAT THIS PROJECT IS LOCATED IN | | | EXPOSURE CATEGORY D. FBC CHAPTER 16 | | | | | | 5) THE VALUE FOR THIS PROJECT OF $12,500 IS LOW FOR | | | REPLACING 19 SH WINDOWS AND 1 SLIDING GLASS DOOR WITH | | | IMPACT RATED ONES. SUBMIT A COPY OF THE SIGNED CONTRACT | | | TO VERIFY. FBC 109.3 BUILDING PERMIT VALUATION. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-10-20 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2021-10-20 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2021-10-20 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2021-10-20 14:59:07 | PROPERTY IS IN A HISTORIC DISTRICT-- WINDOWS ARE OK BUT | | | SLIDING GLASS DOOR IS NOT ARCHITECTURALLY COMPATIBLE. | | | FRENCH DOORS WOULD BE APPROPRIATE. | | | | | | QUESTIONS? CONTACT | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-03-17 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-03-17 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-03-17 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2021-03-17 11:58:44 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. PROVIDE WINDOW PRODUCT APPROVAL. | | | 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE | | | WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF | | | AT [email protected] TO REQUEST THE EXAMPLE. AT | | | MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND | | | THE PROPOSED WINDOWS EXTERIOR FRAME COLOR, GLASS | | | GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION | | | WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW | | | MARKED. | | | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | | 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE | | | ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND | | | MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL | | | WINDOWS. | | | 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED | | | WITH A MULLION OF MATCHING WIDTH AND PLACEMENT. IF THE | | | EXISTING MULLION IS NOT WOOD, A 4-INCH WIDE MULLION | | | WILL BE REQUIRED. | | | 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR. | | | ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR | | | WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS | | | MAY BE USED ON NON-STREET FACING BATHROOMS ONLY. | | | | | | AARON BORNGRABER, AICP | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-10-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-10-21 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-09-20 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-18 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-10 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-09-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-09-28 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-09-28 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-03-18 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-03-18 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2021-03-18 16:25:32 | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER | | | VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE | | | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS | | | REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER | | | FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 & | | | 61G15 | | | | | | |
|
|