Plan Review Details - Permit 21030180
Plan Review Stops For Permit 21030180
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By cpuell Date 2021-09-22 Time 15:06 Rev Time 0.00
Received By cpuell Date 2021-09-22 Time 15:06 Sent To  
Notes
2021-09-22 15:07:35ALL WINDOWS TO BE REPLACED ON THE FRONT STRUCTURE, 5107
 N FLAGLER DR ADDRESS IS OK.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-04-14 Cont ID  
Sent By cpuell Date 2021-04-14 Time 11:26 Rev Time 0.00
Received By cpuell Date 2021-04-14 Time 11:26 Sent To  
Notes
2021-04-14 11:28:39WHICH UNIT ARE THE WINDOWS FOR UNTI 1,2,3 & 4 OR IS IT
 FOR THE WHOLE BUILDING? PLEASE RESPOND TO
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-28 Cont ID  
Sent By rmcdouga Date 2021-09-28 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2021-09-28 Time 13:41 Sent To  
Notes
2021-09-28 14:07:40PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SLIDING GLASS DOOR IS FOR AN NON-IMPACT RATED DOOR. THE
 DOOR SCHEDULE ON THE PLANS INDICATES AN IMPACT RATED
 DOOR. PLEASE CLARIFY. FBC AMENDMENTS 107.2.1 (NOTE: IF
 THIS IS A NON-IMPACT RATED DOOR, SUBMIT PRODUCT
 APPROVALS AND AN INSTALLATION SCHEDULE FOR FOR THE
 REQUIRED IMPACT PROTECTION DEVICES THAT WILL BE
 INSTALLED.)
  
 2) (PREVIOUS COMMENT NOT ADDRESSED. SPECIFY THE TOTAL
 VALUE OF THE WORK. PROVIDE A COST BREAKDOWN.) THE VALUE
 FOR THIS PROJECT OF $12,500 IS LOW FOR REPLACING (23)
 SH WINDOWS, (9) SWING DOORS AND (1) SLIDING GLASS DOOR
 WITH IMPACT RATED ONES. SUBMIT A COPY OF THE SIGNED
 CONTRACT TO VERIFY. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By rmcdouga Date 2021-03-18 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2021-03-18 Time 16:01 Sent To  
Notes
2021-03-18 16:14:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS FOR THE SINGLE HUNG WINDOWS
 AND THE MULLIONS ARE MISSING THE FLORIDA PRODUCT
 APPROVAL COVERSHEETS. FBC 107.2.1
  
 2) THE PRODUCT APPROVALS FOR THE WINDOWS AND MULLIONS
 ARE LABELED AS LOAD CALCULATIONS1 AND 2 IN PROJECTDOX.
 PLEASE LABEL CORRECTLY. FBC 107.2.1
  
 3) CIRCLE THE ITEMS SUCH AS SIZE AND DESIGN PRESSURES
 THAT APPLY TO THIS PROJECT IN THE PRODUCT APPROVALS.
 FBC 107.2.1
  
 4) THIS IS A 4 UNIT CONDOMINIUM AND THE 2020 FBC AND
 ASCE 7-16 APPLIES. SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15 SUBMIT SIGNED AND SEALED
 WINDLOAD DATA AND OPENING DESIGN PRESSURES FOR THIS
 PROJECT. IT APPEARS THAT THIS PROJECT IS LOCATED IN
 EXPOSURE CATEGORY D. FBC CHAPTER 16
  
 5) THE VALUE FOR THIS PROJECT OF $12,500 IS LOW FOR
 REPLACING 19 SH WINDOWS AND 1 SLIDING GLASS DOOR WITH
 IMPACT RATED ONES. SUBMIT A COPY OF THE SIGNED CONTRACT
 TO VERIFY. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2021-10-20 Cont ID  
Sent By amhamilt Date 2021-10-20 Time 14:57 Rev Time 0.00
Received By amhamilt Date 2021-10-20 Time 14:57 Sent To  
Notes
2021-10-20 14:59:07PROPERTY IS IN A HISTORIC DISTRICT-- WINDOWS ARE OK BUT
 SLIDING GLASS DOOR IS NOT ARCHITECTURALLY COMPATIBLE.
 FRENCH DOORS WOULD BE APPROPRIATE.
  
 QUESTIONS? CONTACT
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By aborngra Date 2021-03-17 Time 11:58 Rev Time 0.00
Received By aborngra Date 2021-03-17 Time 11:58 Sent To  
Notes
2021-03-17 11:58:44THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. PROVIDE WINDOW PRODUCT APPROVAL.
 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS EXTERIOR FRAME COLOR, GLASS
 GLAZING, LITE PATTERN, MUNTIN PROFILE AND MULLION
 WIDTH. A PHOTO OF EACH ELEVATION WITH EACH WINDOW
 MARKED.
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT. IF THE
 EXISTING MULLION IS NOT WOOD, A 4-INCH WIDE MULLION
 WILL BE REQUIRED.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-21 Cont ID  
Sent By lmarchan Date 2021-10-21 Time 10:03 Rev Time 0.00
Received By lmarchan Date 2021-09-20 Time 07:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-18 Cont ID  
Sent By rmcdouga Date 2021-03-18 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2021-03-10 Time 14:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-28 Cont ID  
Sent By rmcdouga Date 2021-09-28 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2021-09-28 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By rmcdouga Date 2021-03-18 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2021-03-18 Time 16:02 Sent To  
Notes
2021-03-18 16:25:32ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  